SECTION [26 09 16.10][16290] ELECTRICAL CONTROLS AND RELAYS Various Electrical Sub-Components (e.g.TeSys T™) by Schneider Electric Schneider Electric Editor’s Note: This guide specification is written in accordance with the Construction Specifications Institute (CSI) Master Format. This section must be carefully reviewed and edited by the architect or the engineer to meet the requirements of the project. Coordinate this section with other specification sections within the Contract Documents and Drawings. In order to properly use / edit this document, show formatting and hidden text by selecting ¶ on the menu or by typing (Ctrl+*) simultaneously. Except for these introductory paragraphs, green hidden text will not print. Text in red is optional. Red text in [brackets] denotes multiple options where one or more should be chosen. All red text should be edited and changed to black for final project conformation. In addition, these introductory paragraphs should be deleted or changed to hidden text. This specification may be used in whole or in part. It is intended that this document specify subcomponent products to be referenced by other specification sections or drawings for the furnishing of completed assemblies or systems. The Part 2 – Product subsections may also be copied into other specification sections in lieu of including this specification section in the Contract Documents. PART 1 - GENERAL 1.1 SUMMARY A. Scope: Provide labor, material, equipment, related services, and supervision required, including, but not limited to, manufacturing, fabrication, configuration and installation for electrical controls and relays as required for the complete performance of the Work, as shown on the Drawings, as specified herein, and as specified elsewhere for the assemblies or systems comprised of the components specified herein. B. Related Sections: Related sections include, but shall not be limited to, the following: 1.2 1. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 2. Applicable general requirements for electrical Work specified within Division 26 Specification Sections apply to this Section. REFERENCES A. General, Publications: The publications listed below form a part of this Specification to the extent referenced. The publications are referred to in the text by the basic designation only. The edition/revision of the referenced publications shall be the latest date as of the date of the Contract Documents, unless otherwise specified. 1. National Fire Protection Agency (NFPA) a. NFPA 70 National Electrical Code® (NEC) b. NFPA 79 Electrical Standard for Industrial Machinery 2. CSA® C22.2 No. 14-M91 – Industrial Control Equipment 3. International Electrotechnical Commission (IEC) a. IEC 61000 Electromagnetic Compatibility b. IEC 61131-3 Programming Languages c. IEC 61850 Electromagnetic Compatibility 4. NEMA a. NEMA 250 – Enclosures for Electrical Equipment 5. Underwriter Laboratories (UL) Section [26 09 16][16290] Electrical Controls and Relays Page 1 05/12/2017 Schneider Electric a. b. c. 6. 1.3 UL® 50 – Enclosures for Electrical Equipment UL 508 – Industrial Control Equipment UL 991 – Safety Tests for Safety Related Controls Employing Solid State Devices IBC® – International Building Code® SUBMITTALS A. 1.4 General: Submittals shall be in accordance with the requirements of Section [01 33 00][01300] Submittals and Section [26 00 00][1600] Electrical, in addition to those specified herein. 1. Submit sufficient information to determine compliance with the Contract Documents. Identify submittal data with the specific equipment tags and/or service descriptions to which they pertain. Submittal data shall be clearly marked to identify the specific model numbers, options, and features of equipment and work proposed. 2. Deviations from the Contract Documents shall be indicated within the submittal. Each deviation shall reference the corresponding drawing or specification number, show the Contract Document requirement text and/or illustration, and shall be accompanied by a detailed written justification for the deviation. QUALITY ASSURANCE A. B. 1.5 Manufacturer Qualifications: Manufacturer shall be a firm engaged in the manufacture of specified products of types and sizes required, and whose products have been in satisfactory use in similar service for a minimum of ten years. 1. The manufacturer shall have a valid ISO 9001 certification and an applicable quality assurance system that is regularly reviewed and audited by a third party registrar. Manufacturing, inspection, and testing procedures shall be developed and controlled under the guidelines of the quality assurance system. 2. The manufacturer shall have the ISO 14001 Environment Certification and shall supply the Product Environmental Profile (P.E.P) upon request of the Engineer. 3. The manufacturer or their representative shall have service, repair, and technical support services available 24 hours 7 days a week basis. All work performed and all materials used shall be in accordance with the National Electrical Code, and with applicable local regulations and ordinances. Process controllers, assemblies, materials, and equipment shall be listed and labeled by Underwriter’s Laboratories or by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. DELIVERY, STORAGE, AND HANDLING A. Prior to delivery to the Project site, ensure that suitable storage space is available to store materials in a well ventilated area protected from weather, moisture, soiling, extreme temperatures, humidity, and corrosive atmospheres. Materials shall be protected during delivery and storage and shall not exceed the manufacturer stated storage requirements. As a minimum, store indoors in clean, dry space with uniform temperature to prevent condensation. Protect process controllers from exposure to dirt, fumes, water, corrosive substances, and physical damage. In addition, protect process controllers from all forms of electrical and magnetic energy that could reasonably cause damage. B. Deliver materials to the Project site in supplier’s or manufacturer’s original wrappings and containers, labeled with supplier’s or manufacturer’s name, material or product brand name, and equipment tag number or service name as identified within the Contract Documents. Section [26 09 16][16290] Electrical Controls and Relays Page 2 05/12/2017 Schneider Electric C. 1.6 Inspect and report any concealed damage or violation of delivery storage, and handling requirements to the [Engineer][Contract Manager]. WARRANTY A. General: Refer to [Section 01 77 00 - Closeout Procedures] [Section 01770 - Closeout Procedures]. B. Additional Owner Rights: The warranty shall not deprive the Owner of other rights the Owner may have under other provisions of the Contract Documents and shall be in addition to and run concurrent with other warranties made by the Contractor under requirements of the Contract Documents. C. Extended Warranty: The manufacturer shall provide a [2] year warranty for the processors, input/output (I/O) systems, power supplies, racks, and communication interface products. The warranty period shall commence on the date of project Substantial Completion. The terms of the warranty shall provide for replacement of defective components, free of charge, at any time during the warranty period. 1.7 SPECIAL TOOLS AND SPARE PARTS A. Any manufacturer specific special tool, not normally found in an electrician’s toolbox, required to remove and install recommended or furnished spare parts shall be furnished. [At a minimum the following shall be provided: 1. Provide a minimum of [one] communication interface cable for each type of cable required to connect a PC-based computer to the devices specified herein for configuration and programming.] PART 2 - PRODUCTS 2.1 General Requirements A. 2.2 Products specified herein shall be the product of a single manufacturer. Products and manufacturers specified are to establish a standard of quality for design, function, materials, and appearance. Products shall be modified as necessary by the manufacturer for compliance with requirements. Intelligent Motor Protection Relay (IMPR) A. Basis-of-Design Product: Subject to compliance with requirements, provide TeSys T, by Schneider Electric. B. Provide the following specified product and manufacturer without exception, unless approved as a substitute by addendum to the Contract Documents prior to the bid date: C. 1. TeSys T by Schneider Electric USA, Inc. 2. [2nd manufacturer] 3. [3rd manufacturer] Intelligent Motor Protection Relays (IMPRs) shall provide protection, metering, control, monitoring, and historical logging for 1ɸ and 3ɸ AC induction motors up to 100 A using integral current transformers (CTs) or up to 810 A using inputs from external CTs. IMPRs shall have selectable trip classes from 5 to 30. The thermal overload trip curve shall be selectable between inverse (I²t) or definite time (Ixt) curves. IMPRs shall have an IP20 rated enclosure for protection against direct contact and shall operate in Section [26 09 16][16290] Electrical Controls and Relays Page 3 05/12/2017 Schneider Electric temperature ranges of -4°F (-20°C) to 140°F (60°C) up to an altitude of 6560 ft (2000 m) without derating. D. IMPRs shall conform to or exceed the applicable requirements of the following standards; provided, that wherever the provisions of said publications are in conflict with the requirements specified herein, the more stringent requirements shall apply: a. Certifications: UL, CSA, ABS, DNV b. Conform to Standards: IEC 60947-4-1, UL 508, CSA C22-2 No. 14, IACS E10 c. Voltage Sag: 70 % of U for 500 ms conforming to EN/IEC 61000-4-11 E. Monitoring and Controls: 1. LED status indicators for power, alarm and communications. 2. Test / reset pushbutton 3. The IMPR shall be capable of providing protection and / or alarm setpoints that occur prior to protection setpoint actuation. a. Thermal overload b. Current phase imbalance c. Current phase loss d. Current phase reversal e. Long start f. Jam (locked rotor during run) g. Undercurrent h. Overcurrent i. Ground current j. Motor temperature sensor k. Rapid cycle lockout l. Voltage phase imbalance m. Voltage phase loss n. Voltage phase reversal o. Undervoltage p. Overvoltage q. Voltage load shedding r. Underpower s. Overpower t. Under power factor u. Over power factor 4. The IMPR shall have the ability to monitor the following parameters: a. Line Currents @ 1% accuracy b. Ground current @ 5% measured accuracy and 5-15% calculated non-measured accuracy c. Average Current @ 1% accuracy d. Current Phase Imbalance e. Thermal capacity Level f. Motor Temperature Sensor g. Protection Fault Counts h. Protection Warning counts i. Diagnostic Fault counts j. Motor Control Function counts k. Fault History l. Internal watchdog results m. Controller Internal Temperature n. Temperature Sensor Connections o. Current Connections p. Voltage Connections q. Control Commands (start, stop, run, check back and stop check back) r. Control configuration checksum s. Communication loss Section [26 09 16][16290] Electrical Controls and Relays Page 4 05/12/2017 Schneider Electric t. u. v. w. x. y. z. a. b. c. d. e. f. g. h. i. F. 5. Inputs a. Ground current sensor b. Motor temperature sensor c. [6][10] discrete inputs (100-240 VAC) d. 1ɸ or 3ɸ current transformer inputs (integral sensing without CTs 0.4 to100 A) e. [1ɸ or 3ɸ voltage inputs for enhanced functionality] 6. Outputs a. 1 Fault DPST relay output (5 A @ 250 VAC or 5 A @ 30 VDC) b. 3 programmable SPDT relay outputs (5A @ 250 VAC 5 A @ 30 VDC) 7. Preconfigured and Custom Logic Programming a. The IMPR shall contain five pre-defined control modes: overload, independent, reverser, 2step, 2-speed and a custom mode defined by the user using function block or structured text programming languages. When custom programming of the IMPR is used, PC-based programming software and application programs shall be provided on electronic media. b. The IMPR shall be capable of being set to compensate for a motor cooled with an auxiliary fan through an internal algorithm. Communications: IMPRs shall support secure industrial networking for implementation of remote monitoring, control, and configuration. The IMPR shall have one serial port provided for device configuration and/or HMI device connection. An additional port(s) shall be provided for industrial network communications using [Ethernet Modbus TCP / Ethernet IP][Modbus][Profibus DP][DeviceNET][CANopen] communication protocol. The product family of the IMPR shall be capable of providing communications using all of the following communication protocols: Ethernet Modbus TCP, Ethernet IP, Modbus, Profibus DP, DeviceNET, and CANopen; so that commonality of devices may be achieved regardless of the protocol needed. 1. G. Motor control states motor starter/LO1 starts/ LO2 starts Operating time Motor starts per hour Last start max current Last start time Time to trip Time to reset [Frequency Line to Line Voltage @ 1% accuracy Line Voltage Imbalance Average Voltage Power Factor @ 3% accuracy Active Power @ 5% accuracy Reactive Power @ 5% accuracy Active Power Consumption Reactive Power Consumption] Two Ethernet ports shall be provided for networking devices in a star, daisy chain or ring topology. Ethernet ports shall be provided with Rapid Spanning Tree Protocol (RSTP) and Broadcast Storm Protection. The Ethernet port shall support built-in Java-free webpages or PCbased software for monitoring and configuration. Operator Interface: 1. [Control Operator Unit: A Control Operator Unit (CU) shall be provided [for each IMPR][where specified or indicated] to provide an operator interface for the configuring, monitoring and controlling a single IMPR. The CU shall include but not be limited to the following features: a. Certifications: UL, CSA b. Conform to Standards: IEC 61131-2m YK 60947-4-1m CSA C22.2 No. 60947-4-1 c. Capable of being IP 54 (NEMA 12) front panel mounted or portable standalone device as specified or indicated d. Backlit LCD Screen with 70,000 hour life Section [26 09 16][16290] Electrical Controls and Relays Page 5 05/12/2017 Schneider Electric e. f. 2. H. Run, Stop, Local-Remote, and Reset Pushbuttons Run, Local and Remote LED Status Indication Lights] [Operator Interface Unit: An Operator Interface Unit (OIT) shall be provided [where specified or indicated][for each system of enclosed IMPRs (e.g. MCC, control panel, etc.)] to provide an operator interface for the configuring, monitoring and controlling a multiple IMPRs.] The OIT shall be as specified in specification Section [00 00 00.00]. Programming and Configuration: In addition to the requirements specified herein, specific IMPR programming and configuration requirements may be specified elsewhere within the Contract Documents. [The Contractor shall coordinate with the motorized equipment supplier to establish settings for the IMPR.][The Contractor shall coordinate the following initial settings with the motorized equipment supplier to establish settings acceptable to the supplier and Owner. 1. … 2. ...] PART 3 - EXECUTION 3.1 GENERAL A. In addition to the requirements specified herein, execution shall be in accordance with the requirements of Specification Section [26 00 00][16010] and Drawings. END OF SECTION [26 29 16][16290] Section [26 09 16][16290] Electrical Controls and Relays Page 6 05/12/2017 Schneider Electric