Download Digital real time simulator

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Voltage optimisation wikipedia , lookup

Ground (electricity) wikipedia , lookup

Mains electricity wikipedia , lookup

Islanding wikipedia , lookup

Power electronics wikipedia , lookup

Semiconductor device wikipedia , lookup

Alternating current wikipedia , lookup

Fault tolerance wikipedia , lookup

Power engineering wikipedia , lookup

Electrical grid wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrical substation wikipedia , lookup

Protective relay wikipedia , lookup

Opto-isolator wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Earthing system wikipedia , lookup

Surge protector wikipedia , lookup

Transcript
Digital real time simulator
Real time digital simulator (RTDS) for testing and training
At a glance
Increased demands on the network availability,
with simultaneously increased complexity, e.g.
lines in Y-joint or series compensation, result in
high demands on the protection devices, but
also on the reliability of the setting values which
cannot be verified theoretically. Safety is provided by a real time simulator, but that is not all.
Siemens Power Technologies International
(Siemens PTI), your provider of network consulting, network planning software and trainings
on the Siemens T&D portfolio, offers protection
simulation tests with the following benefits:
disconnects the faulted grid element. Disconnections due to wrong protection setting values
can lead to unnecessary, often fairly high expenses for the network operator. Such unnecessary costs can be avoided by optimizing the
setting values of the installed protection devices. These values can be optimized and verified for different fault cases by means of digital
simulation.
 Setting values of different fault cases can be
optimized, verified and discussed with experts
 Customers can learn to operate the devices
by means of DIGSI and to evaluate the fault
printouts by means of SIGRA
 Transient processes in the network during
short circuit can be analyzed to gain deeper
insights
Figure 1: Technical equipment of the simulator (from left
to right): RTDS, amplifiers, signal distributor, protection
devices
 The performance of the protection devices is
validated by explicit measurements, e.g., triggering times
Our solution
The challenge
When a new system is installed, the appropriate
protection devices need to be selected and the
settings determined. Depending on the size of
the network this may be a complex task, not
least because the functionalities and the operation of the different protection devices may vary
substantially. Therefore, it can be helpful to
learn how to operate a certain device in order to
be able to decide whether it is suitable for application in a certain system. Real time digital
simulation allows you to learn about the operating principles of different protection devices and
to decide on their suitability.
In an existing protection system, the setting
values determine if and when the circuit breaker
Siemens PTI − Network Consulting
Technical details
Our Real Time Digital Simulator performs calculations for networks with up to 100 single nodes
with a sampling rate of around 20 kHz. You can
simulate generators, sources, multi-circuit lines,
transformers, loads, current transformers with
saturation, capacitive voltage transformers,
circuit breakers etc. Real protection devices
work with the simulator in closed loop to be
able to carry out complex sequences like unsuccessful and 1-pole re-closings or secondary
faults. Voltage amplifiers and current amplifiers
up to 40 A as well as a documentation system
complete the simulator.
Evaluation
After the system disturbance has been
simulated, the malfunction messages are
analyzed and the fault printouts evaluated. This is very important for understanding the processes in the system
and the behavior of the protection devices. Unlike real malfunctions, the solution is known in the simulator and the
customers can train this analysis while
considering the behavior at both line
ends.
experience and training; as well as fault
simulation.
Application example
Figure 2 shows an example of a results
page. Test results will be documented in
our data acquisition system. Current
and / or voltage wave forms as well as
binary output contacts including trip
times of the relays will be recorded. This
ensures an accurate storing of the simulated network faults and shows the reaction of the protection device. The results
thus comprehensively validate the required protection system performance
and form the basis for optional procedures and training.
To get more informative details about
complex configurations or sequences,
DIGSI often ranks more events in malfunction messages. The analysis via
SIGRA in the impedance level also helps
to understand physical influences, e.g. of
the distance measuring. The resulting
report in form of a PDF file often consists
of several thousand pages.
Specification tests
Depending on whether the simulations
are more concentrated on tests or on the
training aspect, approximately 50 to 150
tests can be carried out for a period of
several weeks in a row. Working in small
groups of typically up to three participants ensures efficient discussion and
know-how transfer.
Workshops
In the scope of the Siemens Power
Academy TD, experts are offered workshops with an emphasis on exchange of
Published by and copyright © 2011:
Siemens AG
Infrastructure & Cities Sector
Smart Grid Division
Services
IC SG SE PTI BD
Freyeslebenstr. 1
91058 Erlangen, Deutschland
www.siemens.com/energy/power-technologies
Figure 2: Example of a simulation results page
Siemens Energy, Inc.
Power Distribution, T&D Service Solutions
Siemens Power Technologies International
400 State Street
PO Box 1058
Schenectady, NY 12301-1058
For more information, please contact
our Customer Support Center.
Phone: +49 180 524 70 00
Fax:
+49 180 524 24 71
(Charges depending on provider)
E-mail: [email protected]
Siemens Transmission and Distribution Ltd
PTI
Sir William Siemens House, Princess Road
Manchester, M20 2UR
United Kingdom
Smart Grid Division
Printed in Germany
Printed on elementary chlorine-free
bleached paper.
All rights reserved.
Trademarks mentioned in this document
are the property of Siemens AG, its affiliates,
or their respective owners.
Subject to change without prior notice.
The information in this document contains general
descriptions of the technical options available,
which may not apply in all cases.
The required technical options should therefore be
specified in the contract.