Annex - B
Technical Compliance Sheet
The following Technical data shall be furnished and filled by the bidders:
1-General 90 KVA (Prime Power) Generator
#
1-
Description
Make:
2
Name of
manufacturer
Country of origin
Reference standards:
Ambient temperature
:
345-
678910
1112
Relative Humidity :
Altitude:
System Voltage :
No of phase :
Frequency:
Guarantee:
Generator output
Range
13 Maine MCCB breaker
14- Daily base tank
15 Submit Manufacturers’
UNDP specifications
Original manufacturer (Locally
assembled not acceptable)
Offered specification
IEC/ISO
Maximum:55/C
Minimum:-10/C
92% maximum
1000M above MSL
400V
3PH
50Hz
one year ,1000HR / operation
90 KVA prime load at 55 deg
4pole 160 A…
Minimum 8 -10 hour fuel capacity
certification :
2-ENGINE
1-
Description
Make / Model :
234567891011-
Name of manufacturer
Country of Origin
Reference standards:
RPM:
Prime :
Type of Governor:
Overload rating:
Fuel filter :
Type of fuel :
Type of starting
UNDP specifications
Original manufacturer
(Renovated, Engine not
acceptable)
ISO
Maximum 1500
90 KVA prime load at 55 deg
Mechanical /Electronic
As per International standard
Standard water separator filter
Diesel
24 Volt DC
Offered specification
Annex - B
Radiator–fan cooled–fan to be
driven by the engine shaft.
Turbo charge
Indicator
Submit :Operation and maintenance manual
Submit Detail drawings, brochures and catalogues
Submit type test certificates or reports
12- Type of cooling:
13141516-
3-Alternator
Description
UNDP specifications
Make/Model :
Name of manufacturer:
Country of Origin
IEC
Reference standards:
0.400 KV
Rated Voltage :
90 KVA
Prime power at 55 deg C:
Between 0.8 and 1
Rated power factor :
3Ph
No. of Phase
:
50Hz
Frequency:
Brushless, self-regulation
Type of excitation:
+ -5%
Percentage voltage regulation :
Not less than 23
IP :
Class H
Insulation type :
Digital
AVR type :
Submit detail drawings, brochures and catalogues
Submit type test certificates or reports
Offered specification
4-CONTROL PANEL
Description
Make / Model :
UNDP specifications
CONTROLLER
INFORMATION
Instrumentation
tachometer
switch
switch
Offered specification
Annex - B
SHUTDOWNS
Fire Alarm
.
Submit detail drawings, brochures
and catalogues
5-Automatic Transfer switch
Description
Make:
UNDP specifications
Original manufacturer
(Locally assembled not
acceptable)
Offered specification
Name of manufacturer:
Country of Origin:
Reference standards:
IEC 60947
0.4 kV
Rated voltage :
200 A
Rate current :
Submit detail drawings, brochures
and catalogues
6-Enclosure
Description
Make:
Noise Level :
UNDP specifications
Original manufacturer
(Locally assembled not
acceptable)
Below 95 dB at a distance of
1meter.
Offered specification