High Density HDDC
DC Power Distribution Center
High Current DC Distribution Center
 200A per bus redundant A/B/C version
 300A per bus high ampacity, 22 circuit versions
 Configurable power routing options
o Single input
o A/B isolated input
o A/B input, C-source redundant diode routed
1. High density DC distribution for rack mount servers and Broadband applications such as
VOD,CMTS, VOIP. Allows high density distribution of DC capacity for point of use in high circuit
count server racks or for use in CSI PowerBay BDFB cabinets
2. 19"/ 23" Rack mount, 3 R/U high. High breaker circuit count to support multiple servers and
their redundant power supply requirements and combined high current loads
 High power density and ampacity:
o 300 Amperes per input: (Single input, A/B input) high ampacity versions (3
o 200 Amperes combined load: (A/B/C -source) low ampacity redundant version
o Accepts up to 22 plug-in bullet terminal circuit breakers for convenience and flexibility
4. Small RU requirement leaves room for maximum network equipment space in equipment racks
5. Two-hole lug high current bus bars for input and return terminations. Supports large AWG input
cable feeders
6. Alphanumeric LCD display for voltage, load current per bus, breaker status. Bright, color coded
LED indicators for power input power status, breaker trip and alarms
7. Form-C alarm contacts for Major and Minor alarms
 Single hole or two hole lug termination bus bar array for circuit breaker protected outputs and
returns. Low ampacity
8. A/B/C version provides setscrew barrier strip output terminals. High ampacity versions provide
two-hole lug landing
9. Accepts bullet terminal circuit breakers available from CSI in numerous amperage ratings.
Interchangeable breakers reduces spare parts inventory and cost
10. Flip down front cover panel protects breakers from nuisance tripping. Convenient front access
for breaker installation
11. Plug-in breakers can be installed incrementally as needed to reduce install cost. Breakers can be
changed in seconds to support equipment load and configuration changes over time
12. Input/output clear plastic termination guard
Doc# 048–008–00/Jan.01.07
General Specifications
Model #
P/N 016–400–10
Configuration
Single input, high ampacity
output
Single input,22 breaker sockets
Part #
Single input
300A
Description
Single input breaker panel,
300 ampere rated
22 bullet breaker sockets
2 qty form–c alarm
contacts
LED/LCD front panel
indicators (also used in CSI
PowerBay BDFB cabinets)
-48VDC
P/N 016-401-10
A/B isolated input/output
A/B isolated inputs/split bus
output
11A/11B breaker sockets
High ampacity
Dual A/B input
300A
Isolated A/B input breaker
panel, 300 A per bus
22 bullet breaker sockets
2 qty form–c alarm
contacts
LED/LCD front panel
indicators
–48VDC
P/N 016–402–10 A/B input, C bus output - 200A
Isolated A/B inputs feed diode
power routed output bus and 22
breakers for redundant operation
of load circuits from either A/B
inputs
A/B input, C bus output-300A
Same as 016-402-10 but 300A
output
Dual A/B input
200A maximum
load
A/B input, C–output diode
routed bus feeds
redundant
22 bullet breaker sockets
200 A combined output
load rating
2 qty form–c alarm
contacts
LED/LCD front panel
indicators
–48VDC
P/N 016–404–10
Dual A/B input
300A maximum
load
A/B input, C–output diode
routed bus feeds
redundant
22 bullet breaker sockets
300 A combined output
load rating
2 qty form–c alarm
contacts
–48VDC
Doc# 048–008–00/Jan.01.07
Common Specifications for All Models:
Dimensions: 17" W x 5.25" H (3 RU) x 12.5" D (including bus bar protrusion)
Weight: 13 lbs
Rack mount via 19/23" reversible rack mount ears
Two mounting positions: Front flush or mid-mount
Rear clear cover panel for bus bar termination area
Plug-in bullet terminal circuit breakers: Select amperage rating and quantity at time of order
Circuit Breakers
CSI Part#
470-235-10
470-402-10
470-403-10
470-407-10
470-400-10
470-406-10
470-404-10
470-269-10
Description
10 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
20 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
30 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
40 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
60 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
80 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
100 AMP AM Breaker, Plug-in Type, Midtrip (5/16" Bullet Terminals)
200 AMP AM Breaker, (2 Pole) Plug-in Type, Midtrip (5/16" Bullet Terminals)