TECHNICAL TRAINING
2008
Technical Training 2008
Inverter Mini Chiller
System and Control
Technical Training 2008
Content
1. Introduction
2. Basic Inverter Technology
3. Components
4. Control Algorithm
5. Protection
Technical Training 2008
Introduction
Technical Training 2008
Introduction
5ACV100/135/210 CR
5ACV55/75 CR
5ACV30 CR
Technical Training 2008
Introduction
Capacity (kW)
Model
Cooling
Heating
5ACV030CR
7.94
9.66
5ACV055CR
14.65
16.12
5ACV075CR
20.52
21.99
5ACV100CR
27.80
29.30
5ACV135CR
38.54
41.47
5ACV210CR
58.62
61.55
Technical Training 2008
Introduction
New Technology BPHE- True Dual Circuits
Conventional Back to Back Circuits BPHE
Secondary Circuit
Primary Circuit 1
Primary Circuit 2
5ACV True Dual Circuits BPHE
Primary Circuit 1
Primary Circuit 2
Technical Training 2008
Introduction
Inverter Compressor
Conventional System
Inverter System
Technical Training 2008
Introduction
Elimination of Water Tank
Inverter system provide constant Water Temperature band, or much
lesser water temperature fluctuation. With this, water tank of mini
chiller system can be eliminated
Modular Installation
A network up to 50 chillers in a system is possible. Control on the
operation of chillers will be done through the microprocessor controller.
The external water piping connection can be made either from the left
or right side of the unit.
Safety Protection
• High & Low Pressure Switches
• Anti Freeze Protection Sensor
• Discharge Temperature Sensor
• Over Pressure Relief Valve
Technical Training 2008
• Water Pressure Differential
Switch
• Anti Freeze Heater on BPHE
• Compressor, Water Pump
Overload Protector
Basic Inverter
Technology
Technical Training 2008
Basic Inverter Technology
The system:-
u
Power supply
Input frequency
50Hz
t
Inverter
t1
AC/DC
Rectifier
DC/AC
Inverter
50 Hz
t
100 Hz
15 Hz
(compressor motor input)
PWM
Technical Training 2008
Basic Inverter Technology
AC
DC
Power
supply unit
AC
Three-phase
inverter
Temperature
detection signal
Three-phase
induction motor
PWM control
Operating
frequency signal
(Waveform formation)
AC Inverter Unit
Technical Training 2008
Compressor
Basic Inverter Technology
Inverter Basic Structure
DC Link
Converter
AC
Rectification
AC
Inversion
SMPS
PLC Control
PWM Signal
Technical Training 2008
M
Basic Inverter Technology
Rectification Circuit
Rectifier Bridge
Relay
EMI
Filter
•
•
•
PTC Starter
EMI filter to minimize emission effect (EMC) and raise
immunity level (EMS)
PTC to cushion start-up current to capacitor
Diode bridge inverts AC to DC
Technical Training 2008
Basic Inverter Technology
DC Stage
PFC Capacitor
Reactor
•
Diode
Stabilizing
Capacitor
PFC capacitor acts to curb PF losses caused by DC voltage
fluctuation in order to drive the asynchronous motor
Technical Training 2008
Basic Inverter Technology
Inversion Circuit
•
•
Consists of 6 IGBT (Insulated Gate Bipolar Transistor)
Controlling the ON/OF linkages, different frequency and voltage
of 3-phase AC can be generated
• IPM (Intelligent power module) encased the inversion circuitry
together with error detection and protection features
Technical Training 2008
Basic Inverter Technology
Advantages of Inverter Air Conditioners
Item
Fixed Speed AC
Inverter AC
No
Yes, by 30% - 40%
± 2°C
± 0.5°C
No
Yes
Current surge of 711x
Soft-start. No
current surge
No
Yes, operates at
high freq.
Slow
Fast
Less efficient
Accurate and fast
Protection Features
Basic
Complete
Auto-Mode Features
Basic
Complete
Energy Saving
Temp. Fluctuation
Adjust to Load
Start-up
Full Load Op.
Speed of Cool/Heat
Defrosting
Technical Training 2008
Components
Technical Training 2008
Components
Fan guards
Coil guards
fan motors
Heat
exchangers with
gold fin as
standard
True dual circuits BPHE
(Brazed plate heat
exchanger)
Control box
assembly
Technical Training 2008
Expansion
tank ( 8L)
Water pump
Components
High pressure switch
(NC) 600 psi – open,
480psi – close.
Low pressure switch
(NC) 18 psi – open,
28 psi – close.
Chiller panel
controller
Differential pressure
switch
Over pressure relief
valve
Fixed speed
scroll
compressor
(R410A)
Anti freeze heater on
BPHE
Pump OLP (overload
protector)
Compressor OLP
(overload protector)
Variable speed
scroll
compressor
(R410A)
Variable drive system
compartment
Technical Training 2008
Fixed drive system
compartment
Components
Control box assembly
Unidirectional
bridge diode
IPM board
(Intelligent power module)
3 phase
rectifier
bridge diode
Fan
capacitors
Power board
EMI filter
PFC capacitor
Capacitor
board
(Power factor correction)
Technical Training 2008
Main board
Magnetic
contactors
Components
EMI Filter
Function
• EMI Filter is a device placed between the power source and
control device circuit.
• Prevents external electromagnetic interference from getting
into the controller.
• Prevents internal electromagnetic emission from polluting
the supply grid.
Technical Training 2008
Components
Main Board
For Model 55, 75, 100 & 135
Technical Training 2008
For Model 30
Components
Power Board
- To convert rectified DC current
+590VDC to respective desired
voltages
- 12VDC relay
- MCU +5VDC
- IPM +15VDC
- Ensure stability of above voltages
within power supply voltage fluctuation
range (304-480 VAC)
- Over voltage feedback
- Output short circuit protection
Technical Training 2008
Components
Capacitor Board
Technical Training 2008
Components
IPM
Function
• Invert DC to AC current
• Drive variable compressor
In-Built Protection
• Low voltage lock-out
• Over-heating, over-current and short-circuit protection.
Technical Training 2008
Components
Schematic Diagram
Cond In
Temp 1
(Condenser)
5ACV100CR
Cond Out
Temp 1
(Def Comp 1)
Condenser Coil 1
HP1
Filter
Drier
4WV
Disch
Temp 1
(Disch Comp 1)
LP1
EXV
Suct
Temp
(Suction)
Inv
Comp
O/A Temp
(Outdoor Air)
BPHE In
Temp
(BPHE In)
BPHE Out
Temp
(BPHE Out)
Liq Rvr
Acc
Pump
BPHE
EWT (Water In)
FS
LWT (Water Out)
HP2
Cooling Cap Tube
4WV
Disch
Temp 2
(Disch Comp 2)
Check valve
LP2
Liq
Rvr
Std
Comp
Acc
Condenser Coil 2
Cond Out
Heating Cap Tube
Temp 2
(Def Comp 2)
Check valve
Technical Training 2008
Summary PagesScreen 3
Display MenuDefrost Sensor
Filter Display MenuDrier Inverter Chiller
Display MenuDischarge Sensor
Control Algorithm
Technical Training 2008
Control Algorithm
General Control Flow Chart
Start
No
System On?
Yes
Clash between
current & selected
mode of operation?
Yes
No
Stop Inverter Comp
Cooling?
10s
No
Heating?
No
Stop Fixed Comp
Yes
Yes
60s
Stop pump
Cooling mode
Technical Training 2008
Heating mode
Control Algorithm
Variable Drive Compressor Control
Cooling mode
Start up condition :
• Pump runs normally for 3 minutes *
• 2°C T
water return
– T
set
 4°C
For example :
Return water temp.= 14 to 16 °C
Set temp
= 12°C
DT
= 2 to 4°C
• No irreversible errors in variable drive and the systems
• Satisfy a delay of 3 minutes before restart
#
Note : If fixed drive system starts first, the variable drive system should
trail after 30 sec.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )
# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
Technical Training 2008
Control Algorithm
Variable Drive Compressor Control
Cooling mode
Cooling mode selected  water pump starts  Outdoor
fan starts  variable drive compressor starts
Increase to rated
frequency with the
rate of 1Hz/s
Rated Freq.
5ACV100CR=75Hz
5ACV135CR=95Hz
55Hz
5Hz
t
3 min 5 sec
1 min
Variable drive comp
ON
OFF
ON
OFF
Outdoor fan
Outdoor fan will start 5 sec
before compressor start
Technical Training 2008
Inverter compressor will
start from 5Hz to 55Hz
and maintain this
frequency for 1 min.
Control Algorithm
Variable Drive Compressor Control
Cooling mode
Shut down condition :
• Cooling mode terminates, OR
• Variable drive system error occurs, OR
•T
water return
– T
Technical Training 2008
set
 -2°C
For example :
Return water temp.= 10°C
Set temp
= 12°C
DT
= -2°C
Control Algorithm
Fixed Drive Compressor Control
Cooling mode
Start up condition :
• Pump runs normally for 3 minutes *
•T
water return
– T
set
> 4°C
Fixed drive starts first followed by variable drive
For example :
Water return temp = 16°C
Set temp
= 12°C
DT
= 4°C
• No irreversible errors in fixed drive and the systems
• Satisfy a delay of 3 minutes before restart
#
Note : If variable drive system starts first, the fixed drive system will
only start after the frequency of variable drive drops to 50Hz.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )
# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
Technical Training 2008
Control Algorithm
Fixed Drive Compressor Control
Cooling mode
Cooling mode selected  water pump starts  Outdoor
fan starts  compressor starts
Fixed drive compressor
starts
ON
Fixed drive comp
OFF
3 min
5 sec
1 min
ON
Outdoor fan
Outdoor fan will start 5 sec
before compressor start
Technical Training 2008
OFF
Outdoor fan will stop after
compressor has stopped for
1 min
Control Algorithm
Fixed Drive Compressor Control
Cooling mode
Shut down condition :
• Cooling mode terminates, OR
• Fixed drive system error occurs, OR
• T set - T
20Hz
water return
> 2°C and variable frequency drops pass
For example :
Set temp
= 12°C
Water return temp =
10°C
DT
= 2°C
Technical Training 2008
Control Algorithm
Variable Drive Compressor Control
Heating mode
Start up condition :
• Pump runs normally for 3 minutes *
• 2°C T
set
- T
water return
 4°C
For example :
Set temp
= 40°C
Return water temp.= 36 to 38 °C
DT
= 2 to 4°C
• No irreversible errors in variable drive and the systems
• Satisfy a delay of 3 minutes before restart
#
Note : If fixed drive system starts first, the variable drive system should
trail after 30 sec.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )
# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
Technical Training 2008
Control Algorithm
Variable Drive Compressor Control
Heating mode
Heating mode selected  water pump starts  Variable drive 4WV
engages  Outdoor fan starts  compressor starts
Increase to rated
frequency with the
rate of 1Hz/s
Rated Freq.
5ACV100CR=65Hz
5ACV135CR=90Hz
Inverter compressor will
start from 5Hz to 45Hz
and maintain this
frequency for 1 min.
45Hz
5Hz
t
3 min 10 sec
Variable drive comp
ON
OFF
ON
OFF
ON
OFF
Variable 4WV
Outdoor fan
Variable drive 4WV start 10 sec
before compressor start
Technical Training 2008
1 min
5 sec
Outdoor fan will start 5 sec
before compressor start
Control Algorithm
Variable Drive Compressor Control
Heating mode
Shut down condition :
• Heating mode terminates, OR
• Variable drive system error occurs, OR
•T
set
- T
Technical Training 2008
water return
 -2°C
For example :
Set temp
= 40°C
Water return temp = 42°C
DT
= -2°C
Control Algorithm
Fixed Drive Compressor Control
Heating mode
Start up condition :
• Pump runs normally for 3 minutes *
•T
set
- T water return > 4°C
For example :
Set temp
= 40°C
Water return temp = 36°C
DT
= 4°C
• No irreversible errors in fixed drive and the systems
• Satisfy a delay of 3 minutes before restart
#
Note : If variable drive system starts first, the fixed drive system will
start after the variable drive frequency drops to 50Hz.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )
# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
Technical Training 2008
Control Algorithm
Fixed Drive Compressor Control
Heating mode
Heating mode selected  water pump starts  Fixed drive 4WV
engages  Outdoor fan starts  compressor starts
Fixed drive compressor
starts
ON
Fixed drive comp
OFF
3 min
10 sec
1 min
ON
5 sec
Variable 4WV
OFF
ON
Outdoor fan
Fixed drive 4WV start 10 sec
before compressor start
OFF
Outdoor fan will start 5 sec
before compressor start
Technical Training 2008
Outdoor fan and 4WV will
stop after compressor has
stopped for 1 min
Control Algorithm
Fixed Drive Compressor Control
Heating mode
Shut down condition :
• Heating mode terminates, OR
• Fixed drive system error occurs, OR
•T
water return
-T
set
> 2°C
For example :
Water return temp = 42°C
Set temp
= 40°C
DT
= 2°C
Technical Training 2008
Control Algorithm
Pump Control
Pump start up
When starting the system, pump will run for 3 minutes * before
proceeding to next step.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min = 0s, Max = 199s,
default = 120s)
Pump shut down
After both compressors shut down for 1 minute, pump shuts down.
Technical Training 2008
Protection
Technical Training 2008
Protection
Compressor Over-Current Protection
Variable drive compressor
• When variable drive compressor current reaches the Ib, over-current
protection triggers and the compressor frequency will reduce.
• When the compressor current drops into Ic to Ib, frequency will not increase.
• When the compressor current drops below the Id, frequency variation resumes.
• When compressor current increase rapidly and reaches the Ia, the
system will be determined as compressor overload and stop the compressor.
Comp amp
(A)
Ia
Ib
Variable compressor stops
Frequency step down
Maintain frequency
Ic
Id
Technical Training 2008
Normal Operation
Protection
Compressor Over-Current Protection
Variable drive compressor
Inv
M5ACV M5ACV M5ACV M5ACV M5ACV M5ACV
Comp
030
055
075
100
135
210
Current
Ia
29
20.5
20.5
20.5
20.5
20.5
Ib
27
18
18
18
18
18
Ic
25
17
17
17
17
17
Id
25
16
16
16
16
16
Technical Training 2008
Protection
Compressor Over-Current Protection
Fix drive compressor
• When fixed compressor current > Ie. The compressor will stops and resumes after
3 minutes
Note: When either drive overload protection occurs more than 3 times within 30
minutes, system triggers irreversible error protection.
Model
5ACV30
5ACV55
5ACV75
5ACV100
5ACV135
5ACV210
Ie
NA
NA
NA
16
30
?
Comp amp
(A)
Technical Training 2008
Ie
Fixed compressor stops
Protection
High Discharge Temperature Protection
Variable drive system
• When variable drive discharge temperature reaches 110°C, system stops.
• When variable drive discharge temp. between 100°C and 110°C, frequency
drops.
• When variable drive discharge temperature is less than 97°C and more than
100°C,
frequency increased restricted.
• When discharge temperature falls below 94°C, normal operation resumes.
Compressor
discharge
temperature
System shuts down
110°C
Frequency step down
100°C
Maintain frequency
97°C
94°C
Technical Training 2008
Normal operation
Protection
High Discharge Temperature Protection
Fixed drive system
• When fixed drive discharge temperature reaches 110°C, system stops.
• When discharge temperature falls below 94°C for 3 minutes, system resumes.
Td = Compressor discharge temperature
Td
Comp Cut
110°C
94°C
Comp start
3 min
Technical Training 2008
Protection
Outdoor Coil High Temperature Protection
Variable drive system
• During cooling, when Tcoil1 > 60 °C, frequency drops.
• During cooling, when Tcoil1 < 55 °C, system resumes.
Fixed drive system
• During cooling, when Tcoil2 > 64°C, compressor stops.
• During cooling, when Tcoil2 < 51°C, system resumes.
Technical Training 2008
Protection
Low Pressure Switch Protection
• Alarm delayed at compressor startup : 30 sec depends on Parameter P3*.
• No protection during defrosting.
• If variable drive or fixed drive low pressure switch is activated for 5
seconds, alarm will be triggered.
* Parameter P3 (Low pressure alarm delay at compressor start up. Min=0s, max=199s, default=30s)
Note : If low pressure alarm occur more than 3 times within
30 minutes, system shuts down to irreversible error.
Technical Training 2008
Protection
High Pressure Switch Protection
• If fixed drive high pressure switch is activated for 30 sec, alarm will
be triggered.
• If variable drive high pressure switch is activated, frequency of
variable drive compressor will decrease at 1Hz/s. If it is re-activated
for 30 sec, alarm will be triggered.
Note : If high pressure alarm occur more than 3 times within
30 minutes, system shuts down to irreversible error.
Technical Training 2008
Protection
3 Phase AC Phase Sequence Protection
If 3 phase AC phase sequence is incorrectly connected,
system will not start and controller will indicate error.
System will resume after rectification. (except M5ACV030CR)
3 Phase AC Phase Missing Protection
If phase missing happens, system will not operate.
Controller will indicate error. System will resume after
rectification.
Technical Training 2008