SiteRanger™
Internet-based Site Monitoring System
Comprehensive Broadband/ Enterprise site monitoring device for Headend’s, Hub Sites
Power Quality Retrofit Monitoring
 8,16,24 or 32 isolated input channels
 Smart transducers for power system monitoring
 Analog measurements such as temperature, generator fuel levels, AC and DC power
systemvoltage, current and power, ground current
1. 19”/23” Rack mount housing
2. Internal Circuit board with integrated electronic components. Internal webserver with TCP/IP,
SNMP
3. 8,16,24, or 32 contact closure input channels - Normally open or closed. Accepts contact
closures from UPS and DC systems, Generators, HVAC units, Fire Suppression, access control and
other site devices
4. Input channels fed from remote relay / form-c dry contact closures. Internal opto isolators
provide electrical isolation to web server module
5. LED indicators for Alarm and system status, power supply status. Extended feature version has
VFD alphanumeric display
6. Flexible and redundant power supply input. Dual A/B -48VDC inputs for redundant DC plant
power, 120VAC input
7. Set-screw terminal blocks for reliable compression connections for direct input wiring. 50
Conductor cable connectors and remote 66 block interface for cross-connect to existing site
alarm connections provided
8. Compliant with MSO VOIP telemetry alarm requirements for site monitoring. SNMP trap output
via internet connections, email, remote internet login webserver. Provides direct SNMP output
support for Spectrum enterprise management software as well as generic SNMP for other
Network management software systems for Regional/National NOC visibility
9. 120VAC, dual -48VDC inputs. Surge protected, fuse protected. PoE option for SiteRanger remote
module powering
10. Extended version provides Integrated annunciator LCD panel including digital site status,
webserver configuration, ethernet port status for communications to network infrastructure
 Available smart transducer system options include AC monitor module for Generator ATS or UPS
power parameter monitoring, DC module for -48VDC power system voltage, current,
distribution monitoring, Environmental module for HVAC alarm status, high/low temperature,
condensate drain alarms. Generator status module for generator alarms, fuel level. Smart
transducers are powered via Power over Ethernet (PoE) from main switch via the SiteRanger
LAN for reliability and uninterrupted monitoring
General Specifications
Model #
P/N 016-900-10
Configuration
SiteRanger Basic -control module:
Part #
Description
Rack mount housing. Accepts
Doc# 048–600–00/Nov.01.06
Contact inputs, Smart transducer
interface, internal DC/AC power
supply. LED interface panel,Rack
mount housing
P/N 016-905-10
ACM AC power module
Monitors single or three phase AC
voltage, current, power
parameters. . Use for ATS site
power monitoring, UPS output
monitoring
P/N 016-910-10
DCM DC power module
Monitors -48VDC rectifier and
battery system status. Measures
DC voltage, current, distribution
circuit breaker trip, battery status,
accepts alarm contact outputs from
DC power system
P/N 016-915-10
EVM Environmental module
Monitors HVAC alarm contact
outputs, temperature, condensate
drain alarm, multiple temperature
sensor inputs for zone temperature
monitoring
P/N 016-920-10
GSM Generator status module
Monitors Generator contact
closures, fuel level, starting battery
voltage
P/N 016-925-10
FSM Generator fuel status module
Monitors Generator fuel level.
(Diesel or propane)
8/16/24/32 contact inputs,
interfaces with CSI smart
transducer SiteRanger LAN.
Ethernet 10/100 Base T jack
with LED indicators. 48VDC/120VAC input, internal
power supply
Non-metallic housing with
terminal block connections for
AC voltage sense, current
transformer input sense, ATS
position sensing
(generator/commercial
power), 5 alarm contact
inputs. SiteRanger LAN port.
Specify 1,2 or 3 phase, 120V,
240V, 208V, 480V versions.
Current transformers available
for 100, 200, 400 and 600A
systems
Non-metallic housing with
terminal block connections for
DC voltage sense, DC power
system contact closure inputs,
distribution alarm contact
inputs, SiteRanger LAN port.
Specify input configuration,
current monitoring kit, battery
temperature probe kit
Non-metallic housing with
terminal block connections for
8 HVAC system alarm contact
inputs. 4 Temperature sensor
inputs, SiteRanger LAN port.
Specify number of
temperature sensors required
(up to 4)
Non-metallic housing with
terminal block connections for
generator output AC
voltage/current sense, 8 alarm
contact inputs. SiteRanger LAN
port. Specify 1,2 or 3 phase.
Monitors Generator fuel level.
Specify diesel tank level
sensor, propane tank
transducer head (various
Doc# 048–600–00/Nov.01.06
P/N 016-927-10
GNSM Ground network system
monitor Multipoint ground current
monitoring
versions depending upon tank
vendor)
Monitors ground current /
fault current. Supports up to 8
Hall effect or shunt based
ground current detector
modules
Common Specifications for All Models
Dimensions: 17" W x 3.75” (2RU) T x 12” D
Weight: 10 lbs
Rack mount with 19/23” reversable mounting flanges. Hinged cover w/LED or VFD control panel. Unit
includes wiring diagram / instruction manual, software, spare fuses
Electrical specifications:
Input: 120VAC power supply and dual -48VDC redundant inputs. All three power inputs are redundant
and will operate the unit.
Order Information
Shipping box packaging for UPS/FedEx shipment. Typical configuration includes bill of materials/parts kit
as per customer site survey order form
CSI Provides customer site surveys at no charge to provide customer proposals for the correct
SiteRanger component and installation configurations.
Doc# 048–600–00/Nov.01.06