www.eurojauge.fr
Signal isolation/signal amplification
TV 22 GL
TV 200 GS
Description
The TV 22 GL isolating amplifier is
used for the galvanic isolation and
amplification of DC current signals
(mA). Input and output are galvanically isolated with a high level of
isolation. The integrated electronic
high efficiency power supply unit
prevents overheating and allows for
high output loads. The extremely
narrow design allows for space
saving installation.
STV 22 GL
Description
The TV 200 GS isolating amplifier is
used for galvanic isolation, conversion and amplification of standard
output signals (V/mA). Input and
output are galvanically isolated with
a high level of isolation. The integrated high efficiency electronic
power supply unit prevents overheating and allows for high output
loads. Offset and gain can be adjusted by two potentiometers on
the unit front.
Description
The STV 22 GL isolating amplifier
with supply is used for the galvanic
isolation and amplification of DC
current signals (mA). The connected
transducer is directly supplied via a
galvanically isolated and limited supply voltage. Input and output are galvanically isolated with a high level of
isolation. The integrated high efficiency electronic power supply unit
prevents overheating and allows for
high output loads.
Technical specifications
Technical specifications
Housing
Standard DIN-rail housing
W x H x D: 23 x 78 x 103 mm
Housing
Standard DIN-rail housing
W x H x D: 18 x 78 x 103 mm
Supply voltage
DC 20 – 30 V or AC 230 V
Supply voltage
AC/DC 20 – 253 V
Input
0 – 20 mA or 4 – 20 mA
Sensor supply
DC 27 V open circuit voltage
DC 21 V at 20 mA
Technical specifications
Housing
Standard DIN-rail housing
W x H x D: 18 x 78 x 103 mm
Supply voltage
AC/DC 20 – 253 V
Input
0 – 20 mA or 4 – 20 mA
Output
0 – 20 mA or 4 – 20 mA
1:1 proportional to input signal
Output
0 –10 V or 4 – 20 mA
Output load
Max. 400 Ohm
Output load
I max. 900 Ohm/U min. 500 Ohm
DG: H
TV 22 GL
TW 41 GM
Part no.
53701
53702
(isolator without
power supply)
TWH 41 GM
(HART-enabled)
DG: H
TV 200 GS
53704
Input 4/20 mA
Output 0/10 V
TV 200 GS
53703
Part no.
Input 0/10 V
Output 4/20 mA
other signals
Input
0 – 20 mA or 4 – 20 mA
Output
0 – 20 mA or 4 – 20 mA
1:1 proportional to input signal
Output load
Max. 800 Ohm
DG: H
53705
Part no.
STV 22 GL
53706
STH 22 GL
53707
(HART-enabled))