Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
KSN ENERGY – BETTER ENERGY COMMUNITIES 2016 Pre-Start Meeting KSN Energy June 2016 M Mullen & R Ua Fearghail 2015 Results Overview • 66% of houses inspected in 2015 passed. • 8 projects had 100% pass rate for all inspections Most Common Reworks (Contractors with less than 70% Pass rate) o Roof ventilation (10% of roofs inspected) o Cavity wall ventilation (24% of CWI inspected) o External wall insulation – not covering accessible area (19% of EWI inspected) o Heating – Immersion heater timer (12% of inspected) Technical Specification 2016 Introduction Specifications are based on the following documents: • Better Energy Scheme – Contractors Code of Practice and Standards and Specification Guidelines – Version 7.0 http://www.seai.ie/Grants/Better_energy_homes/contractor/Code-of-Practice-Rev-7-1-2016.pdf • NSAI S.R.54:2014 – Code of practice for the energy efficient retrofit of dwellings: http://www.nsai.ie/S-R-54-2014-Code-ofPractice.aspx • Relevant building regulations http://www.environ.ie/housing/building-standards/tgd-part-d-materials-and-workmanship/technical-guidance-documents Heating • SEAI are holding a separate workshop specifically to address heating installations. • This is to be held on the 13th of July in SEAI’s Wilton offices • All heating elements will be covered on the day • There will be presentations given by KSN, The heat pump association of Ireland, OFTEC and RGII • • Measures covered will include: • SEAI heating inspections • Oil storage and oil supply • Heat pumps • Stoves There are limited places 2 per project guaranteed but we will try to accommodate all requests where possible. • Heating installers are urged to attend Ventilation overview There are 2 main points to note when assessing ventilation; • Fuel poor- Better Energy Warmer Homes spec (where advised is mentioned this has to be installed) • Non-fuel poor- Better Energy Homes spec (where advised is mentioned this can be assessed by home) What measures will this affect; • Wall insulation • Attic insulation Table 30 – SR54 Existing dwelling condition Retrofit works 1 Internal/External/Cavity insulation for walls 2 Replacement of windows 3 Sealing/insulating of timber suspended floors 4 Two or more of the above measures done in combination or separately A. No existing background ventilation in some or all habitable rooms and no extract ventilation in wet rooms B. Existing purpose provided background ventilation in each habitable room. No extract ventilation provided in wet rooms Background ventilation should be provided to rooms without background ventilation in accordance with Column 2, Table 31 No requirement to upgrade background ventilation. It is advised to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 It is advised to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 C. Existing purpose provided background ventilation in each habitable room. Extract ventilation provided in wet rooms No requirement to provide 2. further ventilation Where evidence of inadequate ventilation Where evidence of inadequate ventilation exists exists (e.g. mould, condensation) - extract (e.g. mould, condensation) - extract ventilation ventilation should be provided to all wet should be provided to all wet rooms in accordance rooms in accordance with Column 3, Table with Column 3, Table 31 31 No requirement to upgrade background ventilation No requirement to provide Extract ventilation should be further ventilation provided to all wet rooms in accordance with Table 31 NOTE Covered/Damaged covers on ventilators should be replaced with equivalent or better. Deficiencies or faults in ventilator grills or fans should be rectified and returned to intended working condition. Background and extract ventilation should be provided in accordance with Table 31 NOTE Where ventilation exists and severe conditions of condensation or mould growth have developed, specialist advise should be sought. Table 30 S.R. 54:2014 Code of practice for the energy efficient retrofit of dwellings, Ventilation Pg. 164 SR54 Table 30 – SR54 Interpretation for fuel poor homes Existing dwelling condition Retrofit works 1 Internal/External/Cavity insulation for walls A. No existing background ventilation in some or all habitable rooms and no extract ventilation in wet rooms B. Existing purpose provided background ventilation in each habitable room. No extract ventilation provided in wet rooms Background ventilation must be provided to rooms without background ventilation in accordance with Column 2, Table 31 No requirement to upgrade background ventilation. It is must to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 2 Replacement of windows It is must to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 C. Existing purpose provided background ventilation in each habitable room. Extract ventilation provided in wet rooms No requirement to provide further ventilation Where evidence of inadequate ventilation Where evidence of inadequate ventilation exists exists (e.g. mould, condensation) - extract (e.g. mould, condensation) - extract ventilation ventilation must be provided to all wet rooms must be provided to all wet rooms in in accordance with Column 3, Table 31 accordance with Column 3, Table 31 NOTE Covered/Damaged covers on ventilators should be replaced with equivalent or better. Deficiencies or faults in ventilator grills or fans should be rectified and returned to intended working condition. NOTE Where ventilation exists and severe conditions of condensation or mould growth have developed, specialist advise should be sought. SR54 Table 30 – Interpretation for non fuel poor homes Existing dwelling condition A. No existing background ventilation in some or all habitable rooms and no extract ventilation in wet rooms Retrofit works 1 Internal/External/Cavity Background ventilation must be provided to rooms without background ventilation in accordance with insulation for walls Column 2, Table 31 It is advised to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 2 Replacement of windows 4 Two or more of the above measures done in combination or separately Where evidence of inadequate ventilation exists (e.g. mould, condensation) - extract ventilation must be provided to all wet rooms in accordance with Column 3, Table 31 B. Existing purpose provided background ventilation in each habitable room. No extract ventilation provided in wet rooms C. Existing purpose provided background ventilation in each habitable room. Extract ventilation provided in wet rooms No requirement to upgrade background ventilation. It is advised to provide extract ventilation in wet rooms in accordance with Column 3, Table 31 Where evidence of inadequate ventilation exists (e.g. mould, condensation) - extract ventilation must be provided to all wet rooms in accordance with Column 3, Table 31 No requirement to provide further ventilation No requirement to upgrade background ventilation Extract ventilation must be provided to all wet rooms in accordance with Table 31 NOTE Covered/Damaged covers on ventilators should be replaced with equivalent or better. Deficiencies or faults in ventilator grills or fans should be rectified and returned to intended working condition. Background and extract ventilation must be provided in accordance with Table 31 NOTE Where ventilation exists and severe conditions of condensation or mould growth have developed, specialist advise should be sought. Mechanical extract ventilation notice In non fuel poor homes, where the homeowner is advised but decides not to have mechanical extract ventilation fitted. The following must be done: • The SEAI guidance note must be issued to the homeowner • http://www.seai.ie/Grants/Better_energy_homes/contractor/Newslet ter/Important-notice-in-relation-to-mechanical-extract-ventilation.pdf • A signed copy must be kept by the project coordinator. • This should be scanned and sent to [email protected] Table 31 - Minimum levels of background and extract ventilation as specified by Table 30 Room usage Minimum background ventilation (mm2)(d) Intermittent extract fan rating (l/s) Habitable room 6 500 Not required Kitchen(a) 6 500 60 (reduced to 30 for suitably sited extracting cooker hood) Utility room(a) 6 500 30 Bath or shower room(b) Not required 15 WC (only)(c) Not required 6 a) Where the room has no external wall, a floor area of less than 6,5 m2 and background ventilation cannot be provided then extraction fan to operate with a 15 minute overrun etc. * b) Where the room has no external wall and background and purge ventilation cannot be provided then the extraction fan should operate with a 15 minute overrun etc. c) Where a window opening for purge ventilation exists then the window alone may be relied upon to provide extract ventilation. d) Ventilation area as stated above is free area. Equivalent area is measured in accordance with the method specified in I.S. EN 13141-1: 2004. The above values should be multiplied by 0,8 to obtain equivalent areas. Table 31 S.R. 54:2014 Code of practice for the energy efficient retrofit of dwellings, Ventilation Pg. 165 * Ventilation for WC’s is not provided for BEWH Scheme Table 35 - Guidance for the provision of adequate supply of air for combustion appliances Retrofit Works 1 2 3 A. No existing supply of air in room containing a fixed open flued appliance. B. Adequate supply of air provided in each room containing a fixed open flued appliance. Wall Insulation, window replacement or sealing/insulation of suspended floors carried out BUT NO new open flued appliance fitted. No requirement to upgrade permanent Permanent ventilation should be provided ventilation. Recommended to ensure in the room containing the appliance, (see ventilation is unblocked, in good note). condition and permanently open. New open flued or flueless appliance fitted. This work falls within the Building This work falls within the Building Regulations Part J - Heat Producing Regulations Part J- Heat Producing Appliances. See TGD J for further Appliances. See TGD J for further guidance. guidance. Provision of new balanced flue appliance This work falls within the Building This work falls within the Building Regulations Part J - Heat Producing Regulations Part J- Heat Producing Appliances. See TGD J for further Appliances. See TGD J for further guidance. guidance. NOTE This permanent ventilation will also suffice for Background ventilation, see clause 10. Table 31 S.R. 54:2014 Code of practice for the energy efficient retrofit of dwellings, Ventilation Pg. 180 Wall Ventilation Note: New permanent and background vents are advised to be certified to IS EN 13141-1: 2004 Wall Ventilation • • • • Where open flued appliances are present extract ventilation should not be installed. This accounts for all fuels: Oil, Gas and solid fuel. This accounts for all rooms e.g. kitchens and utility rooms. Gas cookers are not open flued appliances and therefore are exempt. No extract ventilation to be installed where these are present Wall Ventilation Technical Specification 2015 When do I need to install ventilation • All rooms that have had wall insulation installed must be ventilated as per SR. 54 • If insulation has not been installed in a room then no ventilation is required. • Examples of this can be occasionally found in Dormers. • A handy rule will be to ask yourself is have I insulated any walls in this room? if the answer is no then no ventilation is required extract or background ventilation. No wall insulation Insulated walls Wall Ventilation • ventilating open flued appliances through adjoining rooms • Open flued appliance use the air in the room for combustion • If there is no air there is a risk of carbon monoxide • For safety where there are open flued appliances in internal rooms in a property: • A vent between both rooms should be installed. The vent in the adjoining room should have a free area no smaller than the ventilator to the outside. Open flued Room sealed • What if there is existing ventilation? • If a room requires a background ventilation and there is an existing hit and miss vent but it’s cover is painted closed what should I do? • • If a room requires permanent ventilation and there is an existing hit and miss or trickle vent what should I do? • • An extract fan should be installed in the wall with back draught dampers. What if extract ventilation is present but it is not working? • • The preference is to change the vent cover to a permanent cover. If this is not practical e.g. a nonstandard trickle vent then the vent should be fixed open with a small screw. If a cooker is situated where it is impractical to duct it to the outside what should I do? • • Covered/Damaged covers on ventilators should be replaced with equivalent or better. Deficiencies or faults in ventilator grills or fans should be rectified and returned to intended working condition. The homeowner should be advised to get their vent repaired. What do I do if I come across extract ventilation that is not ducted to the outside? • The fan should be ducted to the outside correctly. Extract ventilation. 2016 • Bathroom fan locations • As per ET-101 National Rules for Electrical Installations table 701 A: Extract fans should not be installed in zones 0,1 and 2 unless they are of the extra low voltage type Fans should not be installed in these zones Extract ventilation. • Surface conduits. • Surface conduits or trunking should be kept to a minimum. Care should be taken when choosing positions to minimise the amount of trunking installed. • Floorboards should be lifted Alternate position could have reduced trunking Extract ventilation. • Electrical isolation. • Again floor boards should be lifted in these instances • Also there is a requirement for a fan isolation switch. As per ET-101 National Rules for Electrical Installations, “an extraction fan shall be provided with an isolating device in its vicinity which switches all phase/line conductors”. • “Where a fan and a light are controlled by the one switch isolating devices shall be installed downstream of that switch” Reminders Wall vents Insulated ductwork: Ducting passing through unheated spaces needs to be insulated Back draught dampers: Where wall mounted extract fans are installed, dampers should be provided on the outlet to reduce draughts. • There are numerous options for backdraught dampers • An acceptable alternate would be to fit a fan with a closable cove as shown below: Wall Ventilation • Gas Cookers-as per part J Vent terminal locations Wall vents When installing wall vents care should be taken when positioning the vent. The distance from gas and oil boiler flues is an important consideration. Below are the minimum distances flues should be kept from certain items. This information can be used to determine the distances vents need to be kept from flues. Gas Vent terminal locations Wall vents When installing wall vents care should be taken when positioning the vent. The distance from gas and oil boiler flues is an important consideration. Below are the minimum distances flues should be kept from certain items. This information can be used to determine the distances vents need to be kept from flues. Oil Roof ventilation: Fuel poor homes: • As per TGD part F Non-fuel poor homes: • SEAI advise that all work should be done as per TGD part F • No existing ventilation should be compromised • Where evidence of distress due to lack of ventilation exists e.g. condensation, staining. Ventilation must be installed as per As per TGD part F Roofs The next slides will describe what is meant by various roof types so that we collectively are using the same terminology: • • • • • • Pitched Roof Flat Roof Dormer Roof Storey and a half Roof Mono-pitch Roof Lean – to Roof Terminology is very important! Dormer Roof: A roof which contains a room within it. Identifiable by having a crawl space adjacent to room. There are different versions of dormer roofs. Spray foam roof insulation: Where spray foam insulation is being installed it must: • Be installed as per NSAI certificate • Meet the required U-Value • Meet ventilation requirements 25mm2 equivalent • Make for a whole surface solution • including a ventilation void between the underside of the felt Attics Positioning of Vent Tiles / Slates To be positioned above insulation. Max 300mm above insulation preferable. We acknowledge this may not be possible adjacent to valleys. Not to be positioned below insulation. Guidance from Page 271 of SR54, Figure H.8 Attic Measures Two thirds rule. Do not take account for any existing ventilation located here Where the ceiling to be insulated is greater than 2/3’s of the floor area below the ceiling, attic insulation can proceed. This however is not possible in dormer roofs. It will be applicable to storey and a half type dwellings. Existing ventilation: Where a property has existing ventilation this should be assessed on site. The type of ventilator in Fig A. should be measured in increments of 50mm with an allowance of 1250mm2. e.g. a 200mm soffit ventilator will deliver 5000mm2. The type of ventilator seen in Fig B. can be very difficult to asses and tend have quite small openings. Therefore we do not make allowances for these. Fig. A Fig. B Avoiding Common Fails - Roof Ventilation Roof ventilation requirements are as follows; • Cross ventilation must be achieved • 10mm (25mm for dormer, flat roof) equivalent is required within the soffit using soffit vents or roof vents positioned at low level on the roof slope • 5mm equivalent is required at high level as per BS 5250:2011 to provide ventilation if the roof pitch exceeds 35° or the wall plate to wall plate distance exceeds 10m • High level ventilation must be calculated correctly for a hipped roof construction as per BS5250:2011 Mould growth in 18 months Downlights-fire risks • Recessed downlighter not covered with downlighter cover. • Poor detailing • Spot lights protected • Downlighter covers must be used purpose made recessed down-light covers installed must be tested to BS EN 60598-1 Luminaires . General requirements and tests Avoiding Common Fails – Electrical Penetration Cables pulled up over insulation Avoiding Common Fails - Hatch Insulation Hatches must be insulated to same standard as rest of attic Mineral wool type insulation with a thermal conductivity of circa 0.044 = 300mm Insulation to hatch Aeromark type rigid insulation board with a thermal conductivity of 0.031 = circa 225mm Polyurethane rigid insulation boards with a thermal conductivity of 0.022 = circa 150mm All of the above thicknesses will provide a basic U-Value of 0.16W/m2K. Please note that this is a basic value and does not allow for thermal bridging and other contributing factors Draught proofing: Draught proofing hatches • Good compression must be maintained alternatives are available to the common hooks and eyes: • Where access ladders are present maintaining insulation depth may not be practical but some effort should be made to install some level of insulation. This may also be applicable with the draught proofing. Avoiding Common Fails – Walk Boards Walk boards are required from the attic access to the ball valve of all water tanks. This includes (F&ET) feed and expansion tanks. If the tank is located in close proximity to the attic hatch, it must be assessed if it would be necessary to provide a walkboard at this location for somebody to stand on if carrying out repairs / work in this location. Contractors to install insulated walk board or board fixed to 50 x 50mm and batten insulted underneath. Walk board is to be a minimum of 19mm thickness 450mm wide flooring grade chipboard. It is to be screw fixed to the joists. They must start and finish on a joist to be adequately supported Walk board width not to scheme specification – 300mm not acceptable min.450mm Walk board not safely accessible at entry to attic Avoiding Common Fails - Pipe Insulation • All pipes containing water must be insulated • All sections of pipework must be insulated including bends, valves and joints • Insulation must be correctly fitted and secured • Thermal conductivity of insulation shall be as per Appendix Table 1 for TGD Part G of Building Regulations • If pipe bore ≤ 40mm, pipe insulation thickness should be equal to the outside diameter of the pipe • If pipe bore ≥ 40mm, pipe insulation thickness should be 40 mm Avoiding Common Fails - Pipe Insulation Joints are fully covered and sealed Good quality of insulation used throughout Pipes sealed the whole way into the tank Avoiding Common Fails – CWST and F&E Tank Tanks are to be fully insulated and fitted with lids if insulation is installed at joist level Tank to be insulated throughout including underside if above 300mm from joists Please ensure all expansion pipes are not above the tank jackets Avoiding Common Fails – CWST and F&E Tank Tank with no insulation or lid fitted Quilt “skirted” up around underside of tank Tank insulation not held in place Avoiding Common Fails – Electrical Penetration Electrical Penetration The 6sq and larger cables shown here must NOT be covered with insulation. These are generally mains cables / cooker cables and electric shower cables. Check all electric shower cables and cooker cables. These appliances require heavy duty cables but may have an incorrect cable installed, making them more dangerous if covered. Any Questions… Contact Details - KSN Energy KSN Energy Contact Centre 01 277 6977 Ruaidhri Ua Fearghail [email protected] 01 2776918 James O’Riordan Mat Mullen [email protected] [email protected] 01 277 6911 01 2776946