* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Download EDS 08-0121 Supplies to HOT Sites and
Survey
Document related concepts
Transcript
Document Number: EDS 08-0121 Date: 02/07/2015 ENGINEERING DESIGN STANDARD EDS 08-0121 SUPPLIES TO HOT SITES AND NATIONAL GRID SITES Network(s): EPN, LPN, SPN Summary: This standard details the additional requirements for the provision of LV supplies to higher voltage sites (e.g. 132kV, 33kV etc.) that are HOT or owned by National Grid. Owner: Allan Boardman Date: 02/07/2015 Approved By: Steve Mockford Approved Date: 24/07/2015 This document forms part of the Company’s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current version. Circulation UK Power Networks External All UK Power Networks G81 Website Asset Management Contractors Capital Programme ICPs/IDNOs Connections Meter Operators HSS&TT Network Operations UK Power Networks Services Other THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Version: 2.0 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Revision Record Version 2.0 Review Date 04/09/2017 Date 02/07/2015 Author Stephen Tucker Why has the document been updated: Document revised following business feedback. What has changed: Process added (Section 5). Design options (Section 6.2) and installation requirements (Section 7) refined. HV cable sheath bonding photos added (Figure 7-2). Warning label availability updated (Section 7.5). Operational requirements including Power On updated (Section 8.2/8.3). Recent examples added (Appendix A). Example operational document added (Appendix B). Document title amended. Version 1.0 Review Date 04/09/2017 Date 04/09/2012 Author Stephen Tucker Original © UK Power Networks 2015 All rights reserved 2 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Contents 1 Introduction ............................................................................................................. 5 2 Scope ....................................................................................................................... 5 3 Abbreviations and Definitions ................................................................................ 5 4 Background ............................................................................................................. 6 4.1 Hot Site ..................................................................................................................... 6 4.2 Earth Potential Rise (EPR) ........................................................................................ 6 4.3 Substation Earthing Database ................................................................................... 6 5 Process .................................................................................................................... 7 6 Design Requirements .............................................................................................. 8 6.1 Information Requirements ......................................................................................... 8 6.2 Supply Options .......................................................................................................... 8 6.2.1 Overview ................................................................................................................... 8 6.2.2 Option 1: HOT Grid/Primary Site Supply from a Dedicated Secondary Substation Inside the HOT Zone ............................................................................................... 10 6.2.3 Option 2: Dedicated Secondary Substation Outside the HOT Zone ......................... 11 6.2.4 Option 3: RMU Outside the HOT Zone and a Transformer Inside the HOT Zone .... 12 6.2.5 Option 4: Dedicated Secondary Substation Inside the HOT Zone............................ 13 6.2.6 Option 5: Overhead Line – Dedicated Transformer/Substation Inside HOT Zone .... 14 6.2.7 Option 6: Overhead Line – Dedicated Transformer/Substation Outside HOT Zone . 15 6.2.8 Option 7: LV Network using an Isolation Transformer .............................................. 16 7 Installation Requirements ..................................................................................... 17 7.1 Secondary Substation ............................................................................................. 17 7.2 Lead Sheathed Cables ............................................................................................ 17 7.3 Jointing .................................................................................................................... 18 7.4 Miscellaneous Materials .......................................................................................... 19 7.5 Warning Labels ....................................................................................................... 19 8 Operational Requirements .................................................................................... 21 8.1 General ................................................................................................................... 21 8.2 Documentation ........................................................................................................ 21 8.3 Power On ................................................................................................................ 21 8.4 NetMap.................................................................................................................... 22 9 References ............................................................................................................. 23 Appendix A – Examples ................................................................................................... 24 A.1 National Grid Acton Lane 22kV................................................................................ 24 A.2 Rayleigh Main.......................................................................................................... 25 A.3 Norwich Main........................................................................................................... 27 © UK Power Networks 2015 All rights reserved 3 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 A.4 Bramford Grid .......................................................................................................... 28 Appendix B – Operational Document .............................................................................. 29 Figures Figure 5-1 – Process Flowchart ............................................................................................ 7 Figure 6-1 – Supply Options Overview .................................................................................. 9 Figure 7-1 – RMU Cable Sheath Bonding ........................................................................... 17 Figure 7-2 – RMU Cable Sheath Bonding Example ............................................................ 18 Figure 8-1 – Power On HOT Site Annotation ...................................................................... 22 Figure A-1 – LV Supply to National Grid 22kV Substation at Acton Lane ............................ 24 Figure A-2 – LV Supply to National Grid 22kV Substation at Acton Lane ............................ 24 Figure A-3 – Rayleigh 400kV and 132kV Substations ......................................................... 25 Figure A-4 – Rayleigh 400kV and 132kV Substations – Power On Extract.......................... 25 Figure A-5 – Norwich Main 400kV and 132kV Substations ................................................. 27 Figure A-6 – LV Supply to Norwich Main 400kV and 132kV Substations ............................ 27 Figure A-7 – LV Supply to Bramford 400kV and 132kV Substations ................................... 28 Tables Table 4-1 – EPR Threshold for a HOT Site Classification ..................................................... 6 Table 6-1 – Supply Options Overview ................................................................................... 8 Table 7-1 – Warning Labels ................................................................................................ 19 Table 8-1 – Power On HOT Site Pin Text............................................................................ 21 © UK Power Networks 2015 All rights reserved 4 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 1 Introduction This standard details the additional requirements for the provision of LV supplies to all higher voltage sites (e.g. 132kV, 33kV etc.) that are HOT or owned by National Grid1. Supplies to these sites require special consideration to avoid the earth potential rise (EPR) during an earth fault being exported onto the HV or LV network and into a customer's premises where it could cause danger to life or damage to property. 2 Scope This standard applies to the provision of LV supplies in EPN, LPN and SPN to UK Power Networks HOT sites, third party HOT sites and all National Grid sites. This standard does not apply to supplies to mobile telephone base stations on National Grid towers which are covered in EDS 08-0030. This standard is intended for internal and external use. 3 Abbreviations and Definitions Term Definition COLD Site A site where the EPR is less than 430V or 650V (for high reliability protection) EPR Earth potential rise – the potential (voltage) rise that occurs on any metalwork due to the current that flows through the ground when an earth fault occurs on the network High reliability protection Main protection systems that clear the fault current within 200ms HOT Site A site where the EPR is greater than 430V or 650V (for high reliability protection) NetMap UK Power Networks graphical information system (GIS) Normal reliability protection Main protection systems that clear the fault current in excess of 200ms Power On UK Power Networks network management system ROEP Rise of earth potential – another term for EPR 1 Not all National Grid sites are HOT but they should be treated as HOT for the purpose of providing LV supplies as detailed in this standard. © UK Power Networks 2015 All rights reserved 5 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 4 Background 4.1 Hot Site A site is classified as HOT when the earth potential rise (EPR) during an earth fault exceeds 430V or 650V as defined in Table 4-1. Table 4-1 – EPR Threshold for a HOT Site Classification Substation Voltage Source Circuit Protection EPR Comments 400kV, 275kV, 132kV, 66kV, 33kV, 25kV High reliability 650V Main protection systems that clear the earth fault current within 200ms Normal reliability 430V Main protection systems that clear the earth fault current in excess of 200ms Normal reliability 430V Main protection systems that clear the earth fault current in excess of 200ms 20kV, 11kV, 6.6kV 4.2 Earth Potential Rise (EPR) When an earth fault occurs on a cable or at a substation a proportion of the fault current will return to the source substation through the ground. This ‘ground return’ current will flow into the ground through the earth connection(s) closest to the fault; the current flow through the substation earth resistance will cause the voltage of the substation earth connections to rise above that of a remote (or true) earth. This voltage is known as the earth potential rise or EPR. Note: Some current will flow through the cable sheath back to the source and some will flow through the ground, it is only the current that flows through the ground that causes the EPR. 4.3 Substation Earthing Database The substation earthing database2 contains the available earthing related data for all grid and primary substations together with a substation classification of HOT or COLD. For further information refer to EDS 06-0002. If a HOT zone plot for an existing UK Power Networks HOT substation is required please contact the document author. Any relevant information to the connection can be provided by the UK Power Networks Connection Designer if appropriate. 2 UK Power Networks Substation Earthing Database is available from the UK Power Networks Intranet using the following link Substation Earthing Database. © UK Power Networks 2015 All rights reserved 6 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 5 Process An overview of the design and implementation process is shown in Figure 5-1. The sections that follow provide further details on each part. Design Delivery Network Records START Obtain site information (EPR, HOT zone etc) (Section 5.2) Construct substation in accordance with ECS 06-0023 (Section 7.1) HV or LV supply? Isolate HV cable sheaths, install cables in ducts etc (Section 7.2) HV Select supply option (Table 6-1) Design secondary substation using earthing design tool (EDS 06-0014) LV Apply warning labels (Section 7.4) Prepare operational document (Section 8.2) Ensure earthing doesn’t extend outside the HOT zone Review operational document with Network Manager and Operational Safety Manager (Section 8.2) Connect substation to main earthing system of higher voltage substation Prepare SAN showing HOT Site pins (Section 8.3) Load operational document into Alfresco (Section 8.2) Design supply with TT earth in accordance with EDS 08-0129 or EDS 08-0143 (Section 6.2.3) Customer to provide isolation transformer, RCD and earth (Table 6-1) Apply pins to Power On (Section 8.3) Provide supply from LV network without an earth terminal (TT earthing) Link Power On to operational document in Alfresco (Section 8.3) Apply warning labels (Section 7.4) Update NetMap (Section 8.4) END Figure 5-1 – Process Flowchart © UK Power Networks 2015 All rights reserved 7 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6 Design Requirements 6.1 Information Requirements The following information is required to enable a suitable supply to be designed: Maximum earth potential rise. Latest plot of the HOT zone and necessary potential contours. Other earthing information i.e. soil resistivity, earthing study results, position of buried services/metalwork etc. 6.2 Supply Options 6.2.1 Overview An overview of various supply options are detailed in Table 6-1 and shown in Figure 6-1. The specific requirements for each option are detailed in the sections that follow. Table 6-1 – Supply Options Overview Option Source Description Section 1 Secondary Substation HOT grid/primary site supply from a dedicated secondary substation inside the HOT zone 6.2.2 2 Dedicated secondary substation outside the HOT zone 6.2.3 3 RMU Outside the HOT Zone and a Transformer Inside the HOT Zone 6.2.4 4 Dedicated secondary substation inside the HOT zone 6.2.5 Overhead Line Dedicated transformer/substation inside HOT Zone 6.2.6 Dedicated transformer/substation outside HOT zone 6.2.7 LV Network Via isolation transformer 6.2.8 5 6 7 © UK Power Networks 2015 All rights reserved 8 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Option 1: HOT Grid/Primary Dedicated Secondary Substation Inside the HOT Zone HOT Grid/Primary Substation Option 2: Dedicated Secondary Substation Outside the HOT Zone HV Network HOT Site HOT Site Supplies Only R M U HOT Site Supplies Only R M U Option 4: Dedicated Secondary Substation Inside the HOT Zone Normal Supplies HV Network HV Network HV Earth LV Earth HV Network HV/LV Earth R M U HV Earth LV Earth HV/LV Earth Normal Supplies R M U Option 3: RMU Outside the HOT Zone and a Transformer Inside the HOT Zone HOT Site HOT Site Supplies Only R M U HV Network HOT Site HV/LV Earth HOT Site Supplies Only R M U HV Earth Metalwork/ LV Earth R M U HV Network HV Network Option 5: Overhead Line – Dedicated Transformer/ Substation inside HOT Zone HV Overhead Network Normal Supplies HV/LV Earth Option 6: Overhead Line – Dedicated Transformer/ Substation Outside HOT Zone HV Overhead Network HOT Site HOT Site Pole Tx Pole Tx HOT Site Supplies Only HV/LV Earth HOT Site Supplies Only HV Earth LV Earth HV Overhead Network HV Overhead Network Option 7: LV Network using an Isolation Transformer LV Network HOT Site Isolation Tx HOT Site Supplies Only LV Earth LV Network Figure 6-1 – Supply Options Overview © UK Power Networks 2015 All rights reserved 9 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.2 Option 1: HOT Grid/Primary Site Supply from a Dedicated Secondary Substation Inside the HOT Zone Requirement Details Supply Source HV Cable Arrangement HOT Grid/Primary Substation 4 2 HOT Site Supplies Only R M U HV/LV Earth 1 2 7 Normal Supplies R M U 8m HV Network HV Earth LV Earth 8 2 1 Notes: 1 - EPR <2kV 2 - Warning labels Application/EPR Limit Any HOT grid or primary substation supplying 11/6.6kV distribution network Type of Supply Dedicated standard secondary substation located within and supplied from the HOT grid/primary substation Substation Earthing Standard earthing arrangement designed in accordance with EDS 06-0014 using the earthing design tool Where the secondary substation is installed within the earthing system of a higher voltage substation (e.g. grid, primary or National Grid substation) it should be connected to the main earthing system via two separate connections and additional earth rods will not usually be required. Supply Earthing Combined HV/LV earth bonded to main substation earth Other Requirements Substation generally first leg out of grid/primary switchboard or via spare circuit-breaker. HV/LV earths segregated at the next downstream substation unless the transfer voltage is below the 430V Label (from Table 7-1) Label 4 at substation. Labels 1, 2, 7 and 8 at next substation Comments EPR limit set by transformer LV winding power frequency withstand voltage at the downstream substation © UK Power Networks 2015 All rights reserved 10 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.3 Option 2: Dedicated Secondary Substation Outside the HOT Zone Requirement Details Supply Source HV Cable Arrangement HV Network 1 HOT Site 4 1 2 2 R M U 3 HOT Site Supplies Only 8m HV Earth LV Earth 4 4 4 4 7 8 HV Network Notes: 1 - EPR <2kV 2 – Neutral-earth link removed 3 - LV cable installed in insulated duct 4 - Warning labels Application/EPR Limit Any HOT site where the EPR is less than 2kV Type of Supply Dedicated standard secondary substation located outside the HOT zone Substation Earthing Standard earthing arrangement designed in accordance with EDS 06-0014 using the earthing design tool Where the secondary substation is installed within the earthing system of a higher voltage substation (e.g. grid, primary or National Grid substation) it should be connected to the main earthing system via two separate connections and additional earth rods will not usually be required. Supply Earthing Segregated HV/LV earth. HV earth installed outside the HOT zone and LV earth bonded to HOT site earth Other Requirements LV cable in insulated duct to preserve insulation integrity. Neutral-earth link removed and protected by insulated cover Label (from Table 7-1) Labels 1, 2, 4, 7 and 8 at substation. Label 4 at HOT site Comments Equivalent to NG TS 3.1.2 Figure 3. EPR limit set by LV cable sheath power frequency withstand voltage © UK Power Networks 2015 All rights reserved 11 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.4 Option 3: RMU Outside the HOT Zone and a Transformer Inside the HOT Zone Requirement Details Supply Source HV Cable Arrangement HV Network HOT Site 7 R M U 1 5 2 3 HV Earth 4 HOT Site Supplies Only Metalwork/ LV Earth 4 5 5 6 HV Network Notes: 1 - EPR <12kV 2 - HV cable sheath insulated at transformer 3 - HV cable installed in insulated duct 4 - Cable length less than 1km 5 - Warning labels Application/EPR Limit Any HOT site where the EPR is less than 12kV Type of Supply Dedicated secondary substation with the RMU outside the HOT zone and the transformer inside the HOT zone Note: A variation on this arrangement is to use a metering unit located with the RMU or with the transformer to provide an HV supply Substation Earthing Standard earthing arrangement designed in accordance with EDS 06-0014 using the earthing design tool Where the secondary substation is installed within the earthing system of a higher voltage substation (e.g. grid, primary or National Grid substation) it should be connected to the main earthing system via two separate connections and additional earth rods will not usually be required. Supply Earthing Segregated HV/LV earth HV RMU earth installed outside the HOT zone. Transformer and LV earth bonded to HOT site earth Other Requirements HV cable maximum length of 1km HV cable sheath bonded to RMU earth and insulated from the transformer (sheath cut back inside cable box and insulated in accordance with 11kV Jointing Manual) Label (from Table 7-1) Label 7 at substation. Labels 4, 5 and 6 at HOT site Comments Equivalent to NG TS 3.1.2 Figure 2. EPR limit set by HV cable sheath power frequency withstand voltage Cable length to limit induced voltage to 65V due to single-point cable bonding. Transformer faults should be cleared by the earth fault protection on the ring main unit © UK Power Networks 2015 All rights reserved 12 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.5 Option 4: Dedicated Secondary Substation Inside the HOT Zone Requirement Details Supply Source HV Cable Arrangement 7 4 Normal Supplies R M U HV Network HV/LV Earth HOT Site 3 HOT Site Supplies Only R M U 2 4 HV/LV Earth See Figure 8 4 5 3 Notes: 1 - EPR <5kV 2 - HV cable sheaths bonded together and insulated from RMU 3 - HV cable installed in insulated duct in HOT zone 4 - Warning labels 7 HV Network R M U 4 Normal Supplies HV/LV Earth Application/EPR Limit Any HOT site where the EPR is less than 5kV Type of Supply Dedicated standard secondary substation located in the HOT zone Substation Earthing Standard earthing arrangement designed in accordance with EDS 06-0014 using the earthing design tool Where the secondary substation is installed within the earthing system of a higher voltage substation (e.g. grid, primary or National Grid substation) it should be connected to the main earthing system via two separate connections and additional earth rods will not usually be required. Supply Earthing Combined HV/LV earth bonded to main site earth Other Requirements HV cable sheaths connected together using suitable size bond and insulated at RMU from site earth HV cable in insulated duct in HOT zone to preserve insulation integrity Label (from Table 7-1) Label 7 at upstream and downstream substations either side of HOT site. Labels 4 and 5 at HOT site Comments EPR limit set by the termination method of the bonding between the cable screens. Note: The power frequency withstand voltage of the HV cable screen is 12kV and the insulated stud is 7kV © UK Power Networks 2015 All rights reserved 13 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.6 Option 5: Overhead Line – Dedicated Transformer/Substation Inside HOT Zone Requirement Details Supply Source HV Overhead Line Arrangement HV Overhead Network HOT Site 7 1 2 Pole Tx HOT Site Supplies Only HV/LV Earth HV Overhead Network 2 4 Notes: 1 - EPR <12kV 2 - Warning labels Application/EPR Limit Any HOT site where the EPR is less than 12kV Type of Supply Dedicated pole-mounted transformer or ground-mounted substation located inside the HOT zone Supply Earthing Combined HV/LV earth bonded to main site earth Other Requirements n/a Label (from Table 7-1) Label 7 at pole. Label 4 at HOT site Comments EPR limit set by transformer LV winding and LV cable sheath power frequency withstand voltage © UK Power Networks 2015 All rights reserved 14 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.7 Option 6: Overhead Line – Dedicated Transformer/Substation Outside HOT Zone Requirement Details Supply Source HV Overhead Line Arrangement HV Overhead Network 7 3 HOT Site 1 Pole Tx 2 8m HV Earth HOT Site Supplies Only LV Earth 3 HV Overhead Network 4 Notes: 1 - EPR <12kV 2 - Cable installed in insulated duct 3 - Warning labels Application/EPR Limit Any HOT site where the EPR is less than 12kV Type of Supply Dedicated pole-mounted transformer or ground-mounted substation located outside the HOT zone Supply Earthing Segregated HV/LV earth. HV earth installed outside the HOT zone and LV earth bonded to HOT site earth Other Requirements n/a Label (from Table 7-1) Label 7 at pole. Label 4 at HOT site Comments EPR limit set by transformer LV winding and LV cable sheath power frequency withstand voltage © UK Power Networks 2015 All rights reserved 15 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 6.2.8 Option 7: LV Network using an Isolation Transformer Requirement Details Supply Source LV Network Arrangement LV Network HOT Site 1 Isolation Tx HOT Site Supplies Only 2 Notes: 1 - EPR <12kV 2 - Cable installed in insulated duct 3 - Warning labels 3 LV Earth 3 4 LV Network LV Network HOT Site Cutout Isolation Transformer RCD 3 4 3 Site Earth HOT Site Cutout Isolation Transformer RCD 3 3 4 Site Earth Application/EPR Limit Any HOT site where the EPR is less than 2kV Type of Supply EDS 08-0129 or EDS 08-0143 supply from the LV network via 1:1 Δ-Υ isolation transformer (complying with BS EN 61558-2-4) in the HOT zone Supply Earthing LV earth bonded to HOT site earth. Isolation transformer enclosure bonded to site earth Other Requirements Incoming neutral not connected to isolation transformer enclosure or metalwork. No earth terminal provided (TT earthing) Isolation transformer protected by RCD Label (from Table 7-1) Label 3 next to cut-out. Label 4 next to isolation transformer Comments EPR limit set by LV cable sheath power frequency withstand voltage For a customer site the boundary shall be at the cut-out and the provision, ownership and maintenance of the isolation transformer , RCD and LV earth is the customers responsibility © UK Power Networks 2015 All rights reserved 16 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 7 Installation Requirements 7.1 Secondary Substation The secondary substation earthing system shall be constructed in accordance with ECS 06-0023 paying particular attention to the additional HOT site requirements below: 7.2 Installation of HV cable sheath bonding where required as shown in Figure 7-1 and Figure 7-2. Installation of separate HV and LV earths if required and Removal of the neutral-earth link. Removal/disconnection of associated 13A sockets. Installation of isolation transformer for RTU supply. Installation of appropriate warning labels (refer to Section 7.5) at both the HOT site and any other associated substations. If installed within the earthing system of a higher voltage substation (e.g. grid, primary or National Grid) connected to the main earthing system via two separate connections. Lead Sheathed Cables If lead sheathed (PILC) cables are connected to the HOT site they will export the EPR and therefore they shall be replaced with insulated sheathed cables within the HOT zone and five metres outside it. SW1 (LH) Cable Box SW2 (RH) Cable Box RMU Connector 03196H or MF15/5/SH from 02806D Insulated Earth Stud Removed and Blanked Off Cover Connector with Heat Shrink Cable Sheaths Insulated from Cable Boxes Aluminium or Copper Insulated Cable Sheath Bond Sized to match Earthing System Heat Shrink Boot Figure 7-1 – RMU Cable Sheath Bonding © UK Power Networks 2015 All rights reserved 17 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Figure 7-2 – RMU Cable Sheath Bonding Example 7.3 Jointing Jointing of cables between sites with high EPRs shall be carried out using insulated working practices in accordance with new procedure HSS 40 050 or, in the interim, National Grid instruction NSI 5. Joints within the HOT zone shall be avoided. 11kV cable is available in 250m drums as standard or 1000m drums by special order. © UK Power Networks 2015 All rights reserved 18 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 7.4 Miscellaneous Materials Material Material Code or Reference Description Comments 11kV Cable Duct EAS 00-0002 Ducts and duct accessories Use 33kV ducts from Emtelle LV Duct EAS 00-0002 Ducts and duct accessories Cable Screens Connector 03196H Connector Straight Thru Main 300 (x3) 02806D LV 185mm Waveform Pole Term Direct Connector 7.5 Warning Labels The warning labels detailed Table 7-1 shall be installed as specified in Section 6.2. Table 7-1 – Warning Labels 3 No Situation/Location Reference 4 (Material Code ) Specification 1 Install in prominent position inside fence/enclosure EDS 07-0009.117 100mm x 150mm adhesive label 2 In LV cabinet or micro/compact EDS 07-0009.118 100mm x 50mm adhesive label 3 Next to the cut-out EDS 07-0009.130 100mm x 50mm adhesive label (21515D) (21758H) 4 3 4 Next to the cut-out EDS 07-0009.131 Label 100mm x 37.5mm adhesive label For the availability of labels without a material code please contact the author or refer to EAS 07-0021. UK Power Networks logistics material code. © UK Power Networks 2015 All rights reserved 19 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 3 No Situation/Location Reference 4 (Material Code ) Specification 5 Next to affected equipment EDS 07-0009.132 100mm x 37.5mm adhesive label 6 On substation door EDS 07-0009.133 100mm x 50mm adhesive label 7 On substation door EDS 07-0009.134 100mm x 50mm adhesive label 8 In LV cabinet or micro/compact EDS 07-0009.171 (21517X) 75mm x 110mm adhesive label © UK Power Networks 2015 All rights reserved Label 20 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 8 Operational Requirements 8.1 General Any installation that involves different earthing systems which are not bonded together carries a level of risk should simultaneous contact occur between the two systems. Special care is needed when working on circuits or switchgear where access to the different earthing systems may be made possible. The main issues are: Applying a circuit main earth at the HOT site or adjacent sites. Working on cables between different earthing systems. Insulated working should be considered where applicable, refer to HSS 40 050 for further information. It is therefore important that the switchgear maintenance and cable working requirements are considered at the design stage. 8.2 Documentation It is the joint responsibility of the designer, project manager and senior authorised person to determine any special operating arrangements and prepare an operational requirements document. An example document is included in Appendix B. The document shall be added to Alfresco and linked to the Power On HOT Site pin detailed in Section 8.3. Any special operating arrangements should be approved by the Operational Safety Manager and the Control/Network Manager. 8.3 Power On A HOT Site pin shall be applied on the Power On diagram to each affected site to highlight any non-standard earthing requirements. An example is shown in Figure 8-1 both ‘Action Ln Opp Waxlow Rd National Grid’ (the HOT site with non-standard earthing) and the sites either side have HOT Site pins. Examples of the HOT Site pin text are shown in Table 8-1. Table 8-1 – Power On HOT Site Pin Text HOT Site This substation provides a supply to a HOT site and has a non-standard earthing arrangement and/or insulated cable screens. Refer to the attached site specific operating instructions for further information. This substation shall not be used to provide LV supplies to other customers. Warning Connected to a HOT Site This substation is connected to a HOT site with a non-standard earthing arrangement and/or insulated cable screens. Refer to the attached site specific operating instructions for further information. The relevant information should be included on the System Alteration Notice (SAN) to allow the diagram to be correctly annotated. © UK Power Networks 2015 All rights reserved 21 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Figure 8-1 – Power On HOT Site Annotation 8.4 NetMap On completion of the installation NetMap shall be updated to show: Insulated cable sheaths. Sections of overhead line that should not be undergrounded. Any other bespoke installation details. © UK Power Networks 2015 All rights reserved 22 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 9 References EAS 00-0002 Cables and Joints EDS 06-0001 Earthing Standard EDS 06-0002 HOT Site Requirements (internal document only) EDS 06-0014 Secondary Substation Earthing Design EDS 06-0017 Customer Installation Earthing Design ECS 06-0023 Secondary Distribution Network Earthing Construction EAS 07-0021 Signs and Labels for Operational Sites EDS 08-0030 LV supplies to Mobile Phone Base Stations Mounted on 132, 275 and 400kV Towers (internal document only) EDS 08-0129 LV Metered Connections up to 100A Single-phase EDS 08-0143 LV Metered Connections Above to 100A Single-phase 11kV Jointing Manual HSS 40 050 Controlling Impressed Voltages on Underground Cable Systems (future HSS document) National Grid TS 3.1.2 Earthing National Grid NSI 5 Insulated Working on Cable Systems © UK Power Networks 2015 All rights reserved 23 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Appendix A – Examples A.1 National Grid Acton Lane 22kV Acton Lane consists of 22kV National Grid substation as shown in Figure A-1. Although Acton Lane is not currently classified as a HOT site all supplies to National Grid sites have to be treated as HOT to cater for future changes to the network or an increase in fault level. An LV supply was requested by National Grid and provided from a secondary substation using option 4 (Section 6.2.5) as shown in Figure A-2. Figure A-1 – LV Supply to National Grid 22kV Substation at Acton Lane 240 Gibbons Road SW1 Panel 48 24843 Acton Ln Opp Waxlow Rd National Grid 24731 Waxlow Rd Unit A Centrus 24650 Acton Lne Hamm Med Res HOT Site Figure A-2 – LV Supply to National Grid 22kV Substation at Acton Lane © UK Power Networks 2015 All rights reserved 24 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 A.2 Rayleigh Main Rayleigh Main consists of a 400kV National Grid substation and a UK Power Networks 132kV substation. Rayleigh Main is HOT with a maximum EPR of 1777V for a fault on the 400kV network. The substations are shown in Figure A-3 and the supply arrangement is shown in Figure A-4. Rayleigh Main 132kV Rayleigh GIS Local and Local 2 11kV CEGB 400 Grid11kV Rayleigh Main 400kV NG Switching Station 11kV Figure A-3 – Rayleigh 400kV and 132kV Substations Figure A-4 – Rayleigh 400kV and 132kV Substations – Power On Extract © UK Power Networks 2015 All rights reserved 25 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 A.2.1 Rayleigh Main 400kV via NG Switching Station NG Switching Station is a new secondary substation containing a ring main unit without a transformer. During the design and construction of this substation the switchgear at the CEGB substation located within Rayleigh Main 400kV was solidly bonded to the Rayleigh Main 400kV earth grid. The 11kV cable that feeds into the CEGB substation was of PILC construction and the cable sheath was therefore not insulated from the soil. To separate the earthing the PILC cable was overlaid with plastic sheathed cable. The cable sheath was insulated from the site earth in the CEGB substation. This is an example of Option 3 (Section 6.2.4). A.2.2 Rayleigh Main 132kV Supply via Rayleigh GIS Local and Rayleigh GIS Local 2 Rayleigh Main 132kV has two disparate 400V three-phase supplies. Each is supplied from a separate secondary substation located 3m outside the Rayleigh Main 132kV substation fence. The secondary substations each have an independent earthing system but they are bonded together; however neither is bonded to the Rayleigh Main 132kV earth grid. The three-phase 400V supply from each of the secondary substations is bonded to the Rayleigh Main 132kV substation earth grid at the LVAC distribution board. At each secondary substation the LV neutral has been disconnected from the substation earth. This is where the rise of potential will occur during fault conditions. A label has been applied to draw attention to the arrangement. The power socket in the distribution substation has also been disconnected. This arrangement prevents the earth potential rise occurring during a 400kV fault at Rayleigh Main 400kV from being exported onto the 11kV earthing system. It also prevents other customers from being supplied from this substation as any 400V connections would be bonded to HOT substation earth grid. This is an example of Option 2 (Section 6.2.3). © UK Power Networks 2015 All rights reserved 26 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 A.3 Norwich Main Norwich Main consists of a 400kV National Grid substation and a UK Power Networks 132kV substation as shown in Figure A-5. Norwich Main is HOT with a maximum EPR of 2650V for a fault on the 400kV network. A dual LV supply was requested by National Grid for the 400kV substation and a single LV supply was required for the 132kV substation. The supplies were provided using option 4 (Section 6.2.5) from overhead line on one side and cable on the other as shown in Figure A-6. Norwich Main 400kV Norwich Main 132kV Figure A-5 – Norwich Main 400kV and 132kV Substations Pole 8 Pole 7 HV Earth HOT Zone Norwich Main 400kV Norwich Main Dunston Norwich Main 132kV HOT Site Supply 1 Norwich Main 132kV Local B HOT Site Supply 2 HOT Site Supply HV/LV Earth HV/LV Earth Norwich – London Liverpool St Main Line Orange Mast Ipswich Road Normal Supply HV/LV Earth Pole 12 Pole 11A OHL Pole 11 Cable HV Earth Figure A-6 – LV Supply to Norwich Main 400kV and 132kV Substations © UK Power Networks 2015 All rights reserved 27 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 A.4 Bramford Grid Bramford Grid consists of 400kV and 132kV substations. Bramford Grid is HOT with a maximum EPR of 2880 for a fault on the 400kV network. A ring supply was requested by National Grid for each substation. The supplies were provided using options 5 and 6 (Sections 6.2.6/6.2.7) from overhead line as shown in Figure A-7. Pole 9b Euromast Pole Tx Pole 7b New ABSD Pole 8b Cable sheath insulated from earth HV cable in duct HOT Zone Bramford Grid 400/132kV New Secondary Substation Cable sheaths bonded to steelwork earth CEGB 400kV Site To be removed at later stage HV/LV Earth HV/LV Earth To be removed when NG construction complete CEGB 132kV Site Pot End Bramford Grid Temp Supply Cable sheaths to be connected to steelwork earth Pole 7c HV/LV Earth Pole 1c Figure A-7 – LV Supply to Bramford 400kV and 132kV Substations © UK Power Networks 2015 All rights reserved 28 of 29 Supplies to HOT Sites and National Grid Sites Document Number: EDS 08-0121 Version: 2.0 Date: 02/07/2015 Appendix B – Operational Document An example operational document for the Acton Lane example in Appendix A is available as a separate document EDS 08-0121B. © UK Power Networks 2015 All rights reserved 29 of 29