Magellan QT
®
Quick Install Thermoplastic Exit Sign
housing. Housing design simplifies installation,
and does not require hard wire terminations
inside of the exit housing.
MQTELNCWSRSC
The installation process enables the installer to
easily make all wiring connections in the
junction box, while all mechanical connections
between the exit housing and canopy are made
tool free. The standard product can be top,
end, or back-to-wall mounted, simply by
selecting the access port located on the top,
end or back of the exit enclosure. All access
ports incorporate mechanical connections for
direct installation to standard junction boxes via
the mounting canopy.
Illumination
Illumination of the exit stencil face is
accomplished with long lasting, high output
Light Emitting Diodes (LEDs). Hot spots and
striations are eliminated by the internal “light
chamber” especially designed around the high
performance LED array.
MQTDL12WSRSC
General Description
The Magellan QT Thermoplastic LED exit sign
combines an appealing design, high impact
thermoplastic and high performance electronics
to ensure reliability. Softly rounded corners and
the universal mounting configuration allow the
product to blend nicely with all modern
interiors.
The Magellan QT has been engineered to
ensure ease of installation, as well as provide
years of low cost, efficient service. The
simplified installation process makes the
Magellan QT LED exit both a preferred
specification product and electrical contractor
favorite.
Housing
Impact resistant, UL 94 V-0, 5 VA thermoplastic
housing with NFPA-type field selectable chevrons. Chevrons can be installed/removed from
outside the exit housing. White and black
housing finish is available.
Installation
The canopy installs to a standard junction box
by using screws supplied with the junction box,
or by utilizing “no tools” connectors supplied
with the Magellan QT luminaire.
Electrical power supply connections are made
using the modular plug assemblies supplied
with the product, and are routed though the
center of the canopy for connection to the mating
plug assembly furnished with the exit housing.
The Magellan QT exit housing will mechanically
“snapfit” to the canopy. Once connected the
Magellan QT exit will route AC normal utility
power and begin charging the battery when it
recognizes AC utility power is available.
Electronics
AC Only and Emergency Operation Units
Dual voltage 120/277 VAC input with surge
protection is standard.
Self-Powered Units
All components are located within exit housing.
An indicator light is located on the bottom of
the housing to signify that AC utility is present.
UL damp location listing is available. (DL option
on select models)
AC lockout prevents battery drain prior to the
initial energizing of utility power.
Mechanical and electrical connections allow
installation to a standard ceiling or wall
mounted junction box without the need to
make hard wire terminations within the exit
The low voltage disconnect (LVD) feature will
disconnect the battery prior to an unacceptable
deep discharge, but not before the required 90
minute emergency operation.
HL-1908 Rev. 5/2/13
The brownout protection circuitry will
automatically switch the unit into the
emergency mode if the utility voltage sags
below 20% of nominal.
Exits
Battery charging circuitry is entirely solid-state,
and of a constant current design. Battery recharge time after a complete discharge is less
than the required UL 924 standard.
Solid-state circuitry causes an instantaneous
transfer to battery power if either the loss of
AC utility, or a brownout condition is detected.
When line voltage is present and stabilized, the
transfer circuitry switches back to normal
operation and begins recharging the battery.
The transfer circuitry can be tested via a
momentary test switch located on the bottom
of the housing.
Battery
A maintenance free, sealed nickel cadmium
battery is standard. Construction is of the
sintered plate design and the battery assembly
is equipped with a quick connect plug assembly
for easy installation.
Standard sustained emergency operation is for
90 minutes with the illumination source
providing full light output. Batteries can be
serviced by easily removing the exit stencil front
for battery inspection and/or replacement.
The suggested operating temperature range is
20°F (-7°C) to 95°F (35°C). Typical life of lead
calcium battery is up to 5 years; for nickel cadmium battery up to 10 years.
Electrical Specifications
AC Only Operation
Input Power Requirements at 120 VAC
Red – .89 watts
Green – 2.17 watts
Self-Powered Operation
Input Power Requirements at 120 VAC
Red – 3.62 watts
Green – 2.79 watts
Listings
•UL 924 listed
• UL Damp Location listing optional
• NFPA 101, NEC, BOCA, OSHA and IBC
illumination standards
Warranty
3-year limited warranty.
Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Actual performance may differ as a result of
end-user environment and application.
Note: Specifications are subject to change without notice.
Magellan QT
®
®
Quick Install Thermoplastic Exit Sign
Dimensions
Suggested Specification
Circuitry shall include both a “push-to-test” switch and “utility
power present” indicator LED.
Furnish and install Holophane’s LED exit sign model
_______________________. The exit shall be constructed to
meet Underwriter’s Laboratories, Inc. Standard #924 and the
National Electrical Code (NEC).
Battery (Self-powered operation only)
15.5”
(393.7mm)
13.75”
(349.2mm)
9.5”
(241.3mm)
The battery shall be maintenance free, sealed nickel cadmium
utilizing sintered plate construction and polypropylene
separators for trouble-free operation in ambient temperatures
up to 95ºF (35ºC).
15.0”
(381mm)
Installation and Operation
1.66”
(4.2mm)
8.05”
(204.47mm)
7.3”
(185.4mm)
5.05”
(128.2mm)
15.5”
(393.7mm)
13.75”
(349.2mm)
9.5”
(241.3mm)
15.0”
(381mm)
1.66”
(4.2mm)
8.05”
(204.47mm)
1.55”
(39.3mm)
5.05”
(128.2mm)
13.75”
(349.2mm)
Illumination
The Magellan QT exit sign shall incorporate high intensity
LEDs. The LEDs shall be designed so that the unlikely failure
of the LED will not affect the integrity of the total sign in the
emergency mode. The Magellan QT exit equipped with red
LEDs shall consume .89 watts (120 VAC) or 3.62 watts (120
VAC Self-powered).
If equipped with green LEDs, it shall consume 2.17 watts (120
VAC) or 2.79 watts (Self-powered).
Housing
The Magellan QT LED exit housing shall be constructed of
impact resistant, UL 94 V-0, 5 VA thermoplastic, with NFPAtype field selectable chevrons. The chevrons can be configured
for direction in the field without removal of the exit stencil.
The housing, stencil and canopy finish shall be either white
or black. Mechanical connection of the exit housing to the
junction box shall be accomplished without any requirement to
open the exit housing for wiring or mechanical terminations.
Charger (Self-powered only)
1.66”
(4.2mm)
7.3”
(185.4mm)
Exit shall be easily field connected to a 120 or 277 VAC, 60
1.66”
hertz, unswitched
power source. Installation must comply
(4.2mm)
with the NEC as well as other applicable codes. Product
installation should
not require entry inside of the exit housing
.60”
(15.2mm) wiring connections in the field. Mechanical
to make or arrange
connections
to standard junction boxes shall be accomplished
5.05”
(128.2mm)
by utilizing the access ports and canopy connector supplied
with the product. (Self-Powered Only) - Upon utility power
failure or brownout, the unit shall automatically transfer to
battery power and maintain the required illumination level for
a minimum period of 90 minutes. Upon restoration of utility
power, the charger shall restore the battery to full charge
within UL 924 requirements following a rated discharge of not
more than 90 minutes.
13.75”
(349.2mm)
1.55”
(39.3mm)
Product shall utilize a constant current charging system which
will maintain the battery at full capacity without the need of
periodic exercising or equalization. The following features
shall be standard: low voltage disconnect (LVD), brownout
protection and AC lockout.
.60”
(15.2mm)
5.05”
(128.2mm)
Exits
Ordering Data
MQTE
Series
MQTE Magellan QT
thermoplastic exit
MQTD Magellan QT
thermoplastic
double head exit
with 2 T6, 5.4 watt tungsten lamps
L
How to construct a catalog number
Example: MQTE L NC W SR S C NK
NC
W
SR
S
C
C1
Frame
Number of Faces
Letter/Face Color
Mounting
S Single face
C Canopy mount
W White thermoplastic SGThermoplastic
D Double face
B Black thermoplastic stencil face, green letU1 Universal face
ter
1 1 door kit, 2 stencil
SRThermoplastic
Operation
faces, 2 lenses
stencil face, red letter
1
Options (Factory installed)
AM AC only multi-voltage 120/277 VAC input
C1 120VAC two circuit wiring (Available with “AM” operation only)
1
NC Nickel cadmium emergency 120/277 VAC input
C2
277
VAC,
two
circuit
wiring
(Available with “AM” operation only)
122 Lead calcium emergency 12 watt head capacity 120/277VAC input
BFBuzzer/flasher (Not available with “AM” or “NK”)
2
BZ
Buzzer
(Not
available
with
“AM”
or “NK”)
14N Nickel cadmium emergency 14 watt head capacity 120/277VAC input
DL Damp location (Not available with options NK, ST, or MQTDL12, MQTDL18)
182 Lead calcium emergency 18 watt head capacity 120/277VAC input
F
Fire
alarm
interface
(Not
available
with “AM” or “NK”)
18N2 Nickel cadmium emergency 18 watt head capacity 120/277VAC input
FL Flasher (Not available with “AM” or “NK”)
252
Lead calcium emergency 25 watt head capacity 120/277VAC input
VRS Vandal resistant lens (Available with MQTD only) order 1 per face
Lamp Type
L LED direct
1 “MQTE” only
2 “MQTD” only
X1
X2
X3
LL 1
200 volt 50/60 Hz transformer
220 volt 50/60 Hz transformer
240 volt 50/60 Hz transformer
Matching low level remote exit, thermoplastic frame (“MQTD” 18, 18N or 25 operation only,
not available with NK)
available with NK)
LP 1
EX
NK
TP
T7 T9 H7 H12 ST Matching low level remote exit, aluminum frame (“MQTD” 18, 18N or 25 operation only, not
Special input transformer (specify voltages and frequency). Consult factory
Self diagnostics (not available with “AM” operation)
Tamperproof screws (includes tamperproof bit)
Tungsten 7 watt, optional heads for MQDT only
Tungsten 9 watt, optional heads for MQDT only
Halogen 7 watt, optional heads for MQDT only
Halogen 12 watt, optional heads for MQDT only
Quick check self diagnostics with 15 minute time delay
1 “LP” and “LL” options reflect price of remote exit and wiring harness only to be added to price of master exit
2 Available on 25 watt lead calcium and nickel cadmium batteries
3 Available with AM operation only
Accessories (Ships separately) Available with MQTE series only
HPSPKIT12WH 1,2
Unison exit pendant kit, 12 inch, white finish
HPSPKIT12BK 1,2
Unison exit pendant kit, 12 inch, black finish
HPT15TPTOOL
Tamper-proof screwdriver
HPWG4
Wire guard for exit wall mounting
HPWG10
Wire guard for exit end mounting
PVS
Polycarbonate vandal shield (“MQTE” only)
Acuity Brands Lighting, Inc.
Holophane Headquarters, 3825 Columbus Road,
Granville, OH 43023
Acuity Brands Lighting Canada, Inc.,
35B Minthorn Blvd., Markham, ON., L3T 7N5
Holophane Europe Limited, Bond Ave.,
Milton Keynes MK1 1JG, England
Holophane, S.A. de C.V., Km. 31 Carretera
Mexico-Cuautitlan 54900 Tultitlan Edo. De Mexico
1 Consult factory for special pendant lengths
2 Not available with NK option
Contact your local Holophane factory sales representative
for application assistance, and computer-aided design and cost
studies. For information on other Holophane products and
systems, call the Inside Sales Service Department at 740-345-9631.
In Canada call 905-886-8967.
HL-1908 Rev. 5/2/13
©2012-2013 Acuity Brands Lighting, Inc. All Rights Reserved.
Visit our web site at www.holophane.com
Luminaires may utilize fluorescent or high intensity discharge
sources that contain small amounts of mercury. New disposal
labeling for these lamps includes the mercury identifier shown
on the left to indicate that the lamp contains mercury and
should be disposed of in accordance with local requirements.
Information sources regarding lamp recycling and disposal are included on
the packaging of most mercury-containing lamps and also can be located at
www.lamprecycle.org.