Download Sun Rack II Power Distribution Units User`s Guide

Document related concepts

Recurrent neural network wikipedia , lookup

Transcript
Sun Rack II Power Distribution Units
User's Guide
Part No: E23956-11
December 2016
Sun Rack II Power Distribution Units User's Guide
Part No: E23956-11
Copyright © 2009, 2016, Oracle and/or its affiliates. All rights reserved.
This software and related documentation are provided under a license agreement containing restrictions on use and disclosure and are protected by intellectual property laws. Except
as expressly permitted in your license agreement or allowed by law, you may not use, copy, reproduce, translate, broadcast, modify, license, transmit, distribute, exhibit, perform,
publish, or display any part, in any form, or by any means. Reverse engineering, disassembly, or decompilation of this software, unless required by law for interoperability, is
prohibited.
The information contained herein is subject to change without notice and is not warranted to be error-free. If you find any errors, please report them to us in writing.
If this is software or related documentation that is delivered to the U.S. Government or anyone licensing it on behalf of the U.S. Government, then the following notice is applicable:
U.S. GOVERNMENT END USERS. Oracle programs, including any operating system, integrated software, any programs installed on the hardware, and/or documentation, delivered
to U.S. Government end users are "commercial computer software" pursuant to the applicable Federal Acquisition Regulation and agency-specific supplemental regulations. As
such, use, duplication, disclosure, modification, and adaptation of the programs, including any operating system, integrated software, any programs installed on the hardware, and/or
documentation, shall be subject to license terms and license restrictions applicable to the programs. No other rights are granted to the U.S. Government.
This software or hardware is developed for general use in a variety of information management applications. It is not developed or intended for use in any inherently dangerous
applications, including applications that may create a risk of personal injury. If you use this software or hardware in dangerous applications, then you shall be responsible to take all
appropriate fail-safe, backup, redundancy, and other measures to ensure its safe use. Oracle Corporation and its affiliates disclaim any liability for any damages caused by use of this
software or hardware in dangerous applications.
Oracle and Java are registered trademarks of Oracle and/or its affiliates. Other names may be trademarks of their respective owners.
Intel and Intel Xeon are trademarks or registered trademarks of Intel Corporation. All SPARC trademarks are used under license and are trademarks or registered trademarks of
SPARC International, Inc. AMD, Opteron, the AMD logo, and the AMD Opteron logo are trademarks or registered trademarks of Advanced Micro Devices. UNIX is a registered
trademark of The Open Group.
This software or hardware and documentation may provide access to or information about content, products, and services from third parties. Oracle Corporation and its affiliates are
not responsible for and expressly disclaim all warranties of any kind with respect to third-party content, products, and services unless otherwise set forth in an applicable agreement
between you and Oracle. Oracle Corporation and its affiliates will not be responsible for any loss, costs, or damages incurred due to your access to or use of third-party content,
products, or services, except as set forth in an applicable agreement between you and Oracle.
Documentation Accessibility
For information about Oracle's commitment to accessibility, visit the Oracle Accessibility Program website at http://www.oracle.com/pls/topic/lookup?ctx=acc&id=docacc.
Access to Oracle Support
Oracle customers that have purchased support have access to electronic support through My Oracle Support. For information, visit http://www.oracle.com/pls/topic/lookup?
ctx=acc&id=info or visit http://www.oracle.com/pls/topic/lookup?ctx=acc&id=trs if you are hearing impaired.
Référence: E23956-11
Copyright © 2009, 2016, Oracle et/ou ses affiliés. Tous droits réservés.
Ce logiciel et la documentation qui l’accompagne sont protégés par les lois sur la propriété intellectuelle. Ils sont concédés sous licence et soumis à des restrictions d’utilisation et
de divulgation. Sauf stipulation expresse de votre contrat de licence ou de la loi, vous ne pouvez pas copier, reproduire, traduire, diffuser, modifier, accorder de licence, transmettre,
distribuer, exposer, exécuter, publier ou afficher le logiciel, même partiellement, sous quelque forme et par quelque procédé que ce soit. Par ailleurs, il est interdit de procéder à toute
ingénierie inverse du logiciel, de le désassembler ou de le décompiler, excepté à des fins d’interopérabilité avec des logiciels tiers ou tel que prescrit par la loi.
Les informations fournies dans ce document sont susceptibles de modification sans préavis. Par ailleurs, Oracle Corporation ne garantit pas qu’elles soient exemptes d’erreurs et vous
invite, le cas échéant, à lui en faire part par écrit.
Si ce logiciel, ou la documentation qui l’accompagne, est livré sous licence au Gouvernement des Etats-Unis, ou à quiconque qui aurait souscrit la licence de ce logiciel pour le
compte du Gouvernement des Etats-Unis, la notice suivante s’applique:
U.S. GOVERNMENT END USERS. Oracle programs, including any operating system, integrated software, any programs installed on the hardware, and/or documentation, delivered
to U.S. Government end users are "commercial computer software" pursuant to the applicable Federal Acquisition Regulation and agency-specific supplemental regulations. As
such, use, duplication, disclosure, modification, and adaptation of the programs, including any operating system, integrated software, any programs installed on the hardware, and/or
documentation, shall be subject to license terms and license restrictions applicable to the programs. No other rights are granted to the U.S. Government.
Ce logiciel ou matériel a été développé pour un usage général dans le cadre d’applications de gestion des informations. Ce logiciel ou matériel n’est pas conçu ni n’est destiné
à être utilisé dans des applications à risque, notamment dans des applications pouvant causer des dommages corporels. Si vous utilisez ce logiciel ou matériel dans le cadre d’
applications dangereuses, il est de votre responsabilité de prendre toutes les mesures de secours, de sauvegarde, de redondance et autres mesures nécessaires à son utilisation dans des
conditions optimales de sécurité. Oracle Corporation et ses affiliés déclinent toute responsabilité quant aux dommages causés par l’utilisation de ce logiciel ou matériel pour ce type
d’applications.
Oracle et Java sont des marques déposées d’Oracle Corporation et/ou de ses affiliés. Tout autre nom mentionné peut correspondre à des marques appartenant à d’autres propriétaires
qu’Oracle.
Intel et Intel Xeon sont des marques ou des marques déposées d’Intel Corporation. Toutes les marques SPARC sont utilisées sous licence et sont des marques ou des marques
déposées de SPARC International, Inc. AMD, Opteron, le logo AMD et le logo AMD Opteron sont des marques ou des marques déposées d’Advanced Micro Devices. UNIX est une
marque déposée d’The Open Group.
Ce logiciel ou matériel et la documentation qui l’accompagne peuvent fournir des informations ou des liens donnant accès à des contenus, des produits et des services émanant de
tiers. Oracle Corporation et ses affiliés déclinent toute responsabilité ou garantie expresse quant aux contenus, produits ou services émanant de tiers, sauf mention contraire stipulée
dans un contrat entre vous et Oracle. En aucun cas, Oracle Corporation et ses affiliés ne sauraient être tenus pour responsables des pertes subies, des coûts occasionnés ou des
dommages causés par l’accès à des contenus, produits ou services tiers, ou à leur utilisation, sauf mention contraire stipulée dans un contrat entre vous et Oracle.
Accessibilité de la documentation
Pour plus d’informations sur l’engagement d’Oracle pour l’accessibilité à la documentation, visitez le site Web Oracle Accessibility Program, à l’adresse http://www.oracle.com/
pls/topic/lookup?ctx=acc&id=docacc.
Accès aux services de support Oracle
Les clients Oracle qui ont souscrit un contrat de support ont accès au support électronique via My Oracle Support. Pour plus d’informations, visitez le site http://www.oracle.com/
pls/topic/lookup?ctx=acc&id=info ou le site http://www.oracle.com/pls/topic/lookup?ctx=acc&id=trs si vous êtes malentendant.
Contents
Using This Documentation ................................................................................ 11
Product Documentation Library ....................................................................... 11
Feedback ...................................................................................................... 11
Understanding PDUs ......................................................................................... 13
Task Installation Overview (Standard PDU) ....................................................... 13
Task Installation Overview (Compact PDU) ....................................................... 13
PDU Overview ............................................................................................. 14
Confirming Facility Requirements and PDU Specifications .............................. 17
Confirming Facility Requirements .................................................................... 17
Facility Power Requirements ................................................................... 17
Circuit Breaker Capacity and Characteristics .............................................. 18
Grounding Requirements ........................................................................ 18
Confirming PDU Specifications ....................................................................... 19
Standard PDU Physical Specifications ....................................................... 19
Standard PDU Electrical Specifications ..................................................... 20
Standard PDU Input Leads and Outlet Groups on Single-Phase PDUs ............. 21
Standard PDU Input Leads and Outlet Groups on Three-Phase PDUs .............. 22
Compact PDU Physical Specifications ...................................................... 22
Compact PDU Electrical Specifications ..................................................... 22
Environmental Specifications ................................................................... 23
Preparing for Installation .................................................................................. 25
Safety Notices .............................................................................................. 25
ESD Precautions ........................................................................................... 27
Tools (Standard PDU) .................................................................................... 27
Tools (Compact PDU) .................................................................................... 27
▼ Attach an Antistatic Wrist Strap .................................................................. 28
▼ Attach a Grounding Strap .......................................................................... 29
5
Contents
▼ Install Equipment ..................................................................................... 29
Installing PDUs Into a Sun Rack II Cabinet ....................................................... 31
Installing Standard PDUs ................................................................................ 31
▼ Prepare to Install a Standard PDU ....................................................... 31
▼ Install a Standard PDU ...................................................................... 32
Installing Compact PDUs ................................................................................ 35
▼ Prepare to Install a Compact PDU ....................................................... 36
▼ Install a Compact PDU ..................................................................... 40
Compact PDU Installation Locations ........................................................ 44
Mounting Bracket Screw and Spring Nut Locations ..................................... 46
Connecting the PDU to the AC Power Source .................................................... 48
Circuit Breaker Overview ....................................................................... 49
Circuit Breaker Locations (Standard PDU) ................................................. 49
Circuit Breaker Locations (Compact PDU) ................................................ 50
▼ Connect the PDU to the AC Power Source ........................................... 50
▼ Connect Equipment Power Cords to PDUs ............................................ 51
▼ Power on the Equipment ........................................................................... 52
Connecting Standard PDUs to the Network ...................................................... 53
Connecting an Original PDU to a Network ........................................................ 54
▼ Connect an Original PDU to a DHCP Network ...................................... 54
▼ Prepare to Connect an Original PDU to a Static IP Address Network .......... 57
▼ Configure a Windows PC for a Point-to-Point Connection ........................ 58
▼ Configure an Oracle Solaris System for a Point-to-Point Connection .......... 62
▼ Connect an Original PDU to a Static IP Address Network ........................ 63
Crossover Cable Pinout Diagram .............................................................. 66
Connecting an Enhanced PDU to a Network ...................................................... 66
▼ Connect an Enhanced PDU to a DHCP Network .................................... 66
▼ Connect an Enhanced PDU to a Static IP Address Network Through a SER
MGT Port ............................................................................................ 68
▼ Connect an Enhanced PDU to a Static IP Address Network Through a
DHCP-Capable Network ......................................................................... 69
Login Information ......................................................................................... 71
Terminal Configuration Settings ....................................................................... 72
Monitoring Original PDUs ................................................................................. 73
Understanding the Relationship Between Modules and Outlet Groups ..................... 73
Relationship Between Modules and Outlet Groups Overview ......................... 74
6
Sun Rack II Power Distribution Units User's Guide • December 2016
Contents
Single-Phase PDU Module and Outlet Group Relationship ............................ 75
Three-Phase PDU Module and Outlet Group Relationship ............................. 77
▼ Access a Metering Unit on the Network (Original PDU) .................................. 78
▼ Set Threshold Parameter Levels (Original PDU) ............................................ 79
Monitoring an Original PDU ........................................................................... 81
▼ Monitor an Original PDU (LCD Screen) .............................................. 81
▼ Monitor an Original PDU (HTML Interface) ......................................... 83
Current and Voltage Measurement Colors .......................................................... 85
Changing Interface Settings (Original PDU) ....................................................... 86
▼ Set the PDU Name and Location (Original PDU) ................................... 86
▼ Add Users and Change Passwords (Original PDU) ................................. 87
▼ Send System Log Messages to Systems on the Network (Original PDU) ...... 88
Enabling and Configuring SNMP (Original PDU) ............................................... 91
Types of PDU Metering Unit SNMP Traps (Original PDU) ........................... 92
▼ Enable and Configure SNMP (Original PDU) ........................................ 92
▼ Specify NMS Hosts (Original PDU) .................................................... 95
Verifying and Updating the Firmware (Original PDU) .......................................... 96
▼ View Module Information (Original PDU) ............................................ 97
▼ Update the PDU Metering Unit Firmware (Original PDU) ....................... 98
Administering the PDU Metering Unit (Original PDU) ........................................ 99
▼ Reset the PDU Metering Unit (Original PDU) ....................................... 99
▼ View Status Information on the LCD Screen (Original PDU) .................. 100
▼ Adjust the LCD Screen (Original PDU) .............................................. 101
▼ Restore the PDU to Factory Default Settings (Original PDU) .......................... 102
NET MGT Port LED and Pin Descriptions ....................................................... 103
Monitoring Enhanced PDUs ............................................................................ 105
Understanding the Relationship Between Inputs and Outlet Groups ....................... 105
Relationship Between Inputs and Outlet Groups Overview .......................... 106
Single-Phase PDU Input and Outlet Group Relationship ............................. 107
Three-Phase PDU Input and Outlet Group Relationship .............................. 109
▼ Access a Metering Unit on the Network (Enhanced PDU) .............................. 110
▼ Set Threshold Parameter Values (Enhanced PDU) ......................................... 111
Monitoring an Enhanced PDU ....................................................................... 114
▼ Monitor the Enhanced PDU (LCD Screen) .......................................... 114
▼ Monitor the Enhanced PDU (HTML Interface) .................................... 115
▼ Monitor the Enhanced PDU (RS-232) ................................................ 118
▼ Monitor the Enhanced PDU (SSH) .................................................... 119
Changing Interface Settings (Enhanced PDU) ................................................... 119
7
Contents
▼ Set the PDU Information (Enhanced PDU) .......................................... 119
▼ Add Users and Change Passwords (Enhanced PDU) .............................. 120
▼ Send System Log Messages to Systems on the Network (Enhanced
PDU) ................................................................................................. 121
Enabling and Configuring SNMP (Enhanced PDU) ............................................ 124
Types of PDU Metering Unit SNMP Traps (Enhanced PDU) ....................... 124
▼ Enable and Configure SNMP (Enhanced PDU) .................................... 125
▼ Configure SNMP Traps ................................................................... 127
Verifying and Updating the Firmware (Enhanced PDU) ...................................... 129
▼ View Module Information (Enhanced PDU) ........................................ 129
▼ Update the PDU Metering Unit Firmware (HTML) ............................... 130
▼ Update the PDU Metering Unit Firmware (SSH) .................................. 131
Administering the PDU Metering Unit (Enhanced PDU) ..................................... 132
▼ Reset the Enhanced PDU Metering Unit (Reset Button) ......................... 133
▼ Reboot the Enhanced PDU Metering Unit (LCD) ................................. 133
▼ Reboot the Enhanced PDU Metering Unit (HTML) ............................... 133
▼ Reboot the Enhanced PDU Metering Unit (RS-232) .............................. 134
▼ Reboot the Enhanced PDU Metering Unit (SSH) .................................. 135
▼ View Status Information on the LCD Screen (Enhanced PDU) ................ 135
▼ Adjust the LCD Screen (Enhanced PDU) ............................................ 136
▼ Set the PDU System Time ....................................................................... 137
▼ Access the Event Logging Page ................................................................ 138
Restoring the PDU to Factory Default Settings (Enhanced PDU) .......................... 139
▼ Restore the PDU to Factory Default Settings (LCD) .............................. 140
▼ Restore the PDU to Factory Default Settings (HTML) ........................... 140
▼ Restore the PDU to Factory Default Settings (RS-232) .......................... 141
▼ Restore the PDU to Factory Default Settings (SSH) .............................. 141
NET MGT Port LED and Pin Descriptions ....................................................... 142
SER MGT Ports and Pin Descriptions ............................................................. 142
Understanding CLI Commands ....................................................................... 145
Help Commands .......................................................................................... 145
Understanding User and Administrator Commands ............................................ 146
User and Administrator Commands ......................................................... 146
PDU System Information Parameters (get Command) ................................. 147
Power Information Parameters ............................................................... 147
Input Parameters .................................................................................. 148
Line Parameters ................................................................................... 149
Understanding Administrator-Only Commands ................................................. 150
8
Sun Rack II Power Distribution Units User's Guide • December 2016
Contents
Administrator-Only Commands .............................................................. 150
PDU System Information Parameters (set Command) ................................. 151
Network Services Configuration Parameters ............................................. 151
Network Ports Configuration Parameters .................................................. 154
IPv4 Configuration Parameters ............................................................... 154
IPv6 Configuration Parameters ............................................................... 155
PDU Events List Parameters .................................................................. 155
Host Configuration Parameters ............................................................... 156
User Configuration Parameters ............................................................... 158
System Time Configuration Parameters ................................................... 159
Servicing PDUs ................................................................................................ 163
▼ Disconnect the Main Input Power Cords From the Power Source ..................... 163
▼ Remove a Standard PDU ......................................................................... 164
▼ Remove a Compact PDU ......................................................................... 166
Glossary .......................................................................................................... 171
Index ................................................................................................................ 173
9
10
Sun Rack II Power Distribution Units User's Guide • December 2016
Using This Documentation
■
■
■
Overview – Provides specifications and describes how to install, administer, and service the
power distribution units designed for Oracle's Sun Rack II family of rack cabinets.
Audience – Technicians, system administrators, and authorized service providers.
Required knowledge – Professional installers, authorized service providers (ASPs), and
users who have been instructed on the hazards within the equipment and have experience
installing and cabling equipment into rack cabinets.
Product Documentation Library
Documentation and resources for this product and related products are available at http://www.
oracle.com/goto/sunrackii/docs.
Feedback
Provide feedback about this documentation at http://www.oracle.com/goto/docfeedback.
Using This Documentation
11
12
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding PDUs
These topics describe various PDUs and the tasks required to install them.
■
■
■
“Task Installation Overview (Standard PDU)” on page 13
“Task Installation Overview (Compact PDU)” on page 13
“PDU Overview” on page 14
Task Installation Overview (Standard PDU)
Step
Description
Links
1.
Familiarize yourself with the standard PDU.
“PDU Overview” on page 14
2.
Review the PDU site requirements and
specifications.
“Confirming Facility Requirements and PDU
Specifications” on page 17
3.
Take safety and ESD precautions and gather the
required tools.
“Safety Notices” on page 25
4.
Install a PDU into the rack.
“Prepare to Install a Standard PDU” on page 31
5.
Connect the PDU to the AC power source.
“Connect the PDU to the AC Power
Source” on page 50
6.
Reset circuit breakers.
“Circuit Breaker Locations (Standard
PDU)” on page 49
7.
Connect equipment power cords to PDU.
“Connect Equipment Power Cords to
PDUs” on page 51
8.
Power on the equipment.
“Power on the Equipment” on page 52
“Tools (Standard PDU)” on page 27
Task Installation Overview (Compact PDU)
Step
Description
Links
1.
Familiarize yourself with the compact PDU.
“PDU Overview” on page 14
Understanding PDUs
13
PDU Overview
Step
Description
Links
2.
Review the PDU site requirements and
specifications.
“Confirming Facility Requirements and PDU
Specifications” on page 17
3.
Take safety and ESD precautions and gather the
required tools.
“Safety Notices” on page 25
4.
Install a PDU into the rack.
“Installing Compact PDUs” on page 35
5.
Connect the PDU to the AC power source.
“Connect the PDU to the AC Power
Source” on page 50
6.
Reset circuit breakers.
“Circuit Breaker Locations (Compact
PDU)” on page 50
7.
Connect equipment power cords to PDU.
“Connect Equipment Power Cords to
PDUs” on page 51
8.
Power on the equipment.
“Power on the Equipment” on page 52
“Tools (Compact PDU)” on page 27
PDU Overview
There are three types of PDUs available for the Sun Rack II cabinets: original PDUs and
enhanced PDUs, which are standard PDUs, and compact PDUs. You can install up to two
standard PDUs in one Sun Rack II cabinet, and you can install up to six of the much smaller
compact PDUs into one Sun Rack II cabinet.
The original PDU metering unit allows you two ways to monitor the current being used by
equipment connected to a standard PDU. You can monitor the current in person by viewing the
LCD screen on the PDU itself or the Current Measurement page using HTML interface.
For enhanced PDUs, there are four ways you can monitor how much power, energy and current
the equipment attached to the PDU uses, as well as the voltage level powering the equipment,
the PDU's LCD screen, the Monitoring Overview page using HTML interface, the RS-232
interface, or the SSH interface.
14
Sun Rack II Power Distribution Units User's Guide • December 2016
PDU Overview
FIGURE 1
Standard PDU and Compact PDU Compared
The are two types of standard PDUs, based on geography.
TABLE 1
PDUs Types
PDU
Phase Type
Compact
Low-voltage, single-phase
Geography
High-voltage, three-phase
Original PDU/
Low-voltage, single-phase
N & S America, Japan, & Taiwan
Enhanced PDU
Low-voltage, three-phase
N & S America, Japan, & Taiwan
High-voltage, single-phase
EMEA & APAC
High-voltage, three-phase
EMEA & APAC
Understanding PDUs
15
16
Sun Rack II Power Distribution Units User's Guide • December 2016
Confirming Facility Requirements and PDU
Specifications
These PDUs are designed exclusively for the Sun Rack II family of rack cabinets. Before
installing PDUs, review the facility requirements and PDU specifications.
Note - The three-phase standard PDUs (both the high-voltage and low-voltage versions) are not
supported in the Sun Rack II 1042. If your equipment requires a three-phase PDU, use the Sun
Rack II 1242 instead.
■
■
“Confirming Facility Requirements” on page 17
“Confirming PDU Specifications” on page 19
Confirming Facility Requirements
Review the power, circuit breaker, and grounding requirements of your facility, and review all
safety notices, prior to installing and cabling the PDU.
■
■
■
“Facility Power Requirements” on page 17
“Circuit Breaker Capacity and Characteristics” on page 18
“Grounding Requirements” on page 18
Facility Power Requirements
To prevent catastrophic failures, design your input power sources to ensure that adequate power
is provided to the PDUs. Use dedicated AC breaker panels for all power circuits that supply
power to the PDU.
Oracle PDUs are designed to measure the incoming line to neutral voltage. There are many
power system types which, when connected to the PDU, will ensure that the PDU outlet groups
provide the required output voltage. However, the PDUs cannot accurately measure the voltage
when connected to certain power system types. Oracle PDUs measure the correct voltage
when connected to a wye TN power system. Using any other power system type might lead to
incorrect voltage measurements.
Confirming Facility Requirements and PDU Specifications
17
Confirming Facility Requirements
Oracle PDUs are designed to be used with either a TN power system or a TT power system.
For TN power systems, the PDUs must be provided with protective earthing (grounding) from
the installation facility through the earth conductor of the PDU power cord. Additional earthing
(grounding) is recommended to ensure continued safe operation of your racked product. Refer
to “Attaching a Grounding Cable” in Sun Rack II User’s Guide for instructions.
Note - For TT power systems, the power source has no earth connection and so the earth
connection must be made through the rack. Refer to “Attaching a Grounding Cable” in Sun
Rack II User’s Guide for instructions.
Note - All Oracle PDUs are suitable for connection to TN and TT power systems. All PDUs
with a maximum of a 240V phase-to-phase rating, fuses in each line, and neutral conductors
are suitable for IT power systems that supply a maximum of 240V phase-to-phase. If you are
installing an Oracle Engineered System, refer to its documentation to determine if the system is
suitable for connection to IT power systems.
While the PDU power cords are 4m (13.12 ft.) long, 1 to 1.5m (3.3 to 4.9 ft.) of the cords will
be routed within the rack cabinet. The installation site's AC power receptacle must be within 2m
(6.6 ft.) of the rack.
Electrical work and installations must comply with applicable local, state, or national electrical
codes. Contact your facilities manager or a qualified electrician to determine what type of
power is supplied to your building.
When planning for power distribution requirements for installed rack equipment:
■
■
Balance the power load between available AC supply branch circuits.
In the United States and Canada, ensure that the overall system AC input current load does
not exceed 80% of the branch circuit AC current rating.
Circuit Breaker Capacity and Characteristics
Each Sun Rack II requires its own customer-supplied circuit breaker and AC receptacle for
each power input cord. Provide a stable power source, such as an uninterruptible power system
(UPS), to reduce the possibility of component failures. If the computer equipment is subjected
to repeated power interruptions and fluctuations, it is susceptible to a higher component failure
rate than it would be with a stable power source.
Grounding Requirements
For TN power systems, always connect the PDU input power cords into grounded power
outlets. For TT power systems, always attach a grounding cable to the rack frame. Refer to
“Attaching a Grounding Cable” in Sun Rack II User’s Guide for further information.
18
Sun Rack II Power Distribution Units User's Guide • December 2016
Confirming PDU Specifications
Caution - To reduce the risk of electric shock or damage to installed equipment, never disable
the grounding plug on any power cord or receptacle.
Confirming PDU Specifications
These topics describe the PDU specifications.
Description
Links
Review specifications for standard PDUs.
“PDU Overview” on page 14
“Standard PDU Physical Specifications” on page 19
“Standard PDU Electrical Specifications” on page 20
“Standard PDU Input Leads and Outlet Groups on Single-Phase
PDUs” on page 21
“Standard PDU Input Leads and Outlet Groups on Three-Phase
PDUs” on page 22
“Environmental Specifications” on page 23
Review specifications for compact PDUs.
“PDU Overview” on page 14
“Compact PDU Physical Specifications” on page 22
“Compact PDU Electrical Specifications” on page 22
“Environmental Specifications” on page 23
Standard PDU Physical Specifications
TABLE 2
Standard PDU Physical Specifications
Dimension
Measurement
Length
1674 mm / 65.91 in.
Depth
47 mm / 1.85 in.
Width
134 mm / 5.28 in.
Power input lead cord nominal length
4 m / 13.12 ft.
Weight (including cords)
Low-voltage PDUs for North and South America, Japan, and Taiwan:
■ 5 kVA, single phase
13.25 kg / 29.21 lbs
■ 10 kVA, single phase
15.00 kg / 33.07 lbs
■ 15 kVA, single phase
16.75 kg / 36.93 lbs
Confirming Facility Requirements and PDU Specifications
19
Confirming PDU Specifications
Dimension
Measurement
■ 15 kVA, three phase
13.60 kg / 29.98 lbs
■ 24 kVA, three phase
15.70 kg / 34.61 lbs
■ 37 kVA, three phase
17.80 kg / 39.24 lbs
High-voltage PDUs for EMEA and APAC:
■ 5 kVA, single phase
13.10 kg / 28.88 lbs
■ 10 kVA, single phase
14.70 kg / 32.41 lbs
■ 15 kVA, single phase
16.30 kg / 35.94 lbs
■ 15 kVA, three phase
16.10 kg / 35.49 lbs
■ 22 kVA, single phase
16.30 kg / 35.94 lbs
■ 24 kVA, three phase
20.60 kg / 45.42 lbs
■ 37 kVA, three phase
25.15 kg / 55.45 lbs
Note - 1 to 1.5 m (3.3 to 4.9 ft.) of the cords will be routed within the rack cabinet, so the site's
AC power receptacle must be within 2m (6.6 ft.) of the rack.
Standard PDU Electrical Specifications
The following tables describe the PDU electrical specifications, including the number and type
of connectors and receptacles.
TABLE 3
Specifications for North and South America, Japan, and Taiwan Low-Voltage PDUs
Specification
5 kVA
10 kVA
15 kVA, 1ph
15 kVA, 3ph
24 kVA
37 kVA
Number of
Inputs
1 x 30A 1ph
2 x 30A 1ph
3 x 30A 1ph
1 x 60A 3ph
2 x 60A 3ph
3 x 60A 3ph
Voltage
200 - 240 VAC
200 - 240 VAC
200 - 240 VAC
200 - 208 VAC
3ph
200 - 208 VAC
3ph
200 - 208 VAC
3ph
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Current
24A max.
24A max. per
input
24A max. per
input
40A max. per
phase
34.6A max. per
phase
34.6A max. per
phase
Power Rating
5 kVA
10 kVA
15 kVA
14.4 kVA
25.0 kVA
37.5 kVA
Output Current
24A
48A (2 x 24A)
72A (3 x 24A)
69A (3 x 23A)
120A (6 x 20A)
180A (9 x 20A)
Outlets
42 x C13 6 x C19
42 x C13 6 x
C19
42 x C13 6 x
C19
42 x C13 6 x C19
42 x C13 6 x C19
45 x C13 9 x C19
Outlet Groups
6
6
6
6
6
9
Group
Protection†
20A
20A
20A
20A
20A
20A
Data Center
Receptacle
NEMA L6-30
NEMA L6-30
NEMA L6-30
IEC309 60A 4
PIN 250VAC 3ph
IP67
IEC309 60A 4
PIN 250VAC 3ph
IP67
IEC309 60A 4
PIN 250VAC 3ph
IP67
†
UL489 2-pole circuit breaker.
20
Sun Rack II Power Distribution Units User's Guide • December 2016
Confirming PDU Specifications
TABLE 4
Specifications for EMEA and APAC High-Voltage PDUs
Specification
5 kVA
10 kVA
15 kVA, 1ph
15 kVA, 3ph
22 kVA
24 kVA
37 kVA
Number of
Inputs
1 x 25A 1ph
2 x 25A 1ph
3 x 25A 1ph
1 x 25A 3ph
3x32A 1ph
2 x 25A 3ph
3 x 25A 3ph
Voltage
220 - 240 VAC
220 - 240V
AC
220 - 240 VAC
220/380 –
240/415 VAC
3ph
220 - 240 VAC
220/380 –
240/415 VAC
3ph
220/380 –
240/415 VAC
3ph
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Current
25A max.
25A max. per
input
25A max. per
input
25A max. per
phase
32A max per
input
18A max. per
phase
18A max. per
phase
Power Rating
5 kVA
10 kVA
15 kVA
14.4 kVA
22 kVA
25.0 kVA
37.5 kVA
Output
Current
24A
48A (2 x 24A)
72A (3 x 24A)
62.7A (3 x
20.9A)
96A
109A (6 x 18.1
A)
163A (9 x 18.1
A)
Outlets
42 x C13 6 x
C19
42 x C13 6 x
C19
42 x C13 6 x
C19
42 x C13 6 x
C19
42 x C13 6 x
C19
42 x C13 6 x
C19
45 x C13 9 x
C19
Outlet Groups
6
6
6
6
6
6
9
Group
Protection†
20A
20A
20A
20A
20A
20A
20A
Data Center
Receptacle
IEC309 32A 3
PIN 250 VAC
IP44
IEC309 32A 3
PIN 250 VAC
IP44
IEC309 32A 3
PIN 250 VAC
IP44
IEC309 32A 5
PIN 230/400V
3ph IP44
IEC309 32A 3
PIN 250 VAC
IP44
IEC309 32A 5
PIN 230/400V
3ph IP44
IEC309 32A 5
PIN 230/400V
3ph IP44
(3x32A)
†
UL489 1-pole circuit breaker.
Standard PDU Input Leads and Outlet Groups on
Single-Phase PDUs
This table lists the input leads and outlet groups for both original PDUs and enhanced PDUs.
TABLE 5
Relationship Between Input Lead and Powered Outlet Groups on Single-Phase PDUs
†
PDU Type
Input Lead
Outlet Groups
5 kVA
0
0, 1, 2, 3, 4, 5
10 kVA
0
0, 1, 2
1
3, 4, 5
0
0, 1
1
2, 3
2
4, 5
15 kVA, 22 kVA
†
If no power is applied to an input lead, the corresponding outlet groups will not provide power and the capacity of the PDU will be reduced.
Confirming Facility Requirements and PDU Specifications
21
Confirming PDU Specifications
Standard PDU Input Leads and Outlet Groups on
Three-Phase PDUs
This table lists the input leads and outlet groups for both original PDUs and enhanced PDUs.
TABLE 6
Relationship Between Input Lead and Powered Outlet Groups on Three-Phase PDUs
†
PDU Type
Input Lead
Outlet Groups
15 kVA
0
0, 1, 2, 3, 4, 5
24 kVA
0
0, 1, 2
1
3, 4, 5
0
0, 1, 2
1
3, 4, 5
2
6, 7, 8
37 kVA
†
If no power is applied to an input lead, the corresponding outlet groups will not provide power and the capacity of the PDU will be reduced.
Compact PDU Physical Specifications
The following table list the physical dimensions for both types of compact PDUs.
TABLE 7
Compact PDU Physical Dimensions
Dimension
5 kVA Low-Voltage PDU
5 kVA High-Voltage PDU
Length
430 mm / 16.93 in.
430 mm / 16.93 in.
Depth
47 mm / 1.85 in.
47 mm / 1.85 in.
Width
134 mm / 5.28 in.
134 mm / 5.28 in.
Power input lead cord nominal
length
4 m / 13.12 ft.
4 m / 13.12 ft.
Weight (including cords)
5.0 kg / 11.0 lbs
5.0 kg / 11.0 lbs
Note - 1 to 1.5m (3.3 to 4.9 ft.) of the cords will be routed within the rack cabinet, so the site's
AC power receptacle must be within 2m (6.6 ft.) of the rack.
Compact PDU Electrical Specifications
The following table list the power specifications for both types of compact PDUs, 5 kVA singlephase low-voltage PDU and 5 kVA single-phase high-voltage PDU.
22
Sun Rack II Power Distribution Units User's Guide • December 2016
Confirming PDU Specifications
TABLE 8
Compact PDU Power Specifications
Specification
5 kVA Low-Voltage PDU
5 kVA High-Voltage PDU
Number of Inputs
1 x 30A 1ph
1 x 25 A 1ph
Voltage
200 - 240 VAC
220 - 240V AC
Frequency
50/60 Hz
50/60 Hz
Current
24A max.
25A max.
Power Rating
5 kVA
5 kVA
Output Current
24A
24A
Outlets
12 x C13, 2 x C19
12 x C13, 2 x C19
Outlet Groups
2
2
Group Protection†
20A
20A
Data Center Receptacle
NEMA L6-30
IEC309 32A 3 PIN 250 VAC IP44
†
UL489 1-pole circuit breaker.
Environmental Specifications
Standard and compact PDU share the same environmental specifications.
TABLE 9
Environmental Specifications
Specification
Definition or Range
Protection class
I
Protection type
IP 20
Overvoltage category
II
Contamination level
2
Operating temperature range
0° C / 32° F to 40° C / 104° F
Relative humidity
10% to 90%, noncondensing
Maximum altitude
3000m / 9842.52 ft above sea level
Confirming Facility Requirements and PDU Specifications
23
24
Sun Rack II Power Distribution Units User's Guide • December 2016
Preparing for Installation
These PDUs are designed exclusively for the Sun Rack II family of rack cabinets. Install the
PDUs into the Sun Rack II cabinets before installing other equipment. Refer to the Sun Rack II
User's Guide for information about installing equipment into the cabinets.
Note - The three-phase standard PDUs (both the high-voltage and low-voltage versions) are not
supported in the Sun Rack II 1042. If your equipment requires a three-phase PDU, use the Sun
Rack II 1242 instead.
■
■
■
■
■
■
“Safety Notices” on page 25
“Tools (Standard PDU)” on page 27
“Tools (Compact PDU)” on page 27
“Attach an Antistatic Wrist Strap” on page 28
“Attach a Grounding Strap” on page 29
“Install Equipment” on page 29
Safety Notices
Before installing the PDU into the rack, observe the following safety and usage notices.
Caution - PDU installation and configuration must be done by qualified personnel with
experience installing similar hardware.
Caution - Before installing and using the PDU, check it for any external damage. If the PDU is
damaged, do not install or operate the PDU and contact your service representative.
Caution - The PDU, and any electrical equipment connected to it, can be damaged by power
load ratings above the values listed in “Standard PDU Electrical Specifications” on page 20.
Caution - Do not use the PDU in damp rooms. If a liquid spills on the PDU, or if the PDU
becomes damp from condensation, immediately disconnect the power input lead connector from
the AC power supply. Contact your service representative before using the PDU again. You
might need to return it for inspection.
Preparing for Installation
25
Safety Notices
Caution - Choose the maximum permitted fuse/circuit breaker load in the building according to
the values listed in “Standard PDU Electrical Specifications” on page 20. Observe all national
and local regulations, safety provisions, and fuse load variations.
Caution - Never bend, or rest any object on, a PDU's power input lead.
Caution - Ensure that the total power consumed by all of the connected equipment does not
exceed the respective nominal power rating of the PDU.
Caution - Always provide an easily accessible safety disconnect for units with fixed
connections.
Caution - When connecting equipment to the PDU, ensure that you install the most
symmetrical load to all of the phases as possible.
Caution - Elevated Operating Ambient – If equipment installed in a closed or multi-unit rack
assembly, the operating ambient temperature of the rack environment might be greater than the
room ambient. Therefore, consider installing the equipment in an environment compatible with
the maximum ambient temperature (Tma) specified by the manufacturer.
Caution - Reduced Air Flow – Install equipment in the rack in a way that does not compromise
the amount of air flow required for the safe operation of the equipment.
Caution - Mechanical Loading – Mount equipment in the rack to prevent a hazardous condition
due to uneven mechanical loading.
Caution - Circuit Overloading – When connecting equipment to the PDU, consider the
damaging effect that overloading the circuits might have on overcurrent protection and supply
wiring. Always review the equipment nameplate ratings when considering circuit overloading
issues.
Caution - Reliable Earthing – Always maintain the reliable earthing of rackmounted equipment.
Give particular attention to supply connections other than the direct connections to the branch
circuit (for example, when using power strips).
26
Sun Rack II Power Distribution Units User's Guide • December 2016
ESD Precautions
ESD Precautions
Electronic equipment is susceptible to damage by static electricity. Use a grounded antistatic
wriststrap, footstrap, or equivalent safety equipment to prevent electrostatic damage when you
install or service the server.
Caution - To protect electronic components from electrostatic damage, which can permanently
disable the server or require repair by service technicians, place components on an antistatic
surface, such as an antistatic discharge mat, an antistatic bag, or a disposable antistatic mat.
Wear an antistatic grounding strap connected to a metal surface on the chassis when you work
on server components.
Tools (Standard PDU)
Prior to installing a standard PDU into your rack, prepare the work area and assemble the
following tools:
■
■
■
■
■
T-25 Torx wrench key (included in the Sun Rack II shipping kit)
T-30 Torx wrench key (included in the Sun Rack II shipping kit)
PDU mounting brackets and M6 screws (included in the PDU shipping kit)
Cable routing support brackets and M6 screws (included in the PDU shipping kit)
M5 shipping screws and washers (included in the PDU shipping kit)
You also must supply:
■
■
■
Antistatic wrist strap
Tie wraps
Clean work table, or area, near the rack
Caution - Because of the their size and weight, you will need another person to help lift and
install the PDU into the rack (see “Standard PDU Physical Specifications” on page 19 to review
the size and weights of each PDU). You might also need additional help when routing the PDU
power input cables.
Tools (Compact PDU)
Prior to installing compact PDUs into your rack, prepare the work area and assemble the
following tools:
Preparing for Installation
27
Attach an Antistatic Wrist Strap
■
T-25 Torx wrench key (included in the Sun Rack II shipping kit)
PDU mounting brackets (included in the PDU shipping kit)
Spring nuts, M5 screws, and washers (included in the PDU shipping kit)
Grounding strap connector (included in the PDU shipping kit)
■
Rack template (included in the PDU shipping kit)
■
■
■
You also must supply:
■
■
■
■
Antistatic wrist strap
Tape measure
Pencil
Clean work table, or area, near the rack
Attach an Antistatic Wrist Strap
Attach a wrist strap to your wrist and to the ESD grounding jack on the rear rail
of the rack.
28
Sun Rack II Power Distribution Units User's Guide • December 2016
Attach a Grounding Strap
Attach a Grounding Strap
Attach a grounding strap from the rack to the top of the PDU.
Install Equipment
Install all hardware you want in the rack.
Refer to the installation guide for each type of hardware.
Preparing for Installation
29
30
Sun Rack II Power Distribution Units User's Guide • December 2016
Installing PDUs Into a Sun Rack II Cabinet
Always install the PDUs prior to installing equipment into the rack. Complete these tasks to
install the PDU and connect it to the installation site's AC power source.
■
■
■
■
“Installing Standard PDUs” on page 31
“Installing Compact PDUs” on page 35
“Connect the PDU to the AC Power Source” on page 50
“Power on the Equipment” on page 52
Installing Standard PDUs
These topics describe how to install standard PDUs.
■
■
“Prepare to Install a Standard PDU” on page 31
“Install a Standard PDU” on page 32
Prepare to Install a Standard PDU
1.
Unpack the PDU from its packaging and place it on a clean work table.
Included with the PDU are two PDU mounting brackets, a cable routing bracket, screws, and
washers.
2.
Open the rear door of the rack and determine where to install the PDU.
You can install up to two PDUs, one per side, into the Sun Rack II cabinet. You can install these
PDUs anywhere between the rear RETMA rail and the rack's rear frame. Provide adequate
space to route the power input lead cords and any equipment data cables.
3.
Attach an antistatic strap to your wrist and to a 10 mm ESD grounding snap on
the rack.
See “Attach an Antistatic Wrist Strap” on page 28 and “Attach a Grounding Strap” on page 29.
4.
Using a T-30 Torx wrench key, secure the top and bottom PDU mounting
brackets to the top rack frame using two M6 screws per bracket.
Installing PDUs Into a Sun Rack II Cabinet
31
Install a Standard PDU
See the following figure, panels 1 and 2.
Each mounting bracket contains two additional screw holes used to secure a PDU to the bracket
when a PDU ships in a rack from the factory. Ignore these shipping screw holes when installing
the PDU into the rack.
5.
Install a standard PDU into the rack.
See “Install a Standard PDU” on page 32.
Install a Standard PDU
1.
32
Lift up the PDU, and ensuring that the circuit breakers are facing the rear of the
rack, carefully set the PDU's standoff bolts into the top and bottom bracket's
keyhole slots.
Sun Rack II Power Distribution Units User's Guide • December 2016
Install a Standard PDU
See the figure in “Prepare to Install a Standard PDU” on page 31, panels 3 and 4).
Caution - You need two people to lift and secure the PDU to the rack.
The PDU is held in the rack by gravity, with the standoff bolts resting in the mounting brackets'
keyhole slots.
Note - The circuit breakers must face the rear of the rack so that you can reset a breaker if one
trips.
2.
(Optional) Use a T-25 Torx wrench and four M5 shipping screws and washers to
secure the PDU to the mounting brackets.
For extra durability, secure the PDU to the mounting brackets using the shipping screws and
washers (two screws and washers per bracket). If you plan to ship the rack to another location,
you must secure the PDU using these shipping screws.
3.
Route the power input lead cords between the rear RETMA rail and side panel.
A PDU has one to three power input lead cords, which you must route between the side panel
and the rear RETMA rail.
Installing PDUs Into a Sun Rack II Cabinet
33
Install a Standard PDU
Route the power input lead cords either down through the bottom of the rack or up through the
top of the rack, depending on where you plan to connect them to the main power source.
If you are routing the cables through the bottom of the rack, refer to the Sun Rack II User's
Guide for the dimensions of the floor cutout.
Caution - Never twist, kink, or tightly bend a power input lead.
Routing standard PDU cables up through the top of the rack.
34
Sun Rack II Power Distribution Units User's Guide • December 2016
Installing Compact PDUs
Routing standard PDU cables through the bottom of the rack.
Caution - If you route power input lead cords through the top cable window, do not rest the
cables on the plastic sliding doors.
4.
Use a T-30 Torx wrench to secure cable routing brackets to the rack frame using
two M6 screws per bracket.
Install these brackets near where the power input leads exit the rack (see the figures in Step 3).
5.
Using tie-wraps, secure the PDU input lead cables to the cable routing brackets.
6.
Determine your next steps.
■
■
■
If you are installing a second PDU into the rack, follow Step 1 through Step 5 to install the
second PDU.
If you are installing a compact PDU, go to “Install a Compact PDU” on page 40.
If you are done installing PDUs and want to power on the rack, go to “Connect the PDU to
the AC Power Source” on page 50.
Installing Compact PDUs
These topics describe how to install compact PDUs.
Installing PDUs Into a Sun Rack II Cabinet
35
Prepare to Install a Compact PDU
■
■
■
■
“Prepare to Install a Compact PDU” on page 36
“Install a Compact PDU” on page 40
“Compact PDU Installation Locations” on page 44
“Mounting Bracket Screw and Spring Nut Locations” on page 46
Prepare to Install a Compact PDU
1.
Determine where to install the PDU and the spring nuts for the mounting
brackets.
See:
■
■
2.
“Compact PDU Installation Locations” on page 44
“Mounting Bracket Screw and Spring Nut Locations” on page 46
Unpack the PDU from its packaging and place it on a clean work table.
Included with the PDU are two PDU mounting brackets, spring nuts, screws, and washers.
3.
Open the rear door of the rack and determine where to install the PDU.
Install compact PDUs from the bottom of the rack up. For more information, see “Compact
PDU Installation Locations” on page 44.
4.
Attach an antistatic strap to your wrist and to a 10 mm ESD grounding snap on
the rack.
See “Attach an Antistatic Wrist Strap” on page 28 and “Attach a Grounding Strap” on page 29.
5.
36
Use the rack template to locate where you will install the spring nuts in the rear
rack frame channel.
Sun Rack II Power Distribution Units User's Guide • December 2016
Prepare to Install a Compact PDU
Hold the rack template up to the rear rack frame and mark where to install the spring nuts
(labeled “Bracket Assembly Point” on the rack template).
6.
Insert three spring nuts into the rear rack frame channel.
Installing PDUs Into a Sun Rack II Cabinet
37
Prepare to Install a Compact PDU
Insert the spring nuts in the frame channel at a 45-degree angle. You use these spring nuts to
secure the mounting brackets to the rack frame.
7.
Move the spring nuts up or down the rack frame to the previously marked
locations.
Use the rack template or the illustration in Step 5 to determine the specific spring nut locations.
38
Sun Rack II Power Distribution Units User's Guide • December 2016
Prepare to Install a Compact PDU
8.
Using a T-25 Torx wrench key, secure the side mounting bracket to the rack by
tightening two M5 screws with washers into the spring nuts.
9.
Using a T-25 Torx wrench key, secure the top mounting bracket to the PDU using
two screws and two washers.
Installing PDUs Into a Sun Rack II Cabinet
39
Install a Compact PDU
Ensure that the upturned side of the bracket faces the side of the PDU that contains the circuit
breakers and standoff bolts.
10.
Install a compact PDU into the rack.
See “Install a Compact PDU” on page 40.
Install a Compact PDU
1.
40
Insert the PDU's standoff bolts into the side mounting bracket's keyhole slots.
Sun Rack II Power Distribution Units User's Guide • December 2016
Install a Compact PDU
Press down on the top of the PDU to ensure that the PDU rests securely in the side mounting
bracket.
2.
Using a T-25 Torx wrench key, secure the top mounting bracket to the rack by
tightening an M5 screw with a washer to the spring nut you installed in “Prepare
to Install a Compact PDU” on page 36.
3.
Using a T-25 Torx wrench key, secure the grounding strap to the PDU with a
screw and a washer.
4.
Insert a spring nut into the rack frame channel parallel to the PDU, approximately
in the middle of the PDU.
Installing PDUs Into a Sun Rack II Cabinet
41
Install a Compact PDU
5.
Using a T-25 Torx wrench key, secure the grounding strap connector to the
spring nut with a screw and a washer.
6.
Connect the loose end of the PDU grounding strap to the connector you installed
in the rack frame.
7.
Route the power input lead cords between the rear RETMA rail and the side
panel.
A PDU has one power input lead cord, which you must route between the side panel and the
rear RETMA rail.
Route the power input lead cord either down through the bottom of the rack, or up through the
top of the rack, depending on where you plan to connect them to the main power source.
If you are routing the cables through the bottom of the rack, refer to the Sun Rack II User's
Guide for the dimensions of the floor cutout.
Caution -Never twist, kink, or tightly bend a power input lead.
42
Sun Rack II Power Distribution Units User's Guide • December 2016
Install a Compact PDU
Routing Compact PDU cables through the bottom of the rack.
Installing PDUs Into a Sun Rack II Cabinet
43
Install a Compact PDU
Routing Compact PDU cables Up through the top of the rack.
Compact PDU Installation Locations
You can install up to six compact PDUs, three per side, in a Sun Rack II cabinet.
Secure the compact PDU to the rack frame using the two mounting brackets that shipped with
the PDU. While these mounting brackets permit you to install the PDU anywhere on the rear
44
Sun Rack II Power Distribution Units User's Guide • December 2016
Install a Compact PDU
rack frame, install new compact PDUs from the bottom of the rack up. The following figure and
table display the compact PDU installation locations and spacing on the rear rack rail.
Note - Once installed, it is challenging to reposition a compact PDU in the rack. If you are
installing only one compact PDU, install it at the bottom of the rack to leave room for additional
compact PDUs.
TABLE 10
Compact PDU Locations on the Rear Rack Frame
PDU
Dimension
Measurement From Bottom of Rack Frame
3
Top of third PDU top mounting bracket
1775 mm / 69.88 in.
Bottom of third PDU
1220 mm / 48.03 in.
Top of second PDU top mounting bracket
1210 mm / 47.64 in.
Bottom of second PDU
655 mm / 25.79 in.
Top of first PDU top mounting bracket
645 mm / 25.39 in.
Bottom of first PDU
90 mm / 3.54 in.
2
1
Installing PDUs Into a Sun Rack II Cabinet
45
Install a Compact PDU
Mounting Bracket Screw and Spring Nut
Locations
Two mounting brackets secure the compact PDU to the rear rack frame. These two mounting
brackets are secured to the rack frame using three screws and spring nuts.
The compact PDU ships with a rack template that is the height and depth of the compact
PDU with an installed top mounting bracket. When installing the compact PDU, use this
rack template to determine where to install the spring nuts in the rack frame as shown in the
following figure.
46
Sun Rack II Power Distribution Units User's Guide • December 2016
Install a Compact PDU
Note - Use this template to determine where to install the spring nuts. Do not install the rack
template between the brackets and the rack frame.
If you lost or recycled the rack template, see the following figure for the locations of these
mounting bracket screws and spring nuts in relation to an installed compact PDU.
Installing PDUs Into a Sun Rack II Cabinet
47
Connecting the PDU to the AC Power Source
FIGURE 2
Compact PDU Mounting Bracket Screw Locations
Figure Legend
1
2
3
4
5
15 mm / 0.59 in.
540 mm / 21.26 in.
110.5 mm / 4.35 in.
310 mm / 12.20 in.
127.5 mm / 5.02 in.
Connecting the PDU to the AC Power Source
Before connecting the PDU to the AC power source, determine your type of PDU for the
locations of the circuit breakers.
■
■
48
“Circuit Breaker Overview” on page 49
“Circuit Breaker Locations (Standard PDU)” on page 49
Sun Rack II Power Distribution Units User's Guide • December 2016
Connecting the PDU to the AC Power Source
■
■
■
“Circuit Breaker Locations (Compact PDU)” on page 50
“Connect the PDU to the AC Power Source” on page 50
“Connect Equipment Power Cords to PDUs” on page 51
Circuit Breaker Overview
Each PDU contains a circuit breaker for each outlet group. These circuit breakers are safety
devices to protect equipment from damage and you from personal injury. A circuit breaker trips
and shuts the power off to an outlet group when it detects an overloaded circuit, a short circuit,
or another fault condition.
When operating normally in the On (|) position, the circuit breakers are flush with the side of
the PDU. When tripped to the Off (0) position, the circuit breakers extend beyond the side of
the PDU.
Caution - To prevent injury and equipment damage, always determine the cause of a tripped
circuit breaker before resetting it.
Circuit Breaker Locations (Standard PDU)
Installing PDUs Into a Sun Rack II Cabinet
49
Connect the PDU to the AC Power Source
Circuit Breaker Locations (Compact PDU)
Connect the PDU to the AC Power Source
Caution - Before connecting the input lead cords to the AC power source, make sure that all of
the PDU circuit breakers are at the Off position.
1.
Switch off every PDU circuit breaker.
Press down on every Off circuit breaker toggle switch to switch off the PDU.
See either “Circuit Breaker Locations (Standard PDU)” on page 49 or “Circuit Breaker
Locations (Compact PDU)” on page 50.
2.
Locate the PDU input lead cord connectors.
Depending on how you routed the cords when you installed the PDUs, route these cords either
out the bottom of the rack or out the top.
3.
50
Connect the PDU power lead cords to the facility AC power source.
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect Equipment Power Cords to PDUs
If your rack contains two PDUs, connect each PDU to different AC power source circuits in the
building whenever possible. You can also make a PDU with multiple AC inputs into a pseudoredundant PDU by connecting each power input lead into a different building circuit.
4.
Switch on every PDU circuit breaker to power on the PDU.
See “Circuit Breaker Locations (Standard PDU)” on page 49 or “Circuit Breaker Locations
(Compact PDU)” on page 50.
Connect Equipment Power Cords to PDUs
After installing equipment into the rack, connect the power cords to the PDUs.
Note - Refer to the Sun Rack II User's Guide and your equipment documentation for
instructions on installing equipment into the rack.
Connect the power cords using these guidelines.
As you connect power cords, label each power cord and note which outlet it is connected to, in
case you need to replace or move equipment in the rack.
Caution - When connecting equipment to the PDU, ensure that you install the most
symmetrical load to all of the phases as possible.
Caution - Circuit Overloading – When connecting equipment to the PDU, consider the
damaging effect that overloading the circuits might have on overcurrent protection and supply
wiring. Always review the equipment nameplate ratings when considering circuit overloading
issues.
Installing PDUs Into a Sun Rack II Cabinet
51
Power on the Equipment
■
When routing jumper cords, avoid cluttering the center of the rack by first routing the
jumper cords away from the PDU. Then route the jumper cords through your equipment
cable management device to your equipment.
■
Do not connect all of the equipment to the same PDU group of sockets.
For equipment with dual redundant power supplies (two power supplies), connect each
power supply to different PDUs.
■
Power on the Equipment
Power on all the equipment in the rack.
Refer to the equipment documentation for the correct power-on procedures.
52
Sun Rack II Power Distribution Units User's Guide • December 2016
Connecting Standard PDUs to the Network
Both original and enhanced standard PDUs contain a metering unit that enables you to monitor
the current (in amperes) being used by the connected equipment. The enhanced PDU metering
unit enables you to monitor voltage, power, apparent power, and energy. Before you can
monitor the PDU remotely, you must first connect it to the network.
These topics describe how to connect a standard PDU metering unit to the network. The
metering unit supports both DHCP and static IP addressing. After connecting the metering unit
to the network, see “Monitoring Original PDUs” on page 73 or “Monitoring Enhanced
PDUs” on page 105 for instructions on how to configure and monitor a PDU.
Note - Compact PDUs do not contain metering units, so you cannot connect them to the
network.
Description
Links
Connect an original PDU to a DHCP network.
“Connect an Original PDU to a DHCP Network” on page 54
Connect an original PDU to a network using a static IP
address.
“Prepare to Connect an Original PDU to a Static IP Address
Network” on page 57
“Configure a Windows PC for a Point-to-Point
Connection” on page 58
“Configure an Oracle Solaris System for a Point-to-Point
Connection” on page 62
“Connect an Original PDU to a Static IP Address
Network” on page 63
“Crossover Cable Pinout Diagram” on page 66
Connect an enhanced PDU to a DHCP network.
“Connect an Enhanced PDU to a DHCP Network” on page 66
Connect an enhanced PDU to a network using a static IP
address.
“Connect an Enhanced PDU to a Static IP Address Network Through a
SER MGT Port” on page 68
“Connect an Enhanced PDU to a Static IP Address Network Through a
DHCP-Capable Network” on page 69
Connecting Standard PDUs to the Network
53
Connecting an Original PDU to a Network
Connecting an Original PDU to a Network
Before you can set threshold alarms or monitor a PDU remotely, you must first connect the
PDU metering unit to an Ethernet network.
■
■
■
■
■
■
“Connect an Original PDU to a DHCP Network” on page 54
“Prepare to Connect an Original PDU to a Static IP Address Network” on page 57
“Configure a Windows PC for a Point-to-Point Connection” on page 58
“Configure an Oracle Solaris System for a Point-to-Point Connection” on page 62
“Connect an Original PDU to a Static IP Address Network” on page 63
“Crossover Cable Pinout Diagram” on page 66
Connect an Original PDU to a DHCP Network
1.
Gather the following:
■
■
■
■
2.
Access to the PDU metering unit
An Ethernet cable to connect the metering unit to the network
Two people—one to connect the power input lead and another to press the reset button on
the metering unit
A system on the network to log into the PDU metering unit
Confirm with your network administrator that your DHCP server can accept new
media access control (MAC) addresses.
For security reasons, some network administrators disable devices with unknown MAC
addresses from connecting to the DHCP network.
54
3.
If you have already connected the PDU's power input leads to the AC power
source, disconnect the power input leads to power off the PDU.
4.
Connect an Ethernet cable to the PDU metering unit's RJ-45 Ethernet port and to
the network.
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect an Original PDU to a DHCP Network
5.
While one person presses and holds down the PDU metering unit reset button,
another person must connect the PDU power input lead to the AC power source.
Connect only one PDU power input lead to power on the metering unit:
■
On PDUs that have one power input lead, connect that one power lead to the
AC power source.
■
On PDUs with two power leads, connect the first power lead (labeled 0) to
the AC power source.
■
On PDUs with three power input leads, connect the middle power lead
(labeled 1) to the AC power source.
Note - Press the reset button until the PDU metering unit powers on.
When you power on the PDU metering unit while pressing down on the reset button, you
temporarily enable it to connect to a DHCP network. The DHCP server assigns an IP address to
the metering unit and connects it to the network. However, if the PDU resets or power cycles,
the PDU metering unit forgets this temporary DHCP setting.
Note - To enable DHCP network connections permanently, you must configure the metering
unit to accept IP addresses only from DHCP servers.
6.
Ask your network administrator for the IP address that the DHCP server
assigned to the PDU metering unit.
Connecting Standard PDUs to the Network
55
Connect an Original PDU to a DHCP Network
Refer to the DHCP server's documentation for instructions on listing devices connected to the
DHCP network.
Note - The metering unit's LCD screen displays the IP address while the PDU powers on. See
“Monitor an Original PDU (LCD Screen)” on page 81 for more information.
7.
Type the metering unit's IP address into the web browser's address line.
On a system connected to the network, use a web browser to log on to the PDU metering unit.
Once connected, the web browser displays the Current Measurement page.
8.
Click the Net Configuration link on the upper left side of the page.
The browser prompts you to log into PDU metering unit.
9.
Log in to the PDU metering unit as an admin user.
See “Login Information” on page 71. Once logged in, the browser displays the Network
Configuration page.
56
Sun Rack II Power Distribution Units User's Guide • December 2016
Prepare to Connect an Original PDU to a Static IP Address Network
10.
Click the DHCP enable checkbox to make the metering unit obtain IP addresses
only from DHCP servers.
After clicking this checkbox, the other IP address configuration fields become unavailable.
11.
Click the Submit button to reset the PDU metering unit.
After resetting, the PDU metering unit obtains a new IP address from the DHCP server. Ask
your network administrator for the IP address that the DHCP server assigned to the PDU
metering unit.
12.
If necessary, connect the remaining PDU power input leads to the AC power
source.
Prepare to Connect an Original PDU to a Static IP
Address Network
In order to configure the PDU metering unit to use a static IP address, you must first connect
the PDU metering unit to a system using a point-to-point connection. After making this pointto-point connection, you can configure the static IP network settings.
1.
Gather the following:
Connecting Standard PDUs to the Network
57
Configure a Windows PC for a Point-to-Point Connection
■
■
■
■
2.
An Oracle Solaris system or PC system, which you use to make a point-to-point connection
to the PDU metering unit
A crossover patch cable, needed to connect the system with the PDU metering unit (see
“Crossover Cable Pinout Diagram” on page 66 for the pin descriptions of an crossover
patch cable)
A standard Ethernet cable for the final network connection
A system on the network to log in to the PDU metering unit
Ask your network administrator for the following information about the network:
■
■
■
IP address—a permanent IP address for the PDU metering unit
Subnetmask number—identifies the local portion of the local area network (LAN)
Default gateway—address of a router or a system on the network that serves as an access
point to another network
3.
If you have already connected the PDU's power input leads to the AC power
source, disconnect the power input leads to power off the PDU.
4.
Use one of the following procedures to configure your Oracle Solaris system or
PC system for a point-to-point connection:
■
■
5.
“Configure a Windows PC for a Point-to-Point Connection” on page 58
“Configure an Oracle Solaris System for a Point-to-Point Connection” on page 62
After configuring the system, connect the PDU to the network.
See “Connect an Original PDU to a Static IP Address Network” on page 63.
Configure a Windows PC for a Point-to-Point
Connection
1.
Select an unused LAN network connection from the available network
connections on your PC.
From the Start menu, select Settings -> Network Connections -> Local Area Connection.
58
Sun Rack II Power Distribution Units User's Guide • December 2016
Configure a Windows PC for a Point-to-Point Connection
where Local Area Connection is an unused LAN connection.
Connecting Standard PDUs to the Network
59
Configure a Windows PC for a Point-to-Point Connection
Selecting the unused LAN connection displays its Local Area Connection Properties window.
2.
60
In the Local Area Connection Properties window, double-click on Internet
Protocol (TCP/IP) to display Internet Protocol (TCP/IP) Properties window.
Sun Rack II Power Distribution Units User's Guide • December 2016
Configure a Windows PC for a Point-to-Point Connection
3.
In the Internet Protocol (TCP/IP) Properties window, configure the network for a
crossover connection.
a.
Select the “Use the following IP address” option.
b.
Type an IP address between 192.168.0.2 and 192.168.0.255 (for example,
192.168.0.5).
Connecting Standard PDUs to the Network
61
Configure an Oracle Solaris System for a Point-to-Point Connection
Do not use 192.168.0.1, since that address is the factory default PDU metering unit
address.
c.
Type 255.255.255.0 in the Subnet mask field.
d.
Leave the Default gateway field blank.
4.
Click the OK button in the Internet Protocol (TCP/IP) Properties window to set
these network properties.
5.
Connect the PDU to the network.
See “Connect an Original PDU to a Static IP Address Network” on page 63.
Configure an Oracle Solaris System for a Point-toPoint Connection
1.
As superuser, use the dladm command to find an unused Ethernet interface.
In the following example, the dladm command lists two Gigabit Ethernet interfaces (ce0 and
ce1) and the ifconfig command shows that only the ce0 interface is being used. Refer to the
dladm(1M) and ifconfig(1M) man pages for more information.
# dladm show-link
ce0
type: legacy
mtu: 1500
device: ce0
ce1
type: legacy
mtu: 1500
device: ce1
# ifconfig -a
lo0: flags=2001000849 <UP,LOOPBACK,RUNNING,MULTICAST,IPv4,VIRTUAL> mtu 8232 index 1
inet 127.0.0.1 netmask ff000000
ce0: flags=1000843 <UP,BROADCAST,RUNNING,MULTICAST,IPv4> mtu 1500 index 2
inet 192.168.84.253 netmask ffffff00 broadcast 192.168.84.255
ether 0:3:ba:7:84:5e
2.
Use the ifconfig command to plumb the unused network interface.
# ifconfig interface plumb up
Replace interface with the network interface device (for example, ce0, hme0, qfe1, and so on).
For example, to plumb an unused ce1 interface, type:
#ifconfig ce1 plumb up
3.
62
Use the ifconfig command to assign an IPv4 address and netmask to the
interface.
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect an Original PDU to a Static IP Address Network
# ifconfig interface IPv4-address netmask + netmaskbroadcast broadcastup
Replace:
■
interface with the network interface device
■
IPv4-address with an address between 192.168.0.2 and 192.168.0.255
■
netmask with 255.255.255.0
■
broadcast with 192.168.0.255
For example:
# ifconfig ce1 192.168.0.5 netmask + 255.255.255.0 broadcast 192.168.0.255 up
Note - Network interfaces explicitly configured using the ifconfig command do not persist
across system reboots. If you prefer, refer to the Oracle Solaris documentation for information
about setting a static IP address permanently.
4.
Connect the PDU to the network.
See “Connect an Original PDU to a Static IP Address Network” on page 63.
Connect an Original PDU to a Static IP Address
Network
Prior to starting this procedure, configure a PC or Oracle Solaris system to permit a point-topoint connection to the PDU. For a PC, see “Configure a Windows PC for a Point-to-Point
Connection” on page 58. See “Configure an Oracle Solaris System for a Point-to-Point
Connection” on page 62 for an Oracle Solaris system.
1.
Connect a crossover patch cable from the system to the PDU metering unit's RJ45 Ethernet port.
Do not connect a standard Ethernet cable between the system and the PDU, since the internal
pinouts for a crossover cable are different from the pinouts used in a standard Ethernet cable.
See “Crossover Cable Pinout Diagram” on page 66 for the pinout diagram of a crossover
cable.
2.
Connect the PDU power input lead to the AC power source.
You need to connect only one PDU power input lead to power on the PDU metering unit:
Connecting Standard PDUs to the Network
63
Connect an Original PDU to a Static IP Address Network
3.
■
On PDUs that have one power input lead, connect that one power lead to the
AC power source.
■
On PDUs with two power leads, connect the first power lead (labeled 0) to
the AC power source.
■
On PDUs with three power input leads, connect the middle power lead
(labeled 1) to the AC power source.
On the system, use a web browser to log in to the PDU metering unit.
Type the metering unit's factory-default 192.168.0.1 address in the browser's address line.
Once connected, the web browser displays the Current Measurement page.
4.
Click the Net Configuration link found in the upper left side of the page.
The browser prompts you to log into the PDU metering unit.
5.
Log in to the PDU metering unit as an admin user.
See “Login Information” on page 71. Once logged in, the browser displays the Network
Configuration page.
6.
64
In the Network Configuration page, confirm that the DHCP Enabled checkbox is
not selected, and type these network settings for the PDU metering unit:
■
IP address
■
Sub-netmask number
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect an Original PDU to a Static IP Address Network
■
Default gateway
7.
Click the Submit button to set these network settings and reset the PDU
metering unit.
8.
Disconnect the crossover cable from the PDU metering unit.
9.
Connect an Ethernet cable to the PDU metering unit's RJ-45 Ethernet port and to
the network.
10.
On a system connected to the network, use a web browser to log on to the PDU
metering unit.
Type the metering unit's static IP address into the browser's address line. If the network
configuration was successful, the browser displays the Current Measurement page.
11.
Connect the remaining PDU power input leads to the AC power source.
Connecting Standard PDUs to the Network
65
Connecting an Enhanced PDU to a Network
Crossover Cable Pinout Diagram
Connecting an Enhanced PDU to a Network
Before you can set threshold alarms or monitor a PDU remotely, you must first connect the
PDU metering unit to an Ethernet network.
■
■
■
“Connect an Enhanced PDU to a DHCP Network” on page 66
“Connect an Enhanced PDU to a Static IP Address Network Through a SER MGT
Port” on page 68
“Connect an Enhanced PDU to a Static IP Address Network Through a DHCP-Capable
Network” on page 69
Connect an Enhanced PDU to a DHCP Network
1.
Gather the following:
■
66
Access to the PDU metering unit
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect an Enhanced PDU to a DHCP Network
■
■
An Ethernet cable to connect the metering unit to the network
A system on the network to log into the PDU metering unit
2.
Confirm with your network administrator that your DHCP server can accept new
MAC addresses.
For security reasons, some network administrators disable devices with unknown MAC
addresses from connecting to the DHCP network.
3.
If you have already connected the PDU's power input leads to the AC power
source, disconnect the power input leads to power off the PDU.
4.
Connect an Ethernet cable to the PDU metering unit's RJ-45 Ethernet port and to
the network.
5.
Connect all the PDU power input leads to the AC power source.
6.
Determine the IP address using one of the following ways:
■
Via LCD screen.
Press the PDU input button the same number of times as the quantity of inputs to display
the PDU IP information on the LCD screen.
■
Via RS-232 cable
a.
Connect an RS-232 cable between the SER MGT port and the host.
b.
Configure the host's terminal or terminal emulator settings.
See “Terminal Configuration Settings” on page 72.
c.
At the terminal device, log in to the PDU metering unit as an admin user.
Connecting Standard PDUs to the Network
67
Connect an Enhanced PDU to a Static IP Address Network Through a SER MGT Port
See “Login Information” on page 71.
d.
After successful login, type get net_ipv4_ipaddr:
pducli -> get net_ipv4_addr
Connect an Enhanced PDU to a Static IP Address
Network Through a SER MGT Port
1.
If you have already connected the PDU's power input leads to the AC power
source, disconnect the power input leads to power off the PDU.
2.
Connect an RS-232 cable between the SET MGT port and the host.
3.
Connect all the PDU power input leads to the AC power source.
4.
Configure the host's terminal or terminal emulator.
See “Terminal Configuration Settings” on page 72.
5.
At the terminal device, log in to the PDU metering unit as admin.
See “Login Information” on page 71.
6.
After successful login, type.
pducli
pducli
pducli
pducli
pducli
pducli
pducli
7.
->
->
->
->
->
->
->
set net_ipv4_dhcp=Off
set net_ipv4_ipaddr=xxx.xxx.xxx.xxx
set net_ipv4_subnet=xxx.xxx.xxx.xxx
set net_ipv4_gateway=xxx.xxx.xxx.xxx
set net_ipv4_dns1=xxx.xxx.xxx.xxx
set net_ipv4_dns2=xxx.xxx.xxx.xxx
reset=yes
To verify that the settings are correct, connect an Ethernet cable between the
NET MGT and the network.
Note - HTTPS is the default setting.
8.
68
Type the IP address in a browser window.
Sun Rack II Power Distribution Units User's Guide • December 2016
Connect an Enhanced PDU to a Static IP Address Network Through a DHCP-Capable Network
If the network configuration was successful, the browser displays the Metering Overview page.
9.
Click on the Net Configuration link found in the upper left side of the page to
view the IP settings.
Connect an Enhanced PDU to a Static IP Address
Network Through a DHCP-Capable Network
1.
Confirm with your network administrator that your DHCP server can accept new
MAC addresses.
For security reasons, some network administrators disable devices with unknown MAC
addresses from connecting to the DHCP network.
2.
If you have already connected the PDU's power input leads to the AC power
source, disconnect the power input leads to power off the PDU.
3.
Connect an Ethernet cable to the PDU metering unit's RJ-45 Ethernet port and to
the network.
Connecting Standard PDUs to the Network
69
Connect an Enhanced PDU to a Static IP Address Network Through a DHCP-Capable Network
4.
Connect all the PDU power input leads to the AC power source.
5.
Determine the IP address via the LCD screen.
Press the PDU Select Input button the same number of times as the quantity of inputs to display
the PDU IP Information on the LCD screen.
6.
On the system, use a web browser to log in to the PDU metering unit.
Type the metering unit's DHCP IP address in the browser's address line. Once connected, the
web browser displays the Metering Overview page.
7.
Click the Net Configuration link found in the upper left side of the page.
The browser prompts you to log into PDU metering unit.
8.
Log in to the PDU metering unit as an admin user.
See “Login Information” on page 71. Once logged in, the browser displays the Network
Configuration page.
9.
70
In the Network Configuration page, confirm that the DHCP Enabled checkbox is
not selected, and type these network settings for the PDU metering unit:
■
IP address
■
Sub-netmask number
■
Default gateway
Sun Rack II Power Distribution Units User's Guide • December 2016
Login Information
■
DNS
10.
Click the Submit button to set these network settings and reset the PDU
metering unit.
11.
On a system connected to the network, use a web browser to log on to the PDU
metering unit.
Type the metering unit's static IP address into the browser's address line. If the network
configuration was successful, the browser displays the Metering Overview page.
12.
Click on the Net Configuration link found in the upper left side of the page to
view the IP settings.
Login Information
To log in to the PDU metering unit, you will type the user name (admin or user) and the
password. Determine the password for your user name based on your firmware version.
Only one admin or user can be logged into the metering unit at a single time.
■
admin – admin users can view all pages and configure all settings.
■
user – for original PDUs, users can view the Current Measurement and the Module Info
pages and set the thresholds on the Param Configuration page. For enhanced PDUs, users
can view the Metering Overview and Module Info pages and set the thresholds on the
Parameter page. See “Add Users and Change Passwords (Original PDU)” on page 87
Connecting Standard PDUs to the Network
71
Terminal Configuration Settings
for original PDU instructions. See “Add Users and Change Passwords (Enhanced
PDU)” on page 120 for enhanced PDU instructions on adding users.
PDU Type
Minimum Firmware Version
User Name
Password
Original PDU
1.00
admin
admin
Original PDU
1.06
admin
adm1n
Enhanced PDU
2.00
admin
adm1n
You should change the password after configuring the network.
Terminal Configuration Settings
Configure the host's terminal or terminal emulator with these settings:
■
■
■
■
■
72
9600 baud
8 bit
1 stop bit
no parity bit
no flow control
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitoring Original PDUs
The original PDU metering unit allows you to monitor the current being used by equipment
connected to a standard PDU. You can monitor the current in person by viewing the LCD
screen on the PDU itself or remotely from a system on the network.
Using the metering unit's HTML and SNMP interfaces, you can set threshold and alarm levels
that you can monitor remotely. You also can configure the metering unit to send messages to
systems on the network.
Note - Compact PDUs do not contain metering units, so you cannot monitor the current of
equipment connected to them.
The following table lists the tasks necessary to configure and use the PDU metering unit.
Description
Links
Understand the relationship between the metering unit
interface and the PDU outlet groups.
“Understanding the Relationship Between Modules and Outlet
Groups” on page 73
Access the metering unit from a system on the network.
“Access a Metering Unit on the Network (Original PDU)” on page 78
Set the amperage threshold alarm values.
“Set Threshold Parameter Levels (Original PDU)” on page 79
Monitor the amperage levels.
“Monitoring an Original PDU” on page 81
Change the metering unit interface settings.
“Changing Interface Settings (Original PDU)” on page 86
Enable and configure SNMP settings.
“Enabling and Configuring SNMP (Original PDU)” on page 91
View the metering unit firmware version and update the
firmware.
“Verifying and Updating the Firmware (Original PDU)” on page 96
Use the PDU metering unit's LCD screen.
“Administering the PDU Metering Unit (Original PDU)” on page 99
Restore the PDU metering unit's settings back to the factory
default settings.
“Restore the PDU to Factory Default Settings (Original
PDU)” on page 102
Understanding the Relationship Between Modules and
Outlet Groups
These topics describe the relationship between modules and outlet groups.
Monitoring Original PDUs
73
Understanding the Relationship Between Modules and Outlet Groups
■
■
■
“Relationship Between Modules and Outlet Groups Overview” on page 74
“Single-Phase PDU Module and Outlet Group Relationship” on page 75
“Three-Phase PDU Module and Outlet Group Relationship” on page 77
Relationship Between Modules and Outlet Groups
Overview
The metering unit monitors modules, which are collections of PDU power outlet groups.
Depending on the PDU, a module might contain all of the outlet groups on the PDU, or a subset
of the groups. The metering unit monitors the current flowing through each module, not through
each outlet group.
A metering unit module might also be divided into phases, which can either correspond to each
power input lead in single-phase PDUs, or the separate phases in three-phase PDUs.
“Single-Phase PDU Module and Outlet Group Relationship” on page 75 and “Three-Phase
PDU Module and Outlet Group Relationship” on page 77 show how the metering unit
divides the outlet groups into modules and phases.
These topics also help you understand the metering unit's web interface, SNMP messages,
system log messages, and LCD screen. For example, if your rack contains a high-voltage
37 kVA PDU and the PDU's LCD screen shows that phase 2 of module 3 is using excessive
current, the equipment connected to outlet group 7 needs attention.
Note - Refer to the labels on the PDUs to see the locations of these outlet groups.
74
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding the Relationship Between Modules and Outlet Groups
Single-Phase PDU Module and Outlet Group
Relationship
FIGURE 3
Single-Phase PDU Metering Unit Module and Outlet Group Relationship
Monitoring Original PDUs
75
Understanding the Relationship Between Modules and Outlet Groups
TABLE 11
Relationship Between Metering Unit Modules and Outlet Groups on Single-Phase PDUs
PDU Type
Metering Unit Module
Metering Unit Phase
Outlet Group
Power Input Lead Number
5 kVA
M1
Phase 1
0, 1, 2, 3, 4, 5
0
10 kVA
M1
Phase 1
0, 1, 2
0
Phase 2
3, 4, 5
1
Phase 1
0, 1
0
Phase 2
2, 3
1
Phase 3
4, 5
2
15 kVA, 22kVA
76
M1
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding the Relationship Between Modules and Outlet Groups
Three-Phase PDU Module and Outlet Group
Relationship
FIGURE 4
Three-Phase PDU Metering Unit Module and Outlet Group Relationship
Monitoring Original PDUs
77
Access a Metering Unit on the Network (Original PDU)
Note - For three-phase, low-voltage PDUs, each metering unit phase reports current from two
outlet groups. Metering unit phase 1 reports a combination of current from outlet groups 0 and
2 (3 and 5 or 6 and 8 depending on which input). Metering unit phase 2 reports a combination
of current from outlet groups 1 and 0 (4 and 3 or 7 and 6 depending on which input). Metering
unit phase 3 reports a combination of current from outlet groups 2 and 1 (5 and 4 or 8 and 7
depending on which input).
Relationship Between Metering Unit Modules and Outlet Groups on Three-Phase PDUs
TABLE 12
PDU Type
Metering Unit Module
Metering Unit Phase
Outlet Group
Power Input Lead
Number
15 kVA
M1
Phase 1
0, 3
0
Phase 2
1, 4
0
Phase 3
2, 5
0
Phase 1
0
0
Phase 2
1
0
Phase 3
2
0
Phase 1
3
1
Phase 2
4
1
Phase 3
5
1
Phase 1
0
0
Phase 2
1
0
Phase 3
2
0
Phase 1
3
1
Phase 2
4
1
Phase 3
5
1
Phase 1
6
2
Phase 2
7
2
Phase 3
8
2
24 kVA
M1
M2
37 kVA
M1
M2
M3
Access a Metering Unit on the Network (Original PDU)
After you connect the PDU metering unit to the network, you can use a web browser to access
the metering unit from any system on the network.
Note - The Original PDU supports both, 10/100 Full Duplex and 10/100 Half Duplex but not
auto-negotiation as defined in IEEE802.3u. The Original PDU uses "auto detection" which
means it configures itself to match the switch port. If a specific mode of operation is needed the
switch port needs to be configured to the specific mode of operation.
1.
78
Ask your network administrator for the IP address of the PDU metering unit.
Sun Rack II Power Distribution Units User's Guide • December 2016
Set Threshold Parameter Levels (Original PDU)
Use the static IP address you configured the metering unit to use, or ask your network
administrator for the IP address assigned by the DHCP server. Refer to the DHCP server's
documentation for instructions on listing devices connected to the DHCP network.
2.
On a system connected to the network, type the metering unit IP address in a
web browser's address line to connect to the PDU metering unit.
Once connected, the browser displays the Current Measurement page.
Note - All users can view the Current Measurement and Module Info pages. If you attempt to
view another page, you are prompted to log in. See the following figure.
3.
When prompted, log in as an admin or a user.
See “Login Information” on page 71.
Set Threshold Parameter Levels (Original PDU)
The Current Measurement page displays the amps being used by each PDU module and phase,
as well as a graphical measurement of the values. After you set amp threshold parameter levels,
the page shows the graphical measurements in different colors, depending on how you set the
threshold levels. See “Monitor an Original PDU (HTML Interface)” on page 83 for more
information.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
Monitoring Original PDUs
79
Set Threshold Parameter Levels (Original PDU)
2.
Click on the Param Configuration link and log in as either an admin or user.
The Param Configuration page displays and identifies the PDU modules and phases. Depending
on your PDU, you might have one or more modules with one or more phases per module. See
“Understanding the Relationship Between Modules and Outlet Groups” on page 73 for a
description of PDU modules.
3.
For each module, type in current levels for each threshold parameter.
a.
80
For each phase of the module, set the following parameters (in amps):
■
Info Low – A value when the attached equipment is not using enough
current
■
Pre Warning – A value when the attached equipment is beginning to use
too much current
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitoring an Original PDU
■
b.
Alarm – A value when the equipment is using a critical amount of
current and requires immediate attention
Set the Out of Balance amp level for the entire module.
A PDU can become out of balance if one phase uses more current than the others. Set
the out of balance parameter to the number of amps that one phase cannot use more than
any other in the module. For example, if you set this parameter to 5, and phase 1 uses 12
amps of current and phase 3 uses 4 amps, the Current Measurement page displays an out of
balance error message.
Note - If the PDU module contains only one phase, the Out of Balance parameter is not
available.
4.
c.
(Optional) If you have enabled SNMP control for the PDU, you can enable
SNMP control for each PDU module.
If you enable SNMP on the Net Configuration page, you enable SNMP for all modules in
the PDU. However, you can disable or enable SNMP control of each PDU module from
this page. See “Enable and Configure SNMP (Original PDU)” on page 92 for more
information about SNMP settings.
d.
Click the Submit button to set these threshold parameter values for the
module.
If you want to reset all values, click the Reset button and then the Submit button.
Repeat Step 3 for each PDU module.
Monitoring an Original PDU
You can monitor how much current the equipment connected to a PDU uses by either checking
the PDU's LCD screen or by viewing the Current Measurement page using the HTML interface.
■
■
“Monitor an Original PDU (LCD Screen)” on page 81
“Monitor an Original PDU (HTML Interface)” on page 83
Monitor an Original PDU (LCD Screen)
You can check the current being used by equipment attached to a PDU by viewing the PDU's
metering unit LCD screen.
1.
Locate the PDU you want to monitor in the rack.
Monitoring Original PDUs
81
Monitor an Original PDU (LCD Screen)
You might need to open the rack's rear door to access the PDU.
82
2.
Locate the metering unit on the PDU.
You can find the metering unit in the middle of the PDU.
3.
Check the metering unit's LCD screen to view the current being used by the
equipment connected to each PDU module.
The LCD screen displays the amp measurements of all of the phases of a single PDU module.
See “Understanding the Relationship Between Modules and Outlet Groups” on page 73 for
a description of PDU modules.
■
If your PDU has more than one module, press the reset button to cycle
through the available modules.
■
For easier viewing, you can rotate the screen in 90-degree intervals by
pressing the reset button for longer than 1 second. See “Adjust the LCD
Screen (Original PDU)” on page 101 for more information.
No.
Description
1
Module number
2
Measured amp reading of the current being used by the equipment connected to the PDU
phase
3
Abbreviation for amperes (amps)
4
Metering unit phase number
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitor an Original PDU (HTML Interface)
Monitor an Original PDU (HTML Interface)
Using the metering unit's HTML interface, you can monitor the current being used by attached
equipment. You can also see how these current readings relate to the threshold parameters you
set in “Set Threshold Parameter Levels (Original PDU)” on page 79.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78. After accessing
the PDU, the Current Measurement page displays.
2.
View the Current Measurement page.
The following figure shows an example Current Measurement page for a 37 kVA PDU, which
has three modules with three phases each. See “Understanding the Relationship Between
Modules and Outlet Groups” on page 73 for a description of PDU modules.
Monitoring Original PDUs
83
Monitor an Original PDU (HTML Interface)
The following figure displays the details of a single PDU module.
No.
Description
1
PDU Module number
2
Out of Balance alarm message
3
Graph displaying the amps of current being used per phase
4
Number of amps of current being used per phase
5
Table showing the threshold parameter settings
If you set threshold parameter values (see “Set Threshold Parameter Levels (Original
PDU)” on page 79), the module graph and current amp number are displayed in different
colors, depending on how much current the attached equipment is using. See the following table
for a description of these colors.
84
Sun Rack II Power Distribution Units User's Guide • December 2016
Current and Voltage Measurement Colors
Note - If you do not set any threshold parameter values, all of the measurements are displayed
in red.
Caution - If the PDU is out of balance, the PDU and the attached equipment might heat up and
cause serious damage to the equipment, PDU, and the rack. Power off the equipment and the
PDU immediately.
Current and Voltage Measurement Colors
If you set threshold parameter values for an original PDU (See“Set Threshold Parameter Levels
(Original PDU)” on page 79), the module graph and current amp number are displayed in
one of the colors in this table.
If you set values for an enhanced PDU (See “Set Threshold Parameter Values (Enhanced
PDU)” on page 111), the color behind the black line is one of the colors in this table.
TABLE 13
Color Descriptions of PDU Module Measurements
Color
Value
Description
Blue
Measured current is below Info Low
threshold.
Attached equipment is using less current than
expected.
Green
Measured current is between the Info Low and
Pre Warning thresholds.
Attached equipment is using the expected
amount of current.
Yellow
Measured current is between the Pre Warning
threshold, and the Alarm threshold.
Attached equipment is using more current
than expected.
Red
Measured current is above the Alarm
threshold.
Attached equipment is using a critical amount
of current and requires immediate attention.
Blinking red
Measured current is above the Out of Balance
threshold. Also, an blinking red “Out of
Balance” message displays above the module
graph.
The equipment attached to one phase is using
more current than the other phases on the
input. The PDU and attached equipment
require immediate attention.
Color
Value
Description
Green
Measure of Voltage is above Warning threshold.
Attached equipment is operating with an
expected voltage level.
Yellow
Measured Voltage is between Warning and Alarm
threshold.
Attached equipment is operating at an
allowable voltage level.
Red
Measured Voltage is below Alarm threshold.
Attached equipment might not operate as
expected.
Monitoring Original PDUs
85
Changing Interface Settings (Original PDU)
Caution - If the PDU input voltage is below the Alarm level, the attached equipment (and PDU)
might be damaged. Power off the equipment and PDU immediately.
Changing Interface Settings (Original PDU)
The HTML interface allows you to name a PDU, assign new users, and send system log
messages to systems on the network.
■
■
■
“Set the PDU Name and Location (Original PDU)” on page 86
“Add Users and Change Passwords (Original PDU)” on page 87
“Send System Log Messages to Systems on the Network (Original PDU)” on page 88
Set the PDU Name and Location (Original PDU)
It is a good practice to name the PDU you are monitoring, especially if your network contains
multiple racks and PDUs. Besides the name, you can set the location of the PDU as well. When
set, the name and location are displayed on the top of each HTML page.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
86
3.
Scroll down the page until you see the Module Name & Location fields.
4.
Provide a name and a location for the PDU.
Sun Rack II Power Distribution Units User's Guide • December 2016
Add Users and Change Passwords (Original PDU)
A name and location cannot be more than 15 characters.
5.
Click the Submit button to set the PDU name and location.
6.
Click your web browser Reload or Refresh button to view the updated PDU name
and location.
Add Users and Change Passwords (Original PDU)
Including the admin user, you can set up to five PDU users. Admin users can view all
pages, while the other users can only view the Current Measurement page and the Param
Configuration page.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
3.
Scroll down the page until you see the Admin/User fields.
4.
Type in up to five users into the Admin/User fields.
Type in a name and password for each user, and designate the user an admin or a user. If you
change the admin user name or password, write the name and password down and save it in a
secure location.
Monitoring Original PDUs
87
Send System Log Messages to Systems on the Network (Original PDU)
Note - Use only letters and numbers in user names and passwords.
5.
Click the Submit button to set the PDU users and passwords.
Send System Log Messages to Systems on the
Network (Original PDU)
In the preceding example, M1Ph1 12.3A means that there is a 12.3 amp current measurement
on module 1, phase 1 of the PDU. A --.-A amp measurement means that the PDU module is not
available (has nothing connected to it or does not exist).
For more information about syslog, refer to the Oracle Solaris documentation and the
syslogd(1M) and syslog.conf(4) man pages.
You can set the PDU to send system log (syslog) messages to up to four systems on the
network. syslog is the standard UNIX system logging utility, which monitors critical system
events and configuration changes. These syslog messages are sent to the systems using user
datagram protocol (UDP) port 514.
Here is an example PDU syslog message:
88
Sun Rack II Power Distribution Units User's Guide • December 2016
Send System Log Messages to Systems on the Network (Original PDU)
PDU-Values: M1Ph1 12.3A M1Ph2 12.1A M1Ph3 12.2A M2Ph1 0.0A
M2Ph2 0.0A M2Ph3 0.0A M3Ph1 --.-A M3Ph2 --.-A M3Ph3 --.-A
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
Monitoring Original PDUs
89
Send System Log Messages to Systems on the Network (Original PDU)
90
3.
Scroll down the page until you see the Syslog heading.
4.
Click the Syslog Enable checkbox to enable the syslog message logging, then
click the Submit button.
Sun Rack II Power Distribution Units User's Guide • December 2016
Enabling and Configuring SNMP (Original PDU)
5.
Type in up to four IP addresses of systems you want the metering unit to send
syslog messages, then click the Submit button below the IP addresses.
6.
Set the time duration between sending syslog messages.
Valid time settings include:
■
Hours: 0 - 23
■
Minutes: 0 - 59
■ Seconds: 0 - 59
For example, if you set the duration for 12 hours, the PDU sends syslog messages every 12
hours.
7.
Click the Alarms checkbox to send alarm messages over syslog messages.
If checked, and if you set threshold parameter values (see “Set Threshold Parameter Levels
(Original PDU)” on page 79), the metering unit sends alarm messages when threshold
parameter values are reached.
Possible syslog alarm messages include:
■
Dead-Trap
A Dead-Trap message is sent after a PDU power cycle.
■
InfoLow-Trap on ModuleNum/PhaseNum
■
PreWarningHigh-Trap on ModuleNum/PhaseNum
■
AlarmHigh-Trap on ModuleNum/PhaseNum
■
ReturnToNormal-Trap on ModuleNum/PhaseNum
■
OutOfBalance-Trap for ModuleNum
ModuleNum/PhaseNum corresponds to the PDU's module number and phase number.
8.
Click the Submit button to enable these settings.
Enabling and Configuring SNMP (Original PDU)
The PDU metering unit supports Simple Network Management Protocol (SNMP). SNMP
provides the ability to send traps, or notifications, when one or more conditions have been met.
Monitoring Original PDUs
91
Enable and Configure SNMP (Original PDU)
If you enable SNMP, the metering unit can send and receive traps to and from SNMP agents on
the network.
Note - These sections do not describe how to view SNMP trap information using an SNMP
agent. Refer to your SNMP agent documentation for details on how to use it to view SNMPbased information.
■
■
■
“Types of PDU Metering Unit SNMP Traps (Original PDU)” on page 92
“Enable and Configure SNMP (Original PDU)” on page 92
“Specify NMS Hosts (Original PDU)” on page 95
Types of PDU Metering Unit SNMP Traps (Original
PDU)
The following table describes the SNMPv2 traps the metering unit can send to SNMP agents on
the network (over UDP port 162). In the trap descriptions, ModuleNum/PhaseNum corresponds
to the module number and phase number of the PDU (for example, Module1/Phase2).
SNMP Trap
SNMP Notification
Description
Keep alive
KeepAlive-Trap
The PDU sends a KeepAlive-Trap message
to the SNMP host to ensure that the link
between them is operational.
Dead
Dead-Trap
Sent after a PDU power cycle.
Info low
InfoLow-Trap on ModuleNum/PhaseNum
Attached equipment is using less current than
expected.
PreWarning high
PreWarningHigh-Trap on ModuleNum/PhaseNum
Attached equipment is using more current
than expected.
Alarm high
AlarmHigh-Trap on ModuleNum/PhaseNum
Attached equipment is using a critical amount
of current and requires immediate attention.
Return to normal
ReturnToNormal-Trap on ModuleNum/PhaseNum
After sending an alarm trap, the attached
equipment has returned to using the expected
amount of current.
Out of balance
OutOfBalance-Trap on ModuleNum/PhaseNum
The equipment attached to one phase is using
more current than the other phases on the
module. The PDU and attached equipment
require immediate attention.
Enable and Configure SNMP (Original PDU)
Use the HTML interface to enable SNMP, specify SNMP community hosts, and set repeating
SNMP trap durations.
92
Sun Rack II Power Distribution Units User's Guide • December 2016
Enable and Configure SNMP (Original PDU)
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
3.
Scroll down the page until you see the SNMP heading.
4.
Click the SNMP Enable checkbox to enable SNMP.
If desired, you can disable HTTP access to the PDU by deselecting the HTTP enable checkbox
located just above the SNMP heading.
Caution - If you disable HTTP, you are no longer be able to log in to the HTML interface using
a web browser. To re-enable HTTP access, you must use your SNMP agent software. Refer to
your SNMP agent documentation or the Solaris snmpset(1M) man page for more information.
5.
Under the Trap Host Setup heading, define up to 10 SNMP hosts.
Monitoring Original PDUs
93
Enable and Configure SNMP (Original PDU)
Once configured, the metering unit sends SNMP traps to these hosts. For each host, type in
the IP address and the SNMP community name. An SNMP community name identifies which
SNMP group the host belongs.
6.
Provide values to the repeating trap settings.
Here is a description of these repeating trap settings.
94
Setting
Description
Permitted
Values
KeepAlive Trap
The number of seconds between repeating the KeepAlive
trap.
0 - 60
Sun Rack II Power Distribution Units User's Guide • December 2016
Specify NMS Hosts (Original PDU)
7.
Setting
Description
Permitted
Values
Repeating Time for Traps
The number of seconds between sending trap messages to
SNMP hosts.
0 - 60
Number of traps
The number of times the same trap can repeated to the same
host.
0 -255
Click the Submit button to enable these SNMP settings.
Specify NMS Hosts (Original PDU)
A network management station (NMS) host runs network management applications that
monitor and control SNMP managed devices. NMS hosts provide the resources required for
network management.
You can specify up to four NMS hosts on the network.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
Monitoring Original PDUs
95
Verifying and Updating the Firmware (Original PDU)
3.
Scroll down the page until you see the NMS heading.
4.
Specify up to four NMS hosts.
For each NMS host, type the IP address and the SNMP community name. An SNMP
community name identifies which SNMP group the host belongs.
5.
Click the Submit button to enable these NMS settings.
Verifying and Updating the Firmware (Original PDU)
The PDU metering module contains firmware that operates the LCD screen and provides the
HTML interface. This firmware might be updated in the future to correct issues and provide
new functionality.
■
■
96
“View Module Information (Original PDU)” on page 97
“Update the PDU Metering Unit Firmware (Original PDU)” on page 98
Sun Rack II Power Distribution Units User's Guide • December 2016
View Module Information (Original PDU)
View Module Information (Original PDU)
Before downloading any new firmware, confirm the firmware revision level currently running
on the PDU metering unit.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Module Info link to verify the firmware revision level, as well as
other information, on the Module Info page.
No.
Description
1
MAC address of the PDU metering unit
2
Currently installed firmware version
3
Currently installed bootloader version
4
PDU serial number
5
PDU part number
6
Date of the PDU manufacture (MM-DD-YYYY)
Monitoring Original PDUs
97
Update the PDU Metering Unit Firmware (Original PDU)
Update the PDU Metering Unit Firmware (Original
PDU)
You can download updates of the PDU metering unit firmware from the Downloads web site.
Caution - When updating the firmware, you must update both the metering unit firmware and
the HTML interface pages. Failure to update the HTML pages causes certain pages of the
interface not to display, which renders the web interface unusable.
Note - Updating the firmware does not overwrite any configurations you set previously.
1.
Using a web browser, connect to the Downloads web site:
https://myoraclesupport.com
2.
Locate and download the latest version of the firmware.
To locate the latest PDU firmware, search the Download Center for the Sun Rack II. Follow the
instructions on the web site to download the firmware.
3.
Save the downloaded firmware ZIP file to a directory accessible to the PDU over
the network.
If the download is not in a ZIP file, make sure you download both the metering unit firmware
(MKAPP_Vx.x.dl) and the HTML interface files (HTML_Vx.x.dl).
4.
Use the unzip command to extract the metering unit firmware from the
downloaded ZIP file.
The downloaded ZIP file contains two update files:
■
MKAPP_Vx.x.dl – metering unit firmware
■
HTML_Vx.x.dl – HTML interface files
If the ZIP file also contains a text file, review it for any additional information about the
firmware updates.
5.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
6.
Click on the Net Configuration link and log in as an admin user.
You are prompted to log in as an admin user. By default, both the admin user name and
password is admin.
98
Sun Rack II Power Distribution Units User's Guide • December 2016
Administering the PDU Metering Unit (Original PDU)
7.
Scroll down the page until you see the Firmware-Update heading.
8.
Click on the Browse button and locate the MKAPP_Vx.x.dl file you downloaded
previously.
9.
Click the Submit button to update the metering unit firmware.
After updating the firmware, you are prompted to update the HTML interface.
10.
Click on the Browse button again, log in as an admin user, and locate the
HTML_Vx.x.dl file you downloaded previously.
11.
Click the Submit button update the metering unit firmware.
12.
Confirm that you updated the firmware and HTML interface successfully.
See “View Module Information (Original PDU)” on page 97 for instructions on viewing the
firmware revision level.
Administering the PDU Metering Unit (Original PDU)
Besides monitoring the current of connect equipment, you can reset the PDU, view information
about the network connection and firmware revisions, and adjust the LCD screen.
■
■
■
“Reset the PDU Metering Unit (Original PDU)” on page 99
“View Status Information on the LCD Screen (Original PDU)” on page 100
“Adjust the LCD Screen (Original PDU)” on page 101
Reset the PDU Metering Unit (Original PDU)
You can reset the PDU metering unit using the reset button.
Note - Resetting the metering unit does not power cycle equipment attached to the PDU.
Monitoring Original PDUs
99
View Status Information on the LCD Screen (Original PDU)
1.
Press and hold the reset button until you see a five-second countdown displayed
on the LCD screen.
You must press the reset button for 20 seconds before the five-second countdown begins.
2.
During the five-second countdown, release the reset button and then tap the
button again to force the metering unit to reset.
View Status Information on the LCD Screen
(Original PDU)
When the PDU metering unit resets or powers on, you can view network and firmware version
level information on the LCD screen.
1.
Reset the PDU metering unit.
See “Reset the PDU Metering Unit (Original PDU)” on page 99 for instructions.
2.
After the metering unit resets, the LCD screen displays information about the
unit.
The screen displays the following information:
HW: x.x FW:x.x
100
Sun Rack II Power Distribution Units User's Guide • December 2016
Adjust the LCD Screen (Original PDU)
DHCP: OFF (or ON)
MAC: xx-xx-xx-xx-xx-xx
IP: xxx.xxx.xxx.xxx
HTML: VALID
The following table describes the LCD screen information.
LCD Text
Description
HW
Version of the PDU hardware.
FW
Version of the PDU firmware.
DHCP
Displays ON, when DHCP is enabled, and OFF when DHCP is disabled. See “Connect an Original
PDU to a DHCP Network” on page 54 for more information about DHCP.
MAC
MAC address of the metering unit.
IP
IP address of the metering unit.
■ If DHCP is OFF, the IP address is an internally stored static address.
■ If DHCP is ON, the IP address is set by the DHCP server.
HTML
Displays VALID when the correct version of the HTML pages is installed, INVALID when not.
Adjust the LCD Screen (Original PDU)
You can adjust the LCD screen orientation and background to help you view the screen within
the rack.
Press and hold the reset button until the LCD screen rotates 90 degrees??.
Continue to press and release the reset button to cycle through different LCD screen
orientations. The first four screens have white text on a black background, while the other four
Monitoring Original PDUs
101
Restore the PDU to Factory Default Settings (Original PDU)
have black text on a white background. The final selected screen becomes the new default
orientation.
Restore the PDU to Factory Default Settings (Original
PDU)
If you need to correct a configuration error, or you want to clear the PDU before moving it to a
different rack, you can restore the PDU metering unit back to its factory settings.
After restoring the unit, all network and configuration settings reset back to their default values
(for example, admin is the only user and the IP address returns to 192.168.0.1). All settings
that you set for your environment are lost.
Note - After restoring the PDU metering unit back to its factory settings, you must reconnect it
to the network. See “Connecting Standard PDUs to the Network” on page 53 for instructions.
102
1.
Log in to the PDU metering unit.
See “Access a Metering Unit on the Network (Original PDU)” on page 78.
2.
Click on the Net Configuration link and log in as an admin user.
Sun Rack II Power Distribution Units User's Guide • December 2016
NET MGT Port LED and Pin Descriptions
See “Login Information” on page 71.
3.
Scroll down the page until you see the Factory-Reset heading.
4.
Click the Submit button to restore the PDU metering unit back to its default
factory settings.
NET MGT Port LED and Pin Descriptions
Pin
Signal Description
Pin
Signal Description
1
Transmit+ (TX+)
6
Receive- (RX-)
2
Transmit- (TX-)
7
Not used
3
Receive+ (RX+)
8
Not used
4
Not used
9
Activity LED – flashes when network data is
being transmitted through the port
5
Not used
10
Link LED – lights when the unit is connected
to a network
Monitoring Original PDUs
103
104
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitoring Enhanced PDUs
For enhanced PDUs, there are four ways you can monitor how much power, energy, and current
the equipment attached to the PDU uses, as well as the voltage level powering the equipment.
You also can configure the metering unit to send messages to systems on the network.
Note - Compact PDUs do not contain metering units, so you cannot monitor the current of
equipment connected to them.
The following table lists the tasks necessary to configure and use the PDU metering unit.
Description
Links
Understand the relationship between the metering unit
interface and the PDU outlet groups.
“Understanding the Relationship Between Inputs and Outlet
Groups” on page 105
Access the metering unit from a system on the network.
“Access a Metering Unit on the Network (Enhanced
PDU)” on page 110
Set the voltage and current threshold values.
“Set Threshold Parameter Values (Enhanced PDU)” on page 111
Monitor the power, energy, current, and voltage levels.
“Monitoring an Enhanced PDU” on page 114
“Understanding CLI Commands” on page 145
Change the metering unit interface settings.
“Changing Interface Settings (Enhanced PDU)” on page 119
Enable and configure SNMP settings.
“Enabling and Configuring SNMP (Enhanced PDU)” on page 124
View the metering unit firmware version and update the
firmware.
“Verifying and Updating the Firmware (Enhanced PDU)” on page 129
Use the PDU metering unit's LCD screen.
“Administering the PDU Metering Unit (Enhanced PDU)” on page 132
Set the PDU time.
“Set the PDU System Time” on page 137
Check the PDU event logging page.
“Access the Event Logging Page” on page 138
Restore the PDU metering unit's settings back to the factory
default settings.
“Restoring the PDU to Factory Default Settings (Enhanced
PDU)” on page 139
Understanding the Relationship Between Inputs and Outlet
Groups
These topics describe the relationship between inputs and outlet groups.
Monitoring Enhanced PDUs
105
Understanding the Relationship Between Inputs and Outlet Groups
■
■
■
“Relationship Between Inputs and Outlet Groups Overview” on page 106
“Single-Phase PDU Input and Outlet Group Relationship” on page 107
“Three-Phase PDU Input and Outlet Group Relationship” on page 109
Relationship Between Inputs and Outlet Groups
Overview
The metering unit monitors inputs, which are collections of PDU power outlet groups.
Depending on the PDU, an input might contain all of the outlet groups on the PDU, or a subset
of the groups. The metering unit monitors the current, voltage, power, apparent power, and
energy flowing through each input, not through each outlet group.
A metering unit input might also be divided into phases, which can either correspond to each
power input lead in single-phase PDUs, or the separate phases in three-phase PDUs.
“Single-Phase PDU Input and Outlet Group Relationship” on page 107 and “Three-Phase
PDU Input and Outlet Group Relationship” on page 109 show how the metering unit divides
the outlet groups into inputs and phases.
These topics also help you understand the metering unit's web interface, SNMP messages,
system log messages, and LCD screen. For example, if your rack contains a high-voltage 37
kVA PDU and the PDU's LCD screen shows that L2 of IN2 is using excessive current, the
equipment connected to outlet group 7 needs attention.
Note - Refer to the labels on the PDUs to see the locations of these outlet groups.
106
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding the Relationship Between Inputs and Outlet Groups
Single-Phase PDU Input and Outlet Group
Relationship
FIGURE 5
Single-Phase PDU Input and Outlet Group Relationship
Monitoring Enhanced PDUs
107
Understanding the Relationship Between Inputs and Outlet Groups
TABLE 14
PDU Type
Metering Unit Inputs and Outlet Groups on Single-Phase PDUs
Power Input
Outlet Group
Lead Number
10 kVA
15 kVA, 22 kVA
108
0
0, 1, 2
1
3, 4, 5
0
0, 1
1
2, 3
2
4, 5
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding the Relationship Between Inputs and Outlet Groups
Three-Phase PDU Input and Outlet Group
Relationship
FIGURE 6
Three-Phase PDU Input and Outlet Group Relationship
Monitoring Enhanced PDUs
109
Access a Metering Unit on the Network (Enhanced PDU)
Note - For three-phase, low-voltage PDUs, each metering unit phase reports current from two
outlet groups. Input phase 1 reports a combination of current from outlet groups 0 and 2 (3 and
5, or 6 and 8, depending on which input). Input phase 2 reports a combination of current from
outlet groups 1 and 0 (4 and 3, or 7 and 6, depending on which input). Input phase 3 reports a
combination of current from outlet groups 2 and 1 (5 and 4, or 8 and 7, depending on which
input).
Relationship Between Metering Unit Inputs and Outlet Groups on Three-Phase PDUs
TABLE 15
PDU Type
Power Input
Input Phase
Outlet Group
0
Phase 1
0, 3
0
Phase 2
1, 4
0
Phase 3
2, 5
0
Phase 1
0
0
Phase 2
1
0
Phase 3
2
1
Phase 1
3
1
Phase 2
4
1
Phase 3
5
0
Phase 1
0
0
Phase 2
1
0
Phase 3
2
1
Phase 1
3
1
Phase 2
4
1
Phase 3
5
2
Phase 1
6
2
Phase 2
7
2
Phase 3
8
Lead Number
15 kVA
24 kVA
37 kVA
Access a Metering Unit on the Network (Enhanced PDU)
After you connect the PDU metering unit to the network, you can use a web browser to access
the metering unit from any system on the network.
Note - HTTPS is the default setting.
1.
Determine the IP address of the PDU metering unit.
a.
110
Use the static IP address you configured the metering unit to use.
Sun Rack II Power Distribution Units User's Guide • December 2016
Set Threshold Parameter Values (Enhanced PDU)
2.
b.
Press the Select Input button until the PDU information appears.
c.
Ask your network administrator for the IP address assigned by the DHCP
server. Refer to the DHCP server's documentation for instructions on listing
devices connected to the DHCP network.
On a system connected to the network, type the metering unit IP address in a
web browser's address line to connect to the PDU metering unit.
Once connected, the browser displays the Metering Overview page.
Note - All users can view the Metering Overview and Module Info pages. If you attempt to
view another page, you are prompted to log in.
3.
When prompted, log in as an admin or a user.
See “Login Information” on page 71.
Note - You are automatically logged out after 10 minutes of inactivity. You can also log out by
clicking on the Logout button.
Set Threshold Parameter Values (Enhanced PDU)
The Metering Overview page displays the power information for each PDU input, as well as
a graphical measurement of the values. After you set current threshold parameter levels, the
page shows the graphical measurements in different colors, depending on how you set the
threshold levels. See “Monitor the Enhanced PDU (HTML Interface)” on page 115 for more
information.
Monitoring Enhanced PDUs
111
Set Threshold Parameter Values (Enhanced PDU)
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Parameter link and log in as either an admin or user.
See “Login Information” on page 71.
The Parameter page displays and identifies the PDU inputs and phases. Depending on
your PDU, you might have one or more inputs with one or more phases per input. See
“Understanding the Relationship Between Inputs and Outlet Groups” on page 105 for a
description of PDU inputs.
Note - The Clear Energy for the Input and PDU option allows you to reset Energy to zero to
begin monitoring from “0”.
3.
112
For each input, type in current levels for each threshold parameter.
Sun Rack II Power Distribution Units User's Guide • December 2016
Set Threshold Parameter Values (Enhanced PDU)
a.
b.
For each phase of the input, set the following parameters (in amps):
■
Info – A value when the attached equipment is using less current than
expected.
■
Warning – A value when the attached equipment is using more current
than expected.
■
Alarm – A value when the equipment is using a critical amount of
current and requires immediate attention
Set the Out of Balance current level for the entire input.
A PDU can become out of balance if one phase uses more current than the others. Set the
out of balance parameter to the number of amps that one phase cannot use more than any
other in the input. For example, if you set this parameter to 5, and phase 1 uses 12 amps of
current and phase 3 uses 4 amps, the Metering Overview displays an out of balance error
message.
Note - If the PDU input contains only one phase, the Out of Balance parameter is not available.
c.
For each phase of the input, set the following parameters (in volts).
■
■
d.
Warning – the minimal nominal operating voltage.
Alarm – the minimal allowable operating voltage.
(Optional) If you have enabled SNMP control for the PDU, you can enable
SNMP control for each PDU input.
If you enable SNMP on the Net Configuration page, you enable SNMP for all inputs in
the PDU. However, you can disable or enable SNMP control of each PDU input from
this page. See “Enable and Configure SNMP (Enhanced PDU)” on page 125 for more
information about SNMP settings.
e.
Click the Submit button to set these threshold parameter values for the
input.
■
■
4.
For FW version 2.01, the Reset button is available to reset all values.
Beginning with FW version 2.02, the Reset button is not available.
Repeat Step 3 for each PDU input.
Monitoring Enhanced PDUs
113
Monitoring an Enhanced PDU
Monitoring an Enhanced PDU
There are four ways you can monitor how much power, energy and current the equipment
attached to the PDU uses, as well as the voltage level powering the equipment, the PDU's LCD
screen, the Monitoring Overview page using HTML interface, the RS-232 interface, or the SSH
interface.
Note - To provide better security, CLI access via telnet interface is not supported.
■
■
■
■
“Monitor the Enhanced PDU (LCD Screen)” on page 114
“Monitor the Enhanced PDU (HTML Interface)” on page 115
“Monitor the Enhanced PDU (RS-232)” on page 118
“Monitor the Enhanced PDU (SSH)” on page 119
Monitor the Enhanced PDU (LCD Screen)
Using the metering unit's LCD screen, you can monitor how much power and current the
equipment attached to the PDU uses, as well as the voltage level powering the equipment.
1.
Locate the PDU you want to monitor in the rack.
You might need to open the rack's rear door to access the PDU.
2.
Locate the metering unit on the PDU.
You can find the metering unit in the middle of the PDU.
3.
Check the metering unit's LCD screen to view the current, voltage, and power
being used by the equipment connected to each PDU input.
The LCD screen displays the current measurements of all of the phases of each PDU input.
See “Understanding the Relationship Between Inputs and Outlet Groups” on page 105 for a
description of PDU inputs.
114
■
Press the Select Attribute button to select the parameter displayed.
■
If your PDU has more than one input, press the Select Input button to cycle
through the available inputs.
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitor the Enhanced PDU (HTML Interface)
■
For easier viewing, you can rotate the screen in 90-degree intervals by
pressing the Select Attribute button for longer than 1 second. See “Adjust
the LCD Screen (Enhanced PDU)” on page 136 for more information.
No.
Description
1
Input number
2
Attribute current, voltage or power
3
Measured value being used by the
equipment connected to the PDU phase
Monitor the Enhanced PDU (HTML Interface)
Using the metering unit's HTML interface, you can monitor how much power, energy, and
current the equipment attached to the PDU uses, as well as the voltage level powering the
equipment. The reported voltage for 3ph PDUs is L-N for HV PDUs and L-G for LV PDUs.
The reported voltage for 1ph PDUs is L-N for HV PDUs and L-L for LV PDUs. You can
see how the current and voltage readings relate to the threshold parameters you set in “Set
Threshold Parameter Values (Enhanced PDU)” on page 111.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110. After
accessing the PDU, the Metering Overview page displays.
2.
View the Metering Overview page.
Monitoring Enhanced PDUs
115
Monitor the Enhanced PDU (HTML Interface)
The following figure shows an example Metering Overview page for a 24kVA PDU, which has
two inputs with three phases each. See “Understanding the Relationship Between Inputs and
Outlet Groups” on page 105 for a description of PDU inputs.
The following figure displays the details of the current measurement of an example single PDU
input.
116
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitor the Enhanced PDU (HTML Interface)
No.
Description
1
PDU input number
2
Phase number
3
State
4
Graph displaying the amps of current being used per phase
5
Number of amps of current being used per phase
6
Voltage level applied per phase†
7
Amount of active power being used per phase
8
Amount of apparent power being used per phase
9
Energy level being used per phase
†
The reported voltage for 3ph PDUs is L-N for HV PDUs and L-G for LV PDUs. The reported voltage for 1ph PDUs is L-N for HV PDUs
and L-L for LV PDUs.
The black vertical bar indicates the current used by the attached equipment. The color behind
the line is determined by the threshold parameter values. If you set voltage threshold parameter
values, the background of the voltage color indicates the state of the voltage powering the
equipment. For more information on threshold limits, see “Set Threshold Parameter Values
(Enhanced PDU)” on page 111.
Note - The Enhanced PDU supports both, 10/100 Full Duplex and 10/100 Half Duplex as well
as auto-negotiation as defined in IEEE802.3u. If the switch port supports auto-negotiation the
Enhanced PDU will configure itself to the fastest speed supported by the switch. If a specific
mode of operation is needed the switch port needs to be configured to the specific mode of
operation.
Color
Value
Description
Blue
Measured current is below Info threshold.
Attached equipment is using less current
than expected.
Green
Measured current is between the Info and Warning
thresholds.
Attached equipment is using the
expected amount of current.
Yellow
Measured current is above the Warning threshold,
but below the Alarm threshold.
Attached equipment is using more
current than expected.
Red
Measured current is above the Alarm threshold.
Attached equipment is using a critical
amount of current and requires
immediate attention.
Flashing bar with
red text
Measured current is above the Out of Balance
threshold. Also, a blinking red “Out of Balance”
message displays above the input graph.
The equipment attached to one phase is
using more current than the other phases
on the input. The PDU and attached
equipment require immediate attention.
Monitoring Enhanced PDUs
117
Monitor the Enhanced PDU (RS-232)
Caution - If the PDU is out of balance, the PDU and the attached equipment might heat up and
cause serious damage to the equipment, PDU, and the rack. Power off the equipment and the
PDU immediately.
If you set voltage thresholds parameter values, the background of the voltage color indicates the
state of the voltage powering the equipment. See the following table for a description of these
colors.
Color
Value
Description
Green
Measured Voltage is above Warning threshold.
Attached equipment is operating with an
expected voltage level.
Yellow
Measured Voltage is between Warning and Alarm
threshold.
Attached equipment is operating at an
allowable voltage level.
Red
Measured Voltage is below Alarm threshold.
Attached equipment might not operate as
expected.
Caution - If the PDU input voltage is below the Alarm level, the attached equipment (and PDU)
might be damaged. Power off the equipment and PDU immediately.
Monitor the Enhanced PDU (RS-232)
Using the metering unit's RS-232, you can monitor how much power, energy, and current the
equipment attached to the PDU uses, as well as the voltage level powering the equipment.
1.
Connect an RS-232 cable between the SER MGT port and the host.
2.
Configure the host's terminal or terminal emulator with settings.
See “Terminal Configuration Settings” on page 72.
3.
When prompted, log in as an admin or user.
See “Login Information” on page 71.
4.
Familiarize yourself with the command options.
See “Understanding CLI Commands” on page 145.
118
Sun Rack II Power Distribution Units User's Guide • December 2016
Monitor the Enhanced PDU (SSH)
Monitor the Enhanced PDU (SSH)
Using the metering unit's SSH interface, you can monitor the power, energy, and current being
used by equipment attached to the PDU and voltage powering the equipment.
1.
Connect an Ethernet cable between the NET MGT and the host.
2.
Configure the SSH application with the PDU IP address.
3.
When prompted, log in as an admin or user.
See “Login Information” on page 71.
4.
Familiarize yourself with CLI command options.
See “Understanding CLI Commands” on page 145.
Changing Interface Settings (Enhanced PDU)
The HTML interface allows you to name a PDU, assign new users, and send system log
messages to systems on the network.
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
■
■
■
“Set the PDU Information (Enhanced PDU)” on page 119
“Add Users and Change Passwords (Enhanced PDU)” on page 120
“Send System Log Messages to Systems on the Network (Enhanced PDU)” on page 121
Set the PDU Information (Enhanced PDU)
It is a good practice to name the PDU you are monitoring, especially if your network contains
multiple racks and PDUs. Besides the name, you can set the location of the PDU, Product
Identification, and serial number of the rack in which the PDU is installed. When set, the name
and location are displayed on the top of each HTML page.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
Monitoring Enhanced PDUs
119
Add Users and Change Passwords (Enhanced PDU)
3.
Select the PDU Information tab.
4.
Provide a name, product identifier, rack serial number, and location for the PDU.
The setting cannot exceed the following number of characters:
Setting
Characters
Name
32 maximum
Product identifier
40 maximum
Rack serial number
18 maximum
Location
32 maximum
5.
Click the Submit button to set the PDU name and location.
6.
Click your web browser Reload or Refresh button to view the updated PDU name
and location.
Add Users and Change Passwords (Enhanced
PDU)
You can set up to five PDU users, including the admin user.
See “Login Information” on page 71.
120
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as admin.
See “Login Information” on page 71.
3.
Select the HTTP-Access tab.
4.
Add up to five users.
Sun Rack II Power Distribution Units User's Guide • December 2016
Send System Log Messages to Systems on the Network (Enhanced PDU)
Type in a name and password for each user, re-enter the password for each user, and designate
the user as an admin or a user. If you change the admin user name or password, write the name
and password down and save it in a secure location.
Note - Starting with FW 2.02, the username requires six characters and the password requires a
minimum of eight characters.
5.
Setting
Characters (ISO - 8859-1)
UserName
Uppercase Letters, Lowercase Letters, and Numbers
Password
Uppercase Letters, Lowercase Letters, Numbers, and Special Characters (!,
“, #, $, %, &, ???, (, ), *, +, -, @)
Click the Submit button to set the PDU users and passwords.
Send System Log Messages to Systems on the
Network (Enhanced PDU)
You can set the PDU to send system log (syslog) messages to up to four systems on the
network. syslog is the standard UNIX system logging utility, which monitors critical system
events and configuration changes. These syslog messages are sent to the systems using user
datagram protocol (UDP) port 514.
For more information about syslog, refer to the Oracle Solaris documentation and the
syslogd(1M) and syslog.conf(4) man pages.
Monitoring Enhanced PDUs
121
Send System Log Messages to Systems on the Network (Enhanced PDU)
Example PDU syslog message:
Lines IN0: L1: 0.96kW 0.96kVA 8.02A 120.0V L2: 0.47kW 0.56kVA 4.65A 121.6V L3: 0.50kW 0.56kVA
4.66A 121.1V
Lines IN1: L1: 0.93kW 0.93kVA 7.75A 120.0V L2: 0.47kW 0.55kVA 4.59A 121.6V L3: 0.47kW 0.53kVA
4.44A 121.1V
Inputs: IN0: 1.93kW IN1: 1.88kW
PDU: 3.82kW
In the example, Lines IN0: L1: 0.96kW 0.96kVA 8.02A 120.0V, is a message for Input 0,
Phase 1. The PDU is consuming 8.02A, 0.96 kVA, and 0.96kW with 120.0V applied.
Inputs: IN0: 1.93kW, displays the message of the power consumed by Input 0.PDU: 3.82kW,
displays the message of the power consumed by the PDU.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
3.
122
Select the Syslog tab.
Sun Rack II Power Distribution Units User's Guide • December 2016
Send System Log Messages to Systems on the Network (Enhanced PDU)
Note - This screenshot applies only to FW version 2.01, not FW version 2.02. The syslog and
reset functionalities are not available in FW version 2.02.
4.
For FW version 2.01, click the Syslog Enable checkbox to enable remote syslog
message logging, then click the Submit button.
Note - This step is no longer required beginning with FW version 2.02.
5.
Type in up to four IP addresses and click the enable box next to the IP address
of systems you want the metering unit to send syslog messages, then click the
Submit button below the IP addresses.
6.
Set the time duration between sending syslog messages.
Valid time settings include:
■
Hours: 0 - 23
■
Minutes: 0 - 59
■
Seconds: 0 - 59
Monitoring Enhanced PDUs
123
Enabling and Configuring SNMP (Enhanced PDU)
For example, if you set the duration for 12 hours, the PDU sends syslog messages every 12
hours.
7.
Click the Alarms checkbox to send alarm messages over syslog messages.
If checked, and if you set threshold parameter values (see “Set Threshold Parameter Values
(Enhanced PDU)” on page 111), the metering unit sends alarm messages when threshold
parameter values are reached.
Possible syslog alarm messages are shown in “Enabling and Configuring SNMP (Enhanced
PDU)” on page 124.
8.
Click the Submit button to enable these syslog settings.
9.
Select values to be sent to syslog systems then click the Submit button to
enable.
Enabling and Configuring SNMP (Enhanced PDU)
The PDU metering unit supports Simple Network Management Protocol (SNMP). SNMP
provides the ability to send traps, or notifications, when one or more conditions have been met.
If you enable SNMP, the metering unit can send and receive traps to and from SNMP agents on
the network.
Note - These sections do not describe how to view SNMP trap information using an SNMP
agent. Refer to your SNMP agent documentation for details on how to use it to view SNMPbased information.
■
■
■
“Types of PDU Metering Unit SNMP Traps (Enhanced PDU)” on page 124
“Enable and Configure SNMP (Enhanced PDU)” on page 125
“Configure SNMP Traps” on page 127
Types of PDU Metering Unit SNMP Traps
(Enhanced PDU)
The following table describes the SNMPv2 traps the metering unit can send to SNMP agents on
the network (over UDP port 162). In the trap descriptions, InputNum/LineNum corresponds to
the input number and line number of the PDU (for example, Input1/Line2).
Note - The InputNum for SNMP Traps start at 1, not 0.
124
Sun Rack II Power Distribution Units User's Guide • December 2016
Enable and Configure SNMP (Enhanced PDU)
SNMP Trap
SNMP Notification
Description
Keep alive
KeepAlive-Trap
The PDU sends a KeepAlive-Trap message
to the SNMP host to ensure that the link
between them is operational.
Dead
Dead-Trap
Sent after a PDU power cycle.
Current Info
Info-Trap on InputNum/LineNum
Attached equipment is using less current than
expected.
Current Warning
Warning-Trap on InputNum/LineNum
Attached equipment is using more current
than expected.
Current Alarm
Alarm-Trap on InputNum/LineNum
Attached equipment is using a critical amount
of current and requires immediate attention.
Current Out of balance
OutOfBalance-Trap on InputNum/LineNum
The equipment attached to one phase is using
more current than the other phases on the
input. The PDU and attached equipment
require immediate attention.
Current Return to
normal
ReturnToNormal-Trap on InputNum/LineNum
After sending an alarm trap, the attached
equipment has returned to using the expected
amount of current.
Voltage Warning
Warning-Trap on InputNum/LineNum
Attached equipment is operating with
undesired but acceptable voltage level.
Voltage Alarm
Alarm-Trap on InputNum/LineNum
Attached equipment is operating with an
unacceptable voltage level.
Voltage return to
normal
ReturnToNormal-Trap on InputNum/LineNum
Attached equipment is operating with an
expected voltage level.
Enable and Configure SNMP (Enhanced PDU)
Use the HTML interface to enable SNMP, NMS community hosts, and SNMP users.
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
Monitoring Enhanced PDUs
125
Enable and Configure SNMP (Enhanced PDU)
3.
Select the SNMP-Access tab.
4.
Click the SNMP v1/v2, or v3 Enable checkbox to enable SNMP.
If desired, you can disable HTTP access to the PDU by deselecting the HTTP enable checkbox
on the HTTP-Access tab of the Net Configuration page.
126
Sun Rack II Power Distribution Units User's Guide • December 2016
Configure SNMP Traps
Caution - If you disable HTTP, you are no longer be able to log in to the HTML interface
using a web browser. To re-enable HTTP access, you can use your SNMP agent software.
Refer to the SNMP agent documentation or the Oracle Solaris snmpset(1M) man page for
more information. You can also use the CLI command to re-enable HTTP, pducli -> set
net_web_version=1 or 2 (1 for HTTP, 2 for HTTPS.).
5.
Select the appropriate MIB and click submit.
The enhanced PDU is the default MIB setting.
6.
Define up to four NMS hosts on the network for SNMP v1/v2 then click submit.
A network management station (NMS) host runs network management applications that
monitor and control SNMP-managed devices. NMS hosts provide the resources required for
network management.
7.
Define up to 10 SNMP v3 users then click submit.
For each user select security level, auth algorithm, privacy algorithm, access type, and then
check the enable box to enable this user.
See Step 4 in “Add Users and Change Passwords (Enhanced PDU)” on page 120.
Configure SNMP Traps
Use the HTML interface to specify SNMP trap hosts, trap options, and test trap configurations.
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
1.
Access the PDU metering unit from a system on the network.
Monitoring Enhanced PDUs
127
Configure SNMP Traps
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
3.
Select the SNMP-Traps tab.
4.
Define up to ten SNMP trap hosts then click submit.
Once configured, the Metering unit sends SNMP traps to the hosts that are enabled. For each
host enter the IP address or host name and community name. Select the SNMP trap version and
check the enable box for traps to be sent to this host. If v3 SNMP traps are selected, select the
user associated with this host.
5.
Provide values to the repeating trap settings.
Here is a description of these repeating trap settings.
6.
128
Setting
Description
Permitted
Values
KeepAlive Trap
The number of seconds between repeating the KeepAlive
trap.
0 - 60
Repeating Time for Traps
The number of seconds between sending trap messages to
SNMP hosts.
0 - 60
Number of traps
The number of times the same trap can repeated to the same
host.
0 -255
Click the Submit button to enable these SNMP settings.
Sun Rack II Power Distribution Units User's Guide • December 2016
Verifying and Updating the Firmware (Enhanced PDU)
7.
Send a test trap to verify the SNMP settings.
Verifying and Updating the Firmware (Enhanced PDU)
The PDU metering input contains firmware that operates the LCD screen and provides the
HTML interface. This firmware might be updated in the future to correct issues and provide
new functionality.
■
■
■
“View Module Information (Enhanced PDU)” on page 129
“Update the PDU Metering Unit Firmware (HTML)” on page 130
“Update the PDU Metering Unit Firmware (SSH)” on page 131
View Module Information (Enhanced PDU)
Before downloading any new firmware, confirm the firmware revision level currently running
on the PDU metering unit.
1.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Module Info link to verify the firmware revision level, as well as
other information, on the Module Info page.
Monitoring Enhanced PDUs
129
Update the PDU Metering Unit Firmware (HTML)
Update the PDU Metering Unit Firmware (HTML)
You can download updates of the PDU metering unit firmware from the My Oracle Support
(MOS) web site.
Note - Updating the firmware does not overwrite any configurations you set previously.
1.
Using a web browser, connect to the MOS web site:
https://myoraclesupport.com
2.
Locate and download the latest version of the firmware.
To locate the latest PDU firmware, search the Download Center for the Sun Rack II. Follow the
instructions on the web site to download the firmware.
3.
Save the downloaded firmware ZIP file to a directory accessible to the PDU over
the network.
4.
Use the unzip command to extract the metering unit firmware from the
downloaded ZIP file.
The downloaded ZIP file contains one update file:
■
MKAPP_Vx.x.dl – metering unit firmware
If the ZIP file also contains a text file, review it for any additional information about the
firmware updates.
5.
Access the PDU metering unit from a system on the network.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
6.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
130
7.
Select the Firmware-Update tab.
8.
Click on the Browse button and locate the MKAPP_Vx.x.dl file you downloaded
previously.
Sun Rack II Power Distribution Units User's Guide • December 2016
Update the PDU Metering Unit Firmware (SSH)
9.
10.
Click the Submit button update the metering unit firmware.
Confirm that you updated the firmware successfully.
See “View Module Information (Enhanced PDU)” on page 129 for instructions on viewing
the firmware revision level.
Update the PDU Metering Unit Firmware (SSH)
1.
Using a web browser, connect to the MOS web site:
https://myoraclesupport.com
2.
Locate and download the latest version of the firmware.
To locate the latest PDU firmware, search the Download Center for the Sun Rack II. Follow the
instructions on the web site to download the firmware.
3.
Save the downloaded firmware ZIP file to a directory accessible to the PDU over
the network.
4.
Use the unzip command to extract the metering unit firmware from the
downloaded ZIP file.
The downloaded ZIP file contains one update file:
■
MKAPP_Vx.x.dl – metering unit firmware
If the ZIP file also contains a text file, review it for any additional information about the
firmware updates.
5.
Using an appropriate SSH application, execute the following command.
scp MKAPP_Vx.x.dl [email protected]:Firmware.dl
xxx.xxx.xxx.xxx = PDU ipaddr
6.
When prompted, enter the admin password.
See “Login Information” on page 71.
7.
When finished, the PDU will reboot and disconnect from the SSH application.
8.
Confirm that you updated the firmware successfully.
See “View Module Information (Enhanced PDU)” on page 129.
Monitoring Enhanced PDUs
131
Administering the PDU Metering Unit (Enhanced PDU)
Administering the PDU Metering Unit (Enhanced PDU)
Besides monitoring the power, energy, and current of attached equipment and the voltage
powering the equipment, you can reboot the PDU, view information about the network
connection and firmware revisions, set the time, check events, and adjust the LCD screen.
■
■
■
■
■
■
■
■
■
“Reset the Enhanced PDU Metering Unit (Reset Button)” on page 133
“Reboot the Enhanced PDU Metering Unit (LCD)” on page 133
“Reboot the Enhanced PDU Metering Unit (HTML)” on page 133
“Reboot the Enhanced PDU Metering Unit (RS-232)” on page 134
“Reboot the Enhanced PDU Metering Unit (SSH)” on page 135
“View Status Information on the LCD Screen (Enhanced PDU)” on page 135
“Adjust the LCD Screen (Enhanced PDU)” on page 136
“Set the PDU System Time” on page 137
“Access the Event Logging Page” on page 138
Note - Restarting the metering unit does not power cycle equipment attached to the PDU.
132
Sun Rack II Power Distribution Units User's Guide • December 2016
Reset the Enhanced PDU Metering Unit (Reset Button)
Reset the Enhanced PDU Metering Unit (Reset
Button)
Press the Reset button with a paper clip.
Reboot the Enhanced PDU Metering Unit (LCD)
1.
Press and hold the buttons for 10 seconds until you see a five-second
countdown displayed on the LCD screen.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
During the five-second countdown, release the buttons and then tap the buttons
again to reboot the PDU.
Reboot the Enhanced PDU Metering Unit (HTML)
1.
Log in to the PDU metering unit.
Monitoring Enhanced PDUs
133
Reboot the Enhanced PDU Metering Unit (RS-232)
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
3.
Select the StartUp/Reset heading.
4.
Click the Submit button next to the Restart PDU to reboot the PDU Monitoring
Unit.
Reboot the Enhanced PDU Metering Unit (RS-232)
1.
Connect an RS-232 cable between the SER MGT port and the host.
2.
Configure the host's terminal or terminal emulator.
See “Terminal Configuration Settings” on page 72.
3.
When prompted, log in as admin.
Welcome to Oracle PDU <host name>
pducli -> username:
pducli -> password:
See “Login Information” on page 71.
4.
After successful login, type.
pducli -> reset=yes
134
Sun Rack II Power Distribution Units User's Guide • December 2016
Reboot the Enhanced PDU Metering Unit (SSH)
Reboot the Enhanced PDU Metering Unit (SSH)
1.
Connect an Ethernet cable between the NET MGT and the host.
2.
Configure the SSH application with the PDU IP Address.
3.
When prompted, log in as admin.
See “Login Information” on page 71.
4.
After successful login, type.
pducli -> reset=yes
View Status Information on the LCD Screen
(Enhanced PDU)
When the PDU metering unit resets or powers on, you can view network and firmware version
level information on the LCD screen.
Press the Select Attribute button until the PDU information appears.
The screen displays the following information:
HW: x.x FW:x.x
DHCP: OFF (or ON)
MAC: xx-xx-xx-xx-xx-xx
Monitoring Enhanced PDUs
135
Adjust the LCD Screen (Enhanced PDU)
IP: xxx.xxx.xxx.xxx
SUB:xxx.xxx.xxx.xxx
GATW:xxx.xxx.xxx.xxx
DNS: xxx.xxx.xxx.xxx
The following table describes the LCD screen information.
LCD Text
Description
HW
Version of the PDU hardware.
FW
Version of the PDU firmware.
DHCP
Displays ON, when DHCP is enabled, and OFF when DHCP is disabled. See “Connect an
Original PDU to a DHCP Network” on page 54 for more information about DHCP.
MAC
MAC address of the metering unit.
IP
IP address of the metering unit.
■ If DHCP is OFF, the IP address is an internally stored static address.
■ If DHCP is ON, the IP address is set by the DHCP server.
SUB NET MASK
IP subnet netmask.
GATEWAY
IP address of the gateway router.
DNS
IP address of the DNS server of the metering unit.
Adjust the LCD Screen (Enhanced PDU)
You can adjust the LCD screen orientation and background to help you view the screen within
the rack.
Press and hold the Select Attribute button until the LCD screen rotates 90
degrees.
Continue to press and release the Select Attribute button to cycle through different LCD screen
orientations. The first four screens have black text on a white background, while the other four
136
Sun Rack II Power Distribution Units User's Guide • December 2016
Set the PDU System Time
have white text on a black background. The final selected screen becomes the new default
orientation.
Set the PDU System Time
Use the HTML interface to set the PDU time and configure the NTP server.
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
1.
Log in to the PDU metering unit.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
Monitoring Enhanced PDUs
137
Access the Event Logging Page
3.
Select the System Time tab.
4.
Enter the current date and time and click submit.
5.
If necessary for your location, enable daylight saving time and click submit.
Note - Enabling daylight saving time will add an hour to the previously set time. The time will
not automatically return to standard time when daylight saving time ends. Disable this setting
once Daylight Saving Time ends for your location.
6.
Configure the NTP server and click submit.
Note - If the NTP is not enabled, rebooting the PDU resets the date to 1970 January 1.
Access the Event Logging Page
Use the HTML interface to review the last 1,000 events.
1.
Log in to the PDU metering unit.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
138
Sun Rack II Power Distribution Units User's Guide • December 2016
Restoring the PDU to Factory Default Settings (Enhanced PDU)
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
3.
Select the EventLogging tab.
Restoring the PDU to Factory Default Settings (Enhanced
PDU)
If you need to correct a configuration error, or you want to clear the PDU before moving it to a
different rack, you can restore the PDU metering unit back to its factory settings.
After restoring the unit, all network and configuration settings reset back to their default
values (for example, admin is the only user and the IP address returns to 0.0.0.0 with DHCP
enabled). All settings that you set for your environment are lost.
Note - After restoring the PDU metering unit back to its factory settings, you must reconnect it
to the network. See “Connecting Standard PDUs to the Network” on page 53 for instructions.
■
“Restore the PDU to Factory Default Settings (LCD)” on page 140
■
“Restore the PDU to Factory Default Settings (HTML)” on page 140
“Restore the PDU to Factory Default Settings (RS-232)” on page 141
“Restore the PDU to Factory Default Settings (SSH)” on page 141
■
■
Monitoring Enhanced PDUs
139
Restore the PDU to Factory Default Settings (LCD)
Restore the PDU to Factory Default Settings (LCD)
You can restore the PDU to factory default settings using the two buttons on the LCD.
1.
Press and hold the buttons for 10 seconds until you see a five-second
countdown displayed on the LCD screen.
2.
During the five-second countdown, release the buttons and then press and hold
the buttons.
The countdown continues.
3.
At the end of the five-second countdown, a ten-second countdown starts,
prompting you to hold the buttons until it completes.
4.
At the end of the ten-second countdown, a second five-second countdown is
displayed on the LCD screen.
5.
During the second five-second countdown, release the buttons and then tap the
buttons again to force the PDU to reset to factory defaults.
Restore the PDU to Factory Default Settings
(HTML)
1.
Log in to the PDU metering unit.
See “Access a Metering Unit on the Network (Enhanced PDU)” on page 110.
2.
Click on the Net Configuration link and log in as an admin user.
See “Login Information” on page 71.
3.
140
Select StartUp/Reset heading.
Sun Rack II Power Distribution Units User's Guide • December 2016
Restore the PDU to Factory Default Settings (RS-232)
Note - Screenshots with the reset functionality are from FW version 2.01. The reset
functionality is not available beginning with FW version 2.02.
4.
Click the Submit button to restore the PDU metering unit back to its default
factory settings.
Restore the PDU to Factory Default Settings (RS232)
1.
Connect an RS-232 cable between the SER MGT port and the host.
2.
Configure the host's terminal or terminal emulator.
See “Terminal Configuration Settings” on page 72.
3.
When prompted, log in as an admin user.
See “Login Information” on page 71.
4.
After successful login, type.
pducli -> factory_default=yes
Restore the PDU to Factory Default Settings (SSH)
1.
Connect an Ethernet cable between the NET MGT and the host.
2.
Configure the SSH application with the PDU IP address.
3.
When prompted, log in as an admin user.
Monitoring Enhanced PDUs
141
NET MGT Port LED and Pin Descriptions
See “Login Information” on page 71.
4.
After successful login, type.
pducli -> factory_default=yes
NET MGT Port LED and Pin Descriptions
Pin
Signal Description
Pin
Signal Description
1
Transmit+ (TX+)
6
Receive- (RX-)
2
Transmit- (TX-)
7
Not used
3
Receive+ (RX+)
8
Not used
4
Not used
9
Activity LED – flashes when network data is
being transmitted through the port
5
Not used
10
Link LED – lights when the unit is connected
to a network
SER MGT Ports and Pin Descriptions
The SER MGT RJ-45 port, provides an TIA/EIA-232 serial Oracle/Cisco standard connection
to the SP. This port is the default connection to the Oracle ILOM system controller. For DTE
to DTE communications, you can use the supplied RJ-45 to DB-9 crossover adapter with a
standard RJ-45 cable to achieve the required null modem configuration.
142
Sun Rack II Power Distribution Units User's Guide • December 2016
SER MGT Ports and Pin Descriptions
Pin
Signal Description
Pin
Signal Description
1
Request to Send
5
Ground
2
Data Terminal Ready
6
Receive Data
3
Transmit Data
7
Data Set Ready
4
Ground
8
Clear to Send
Monitoring Enhanced PDUs
143
144
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding CLI Commands
This chapter contains information about user and administrator commands.
■
■
■
“Help Commands” on page 145
“Understanding User and Administrator Commands” on page 146
“Understanding Administrator-Only Commands” on page 150
Help Commands
After successful login, you can use different commands at the CLI prompt.
Starting with FW 2.02, typing help or ? at the command prompt provides a list of covered
topics. The list of covered topics might be different between firmware releases.
pducli -> help
<list of provided topics based on firmware version>
TABLE 16
List of Covered Topics for the help Command
Topics
Syntax
PDU-SystemInfo
pducli -> help PDU-SystemInfo
NetworkServices
pducli -> help NetworkServices
NetworkPorts
pducli -> help NetworkPorts
IPv4-Configuration
pducli -> help IPv4-Configuration
IPv6-Configuration
pducli -> help IPv6-Configuration
Host-Configuratoin
pducli -> help Host-Configuration
User-Configuration
pducli -> help User-Configuration
SystemTime
pducli -> help SystemTime
PowerInfo (Total PDU)
pducli -> help PowerInfo (Total PDU)
PowerInfo (Inputs)
pducli -> help PowerInfo (Inputs)
PowerInfo (Lines)
pducli -> help PowerInfo (Lines)
Understanding CLI Commands
145
Understanding User and Administrator Commands
Topics
Syntax
PDU-EventList
pducli -> help PDU-EventList
Each topic contains a list of valid commands for the PDU. To get a list of valid commands for a
topic, type:
pducli -> help topic- name
Note - Some commands are restricted to accounts with admin privileges only.
To get help on a specific command, type:
pducli -> help command-name
This command provides information on how to use the command in the format:
pducli -> help command-name parameter value <(if applicable)>
Understanding User and Administrator Commands
These topics describe commands for users and administrators.
■
■
■
■
■
“User and Administrator Commands” on page 146
“PDU System Information Parameters (get Command)” on page 147
“Power Information Parameters” on page 147
“Input Parameters” on page 148
“Line Parameters” on page 149
User and Administrator Commands
TABLE 17
User and Administrator Commands
Command
Syntax
Description
get
pducli -> get Params
Gets PDU specific configuration and measurement parameters.
set
pducli -> set Params=Values
Sets PDU specific configuration and measurement parameters.
exit
pducli -> exit
Exits the CLI and returns to the login prompt.
146
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding User and Administrator Commands
PDU System Information Parameters (get
Command)
TABLE 18
PDU System Information Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pdu_name
pducli -> get pdu_name
pducli -> pdu_name=xxxx
pdu_product_id
pducli -> get pdu_product_id
pducli-> pdu_product_id=xxxxx
pdu_rack_serial_number
pducli -> get pdu_rack_serial_number
pducli-> pdu_rack_serial_number=xxxxx
pdu_location
pducli -> get pdu_location
pducli-> pdu_location=xxxxx
pdu_part_number
pducli -> get pdu_part_number
pducli-> pdu_part_number=xxxxx
pdu_serial_number
pducli -> get pdu_serial_number
pducli-> pdu_serial_number=xxxxx
pdu_date_of_manufacture
pducli -> get pdu_date_of_manufacture
pducli-> pdu_date_of_manufacture=xxxxx
pdu_product_description
pducli -> get pdu_product_description
pducli-> pdu_product_description=xxxxx
pdu_hardware_version
pducli -> get pdu_hardware_version
pducli-> pdu_hardware_version=xxxxx
pdu_firmware_version
pducli -> get pdu_firmware_version
pducli-> pdu_firmware_version=xxxxx
pdu_bootloader_version
pducli -> get pdu_bootloader_version
pducli-> pdu_bootloader_version=xxxxx
pdu_mac_address
pducli -> get pdu_mac_address
pducli-> pdu_mac_address=xxxxx
pdu_display_info_time
pducli -> get pdu_display_info_time
pducli-> pdu_display_info_time=xxxxx (with
xxxx in seconds)
pdu_web_gui_refresh_interval
pducli -> get
pducli-> pdu_web_gui_refresh_interval=xx
(with xx in seconds, 1-60 allowed)
pdu_web_gui_refresh_interval
Power Information Parameters
TABLE 19
Power Info on the Total PDU Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
pwr_power_system
pducli -> get pwr_power_system
pducli-> pwr_power_system=EU (or
pwr_power_system=US)
pwr_total_pdu_power
pducli -> get pwr_total_pdu_power
pducli-> pwr_total_pdu_power=xxxxW
pwr_total_pdu_energy
pducli -> get pwr_total_pdu_energy
pducli-> pwr_total_pdu_energy=xxxxWh
pwr_total_pdu_max_load
pducli -> get pwr_total_pdu_max_load
pducli-> pwr_total_pdu_max_load=xxxxVA
pwr_total_pdu_load
pducli -> get pwr_total_pdu_load
pducli-> pwr_total_pdu_load=xxx%
TABLE 20
Power Info on the Total PDU Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
power_total_pdu_energy
pducli -> set power_total_pdu_energy=0 (only
0 allowed for clear energy)
pducli-> set OK (or an error message)
Understanding CLI Commands
147
Understanding User and Administrator Commands
Input Parameters
TABLE 21
Input Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
pwr_input_power
pducli -> get pwr_input_power.x
pducli-> pwr_input_power.x=yyyyW
pwr_input_energy
pducli -> get pwr_input_energy.x
pducli-> pwr_input_energy.x=yyyyWh
pwr_input_max_load
pducli -> get pwr_input_max_load.x
pducli-> pwr_input_max_load.x=yyyyVA
pwr_input_load
pducli -> get pwr_input_load.x
pducli-> pwr_input_load.x=yyy%
Note - Replace x with the input number (0 to 5).
TABLE 22
Input Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pwr_input_outofbalance
pducli -> get pwr_input_outofbalance.x
pducli-> pwr_input_outofbalance.x=yyya
(x=input number)
(yyy=OutOfBalance Current in [A] for input x)
pducli -> get
pducli->
pwr_input_outofbalance_
threshold_alarm
pwr_input_outofbalance_
trap_enable
TABLE 23
pwr_input_outofbalance_threshold_alarm.x pwr_input_outofbalance_threshold_alarm.x=yyya
(x=input number)
(yyy=OutOfBalance-AlarmThreshold in [A] for input
x)
pducli -> get
pwr_input_outofblance_trap_enable.x
pducli->
pwr_input_outofbalance_trap_enable.x=On
(x=input number)
(Or Off for input x)
Inputs Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
power_input_energy
pducli -> set power_input_energy.x=0
pducli-> set OK (or an error message)
(Only 0 allowed for clear energy)
pwr_input_outofbalance_
threshold_alarm
pducli -> set
pducli-> set OK (or an error message)
pwr_input_outofbalance_threshold_alarm.
x=yyy
(yyy=OutOfBalance-alarmThreshold in [A] for
input x)
pwr_input_outofbalance_trap_pducli -> set
enable
pwr_input_outofbalance_trap_enable.x=On
(Or Off for input x)
148
Sun Rack II Power Distribution Units User's Guide • December 2016
pducli-> set OK (or an error message)
Understanding User and Administrator Commands
Line Parameters
TABLE 24
Line Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
pwr_line_current
pducli -> get pwr_line_current.x.y
pducli-> pwr_line_current.x.y=zzzzA
pwr_line_voltage
pducli -> get pwr_line_voltage.x.y
pducli-> pwr_line_voltage.x.y=zzzzV
pwr_line_power
pducli -> get pwr_line_power.x.y
pducli-> pwr_line_power.x.y=zzzzW
pwr_line_energy
pducli -> get pwr_line_energy.x.y
pducli-> pwr_line_energy.x.y=zzzzWh
pwr_line_max_load
pducli -> get pwr_line_max_load.x.y
pducli-> pwr_line_max_load.x.y=zzzzVA
pwr_line_load
pducli -> get pwr_line_load.x.y
pducli-> pwr_line_load.x.y=zzz%
Note - Replace x with the input number (0 to 5) and y with the line number (1 to 3).
TABLE 25
Line Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
pwr_line_apparent_power pducli -> get
Response
pducli-> pwr_line_apparent_power.x.y=zzzzVA
pwr_line_apparent_power.x.y
pwr_line_currrent_
threshold_info
pducli -> get
pwr_line_currrent_
threshold_warning
pducli -> get
pwr_line_currrent_
threshold_alarm
pducli -> get
pwr_line_current_threshold_alarm.x.y
pducli->
pwr_line_current_threshold_alarm.x.y=zzzA
pwr_line_voltage_
threshold_warning
pducli -> get
pducli->
pwr_line_voltage_
threshold_alarm
pducli -> get
pwr_line_trap_enable
pducli -> get pwr_line_trap_enable.x.y
pducli-> pwr_line_current_threshold_info.x.y=zzzA
pwr_line_current_threshold_info.x.y
pducli->
pwr_line_current_threshold_warning.x.y pwr_line_current_threshold_warning.x.y=zzzA
pwr_line_voltage_threshold_warning.x.y pwr_line_voltage_threshold_warning.x.y=zzzV
pwr_line_voltage_threshold_alarm.x.y
pducli->
pwr_line_voltage_threshold_alarm.x.y=zzzV
pducli-> pwr_line_trap_enable.x.y=On (or Off for
input x, line y)
Note - Replace x with the input number (0 to 5) and y with the line number (1 to 3).
TABLE 26
Line Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pwr_line_energy
pducli -> set pwr_line_energy.x.y=0 (only 0
allowed for clear energy for input x, line y)
pducli-> set OK (or an error message)
pwr_line_current_threshold_ pducli -> set
info
pwr_line_current_threshold_info.x.y=zzz
pducli-> set OK (or an error message)
Understanding CLI Commands
149
Understanding Administrator-Only Commands
Parameters
Syntax
Response
(zzz=Current-InfoThreshold in [A] for input x,
line y)
pducli-> set OK (or an error message)
pducli -> set
pwr_line_current_
threshold_warning
pwr_line_current_threshold_warning.x.y=zzz
(zzz= Current-WarningThreshold in [A] for input x,
line y)
pducli-> set OK (or an error message)
pducli -> set
pwr_line_current_
threshold_alarm
pwr_line_current_threshold_alarm.x.y=zzz
(zzz= Current-AlarmThreshold in [A] for input x,
line y)
pducli-> set OK (or an error message)
pducli -> set
pwr_line_voltage_
threshold_warning
pwr_line_voltage_threshold_warning.x.y=zzz
(zzz= Voltage-WarningThreshold in [A] for input x,
line y)
pducli-> set OK (or an error message)
pducli -> set
pwr_line_voltage_
threshold_alarm
pwr_line_voltage_threshold_alarm.x.y=zzz
(zzz= Voltage-AlarmThreshold in [V] for input x,
line y)
pwr_line_trap_enable
pducli -> set pwr_line_trap_enable.x.y=On
(or Off for input x, line y)for input x, line y)
pducli-> set OK (or an error message)
Understanding Administrator-Only Commands
■
■
■
■
■
■
■
■
■
■
“Administrator-Only Commands” on page 150
“PDU System Information Parameters (set Command)” on page 151
“Network Services Configuration Parameters” on page 151
“Network Ports Configuration Parameters” on page 154
“IPv4 Configuration Parameters” on page 154
“IPv6 Configuration Parameters” on page 155
“PDU Events List Parameters” on page 155
“Host Configuration Parameters” on page 156
“User Configuration Parameters” on page 158
“System Time Configuration Parameters” on page 159
Administrator-Only Commands
TABLE 27
Administration-Only Commands
Command
Syntax
Description
set
pducli -> set Params=Values
Sets PDU specific configuration and measurement
parameters.
150
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding Administrator-Only Commands
Command
Syntax
Description
get
pducli -> get Params
Gets PDU specific configuration and measurement
parameters.
reset
pducli -> reset=yes
Reboots the PDU.
factory_default
pducli -> factory_default=yes
Sets PDU to factory default settings.
PDU System Information Parameters (set
Command)
TABLE 28
PDU System Information Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pdu_name
pducli -> set pdu_name=xxxx
pducli-> set OK (or an error message)
pdu_product_id
pducli -> set pdu_product_id=xxxx
pducli-> set OK (or an error message)
pdu_rack_serial_number
pducli -> set
pducli-> set OK (or an error message)
pdu_rack_serial_number=xxxx
pdu_location
pducli -> set pdu_location=xxxx
pducli-> set OK (or an error message)
pdu_display_info_time
pducli -> set pdu_display_info_time=xx
pducli-> set OK (or an error message)
(xx is seconds; 1-60 allowed)
pdu_web_gui_refresh_interval
pducli -> set
pducli-> set OK (or an error message)
pdu_web_gui_refresh_interval=xx
(xx is seconds; 1-60 allowed)
Network Services Configuration Parameters
TABLE 29
Network Services Configuration Parameters (set Command) Available Starting with FW2.01
Parameters
Syntax
Response
net_web_version
pducli -> set net_web_version=x (0 for disable,
1 for HTTP, 2 for HTTPS)
pducli-> set OK (or an error message)
net_snmp_version
pducli -> set net_snmp_version=x (0 for
disable, 1 for SNMPv2, 2 for SNMPv3, 3 to enable
both versions
pducli-> set OK (or an error message)
net_snmp_mib
pducli -> set net_snmp_mib=x
pducli-> set OK (or an error message)
(0 for enhanced PDU MIB, 1 for original PDU MIB)
net_syslog_enable †
pducli -> set net_syslog_enable=On
pducli-> set OK (or an error message)
†
This command is available only in FW 2.01.
Understanding CLI Commands
151
Understanding Administrator-Only Commands
Note - After executing any combination of the commands above, execute a reset=yes
command for the changes to take affect.
TABLE 30
Network Services Configuration Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
net_alivetrap_interval
pducli -> set net_alivetrap_interval=xx
pducli-> set OK (or an error message)
(xx=seconds: 0-60 allowed; 0=disabled)
net_traprepeat_interval
pducli-> set net_traprepeat_interval=xx
(xx=seconds: 0-60 allowed; 0=disabled)
pducli-> set OK (or an error message)
net_traprepeat_qty
pducli-> set net_traprepeat_qty=xx
pducli-> set OK (or an error message)
(xx=number for repeats; 0-255 allowed)
net_testtrap_init
pducli-> set net_testtrap_init=yes (only
available if Enhanced-MIB is selected)
pducli-> set OK (or an error message)
net_syslog_interval_hour
pducli -> set net_syslog_interval_hour=xx
(xx= Interval in hours: 0-24 allowed)
pducli-> set OK (or an error message)
net_syslog_interval_min
pducli -> set net_syslog_interval_min=xx
pducli-> set OK (or an error message)
(xx=Interval in minutes: 0-59 allowed)
net_syslog_interval_sec
pducli -> set net_syslog_interval_sec=xx
pducli-> set OK (or an error message)
(xx= Interval in seconds; 0-59 allowed)
net_syslog_alarm_enable
pducli-> set net_syslog_alarm_enable=on
pducli-> set OK (or an error message)
(or net_syslog_alarm_enable=off)
net_syslog_values_ enable
_pdu
pducli -> set
pducli-> set OK (or an error message)
net_syslog_values_enable_pdu=xx
(0 - disabled, 4 - active power)
net_syslog_values_
enable_inputs
pducli -> set
pducli-> set OK (or an error message)
net_syslog_values_enable_inputs=xx (0 disabled, 4 - active power)
net_syslog_values_
enable_lines
pducli -> set
pducli-> set OK (or an error message)
net_syslog_values_enable_lines=xx
(0 - disable, 1 - for Current, 2 - Voltage,
4 - ActivePower, 8 - ApparentPower => 15
Current/Voltage/ActivePower/ApparentPower)
TABLE 31
Network Services Configuration Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
net_web_version
pducli -> get net_web_version
pducli-> net_web_version=1
(0 for disabled, 1 for HTTP, or 2 for HTTPS)
152
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding Administrator-Only Commands
Parameters
Syntax
Response
net_snmp_version
pducli -> get net_snmp_version
pducli-> net_snmp_version=3
(0 for disabled, 1 for SNMPv1/v2, 2 for SNMPv3, or 3
for both versions)
net_snmp_mib
pducli -> get net_snmp_mib
pducli -> net_snmp_mib=1
(0 for Enhanced PDU MIB or 1 for original PDU MIB)
TABLE 32
Network Services Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
net_term_version
pducli -> get net_term_version
pducli-> net_term_version=2
(2 for ssh; no other versions supported)
net_alivetrap_interval
pducli -> get net_alivetrap_interval
pducli-> net_alivetrap_interval=xx
(with xx in seconds: 0-60 allowed; 0 is disabled)
net_traprepeat_interval
pducli-> get net_traprepeat_interval
pducli-> net_traprepeat_interval=xx
(with xx in seconds: 0-60 allowed; 0 is disabled)
net_traprepeat_qty
pducli-> get net_traprepeat_qty
pducli-> net_traprepeat_qty=xx
(with xx number for repeats: 0-60 allowed)
net_syslog_interval_hour pducli -> get net_syslog_interval_hour
pducli-> net_syslog_interval_hour=xx
(with xx is the interval in hours: 0-24 allowed
net_syslog_interval_min
pducli -> get net_syslog_interval_min
net_syslog_interval_sec
pducli -> get net_syslog_interval_sec
net_syslog_alarm_enable
pducli-> get net_syslog_alarm_enable
pducli-> net_syslog_interval_min=xx
(with xx is the interval in minutes: 0-59 allowed)
pducli-> net_syslog_interval_sec=xx
(with xx is the interval in seconds: 0-59 allowed)
pducli-> net_syslog_alarm_enable=On
(or net_syslog_alarm_enable=Off)
net_syslog_values_
enable_pdu
pducli -> get
net_syslog_values_
enable_inputs
pducli -> get
net_syslog_values_
enable_lines
pducli -> get
net_syslog_values_enable_pdu
net_syslog_values_enable_inputs
net_syslog_values_enable_lines
pducli-> net_syslog_values_enable_pdu=xx
(with xx=0 for disable, or xx=4 for include
ActivePower)
pducli-> net_syslog_values_enable_inputs=xx
(with xx=0 for disable, xx=4 for include ActivePower)
pducli-> net_syslog_values_enable_lines=xx
(xx=0 for disabled, xx=1 for include Current, xx=2
for include Voltage, xx=4 for include ActivePower,
xx=8 for include ApparentPower => xx=15 for include
Current/Voltage/ActivePower/ApparentPower)
Understanding CLI Commands
153
Understanding Administrator-Only Commands
Network Ports Configuration Parameters
TABLE 33
Network Ports Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
net_port_snmp
pducli -> get net_port_snmp
pducli-> net_port_snmp=161
net_port_trap
pducli -> get net_port_traps
pducli-> net_port_traps=162
TABLE 34
Network Ports Configuration Parameters (set Command) for FW 2.02
Parameters
Syntax
Response
net_port_snmp
pducli -> set net_port_snmp=161
pducli-> set OK (or an error message)
net_port_trap
pducli -> set net_port_traps=162
pducli-> set OK (or an error message)
IPv4 Configuration Parameters
TABLE 35
IPv4 Configuration Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
net_ipv4_dhcp
pducli -> get net_ipv4_dhcp
pducli-> net_ipv4_dhcp=On (or net_ipv4_dhcp=Off)
net_ipv4_ipaddr
pducli -> get net_ipv4_ipaddr
pducli-> net_ipv4_ipaddr=xxx.xxx.xxx.xxx
net_ipv4_subnet
pducli -> get net_ipv4_subnet
pducli-> net_ipv4_subnet=xxx.xxx.xxx.xxx
net_ipv4_gateway
pducli -> get net_ipv4_gateway
pducli-> net_ipv4_gateway=xxx.xxx.xxx.xxx
net_ipv4_dns1
pducli -> get net_ipv4_dns1
pducli-> net_ipv4_dns1=xxx.xxx.xxx.xxx
net_ipv4_dns2
pducli -> get net_ipv4_dns2
pducli-> net_ipv4_dns2=xxx.xxx.xxx.xxx
TABLE 36
IPv4 Configuration Parameters (set Command) Available Starting with FW 2.01
Parameters
Syntax
Response
net_ipv4_dhcp
pducli -> set net_ipv4_dhcp=On (or net_ipv4_dhcp=Off)
pducli-> set OK (or an error message)
net_ipv4_ipaddr
pducli -> set net_ipv4_ipaddr=xxx.xxx.xxx.xxx
pducli-> set OK (or an error message)
net_ipv4_subnet
pducli -> set net_ipv4_subnet=xxx.xxx.xxx.xxx
pducli-> set OK (or an error message)
net_ipv4_gateway
pducli -> set net_ipv4_gateway=xxx.xxx.xxx.xxx
pducli-> set OK (or an error message)
net_ipv4_dns1
pducli -> set net_ipv4_dns1=xxx.xxx.xxx.xxx
pducli-> set OK (or an error message)
net_ipv4_dns2
pducli -> set net_ipv4_dns2=xxx.xxx.xxx.xxx
pducli-> set OK (or an error message)
Note - After executing any combination of set commands for IPv4 configuration parameters,
execute a reset=yes command for the changes to take affect.
154
Sun Rack II Power Distribution Units User's Guide • December 2016
Understanding Administrator-Only Commands
IPv6 Configuration Parameters
TABLE 37
IPv6 Configuration Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
net_ipv6_enable
pducli -> get net_ipv6_enable
pducli-> net_ipv6_enable=On (or
net_ipv6_enable=Off)
net_ipv6_manual_ip_enable
pducli -> get net_ipv6_manual_ip_enable
pducli-> net_ipv6_manual_ip_enable=On (or
net_ipv6_manual_ip_enable=Off)
net_ipv6_ipaddr
pducli -> get net_ipv6_ipaddr
pducli-> net_ipv6_ipaddr=xxxx::xxxx,yyyy::yyyy
(with list of all available IPv6-Addresses)
TABLE 38
IPv6 Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
net_ipv6_manual_ipaddr
pducli -> get net_ipv6_manual_ipaddr
pducli-> net_ipv6_manual_ipaddr=xxxx::xxxx (xxxx::
xxxx = manual configured IPv6-Address)
TABLE 39
IPv6 Configuration Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
net_ipv6_enable
pducli -> set net_ipv6_enable=On (or
net_ipv6_enable=Off)
pducli-> set OK (or an error
message)
net_ipv6_manual_ip_enable
pducli -> set net_ipv6_manual_ip_enable=On (or
net_ipv6_manual_ip_enable=Off)
pducli-> set OK (or an error
message)
net_ipv6_manual_ipaddr
pducli -> set net_ipv6_manual_ipaddr=xxxx::xxxx
pducli-> set OK (or an error
message)
PDU Events List Parameters
TABLE 40
PDU Event List Parameter (get Command) Available Starting with FW 2.01
Parameters
Syntax
Description
pdu_event_list
pducli -> get pdu_event_list-xx (with
option xx is max. number of event for CLI output,
without option xx -> default = 10 events)
pducli-> pdu_event_list=E1: yyyy.mm.dd/hh:mm:ss/
xxxxxxxxyyyy.mm.dd/hh:mm:ss/ xxxxxxxx
(with yyyy.mm.dd is date, hh:mm:ss is time and xx is event
info)
Note - A maximum of 1000 events can be handled from a PDU.
Understanding CLI Commands
155
Understanding Administrator-Only Commands
TABLE 41
PDU Event List Parameter (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pdu_clear_event_list
pducli -> set pdu_clear_event_list=yes
pducli-> set OK (or an error message)
Host Configuration Parameters
TABLE 42
Host Configuration Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
snmp_nms_host
pducli -> set snmp_nms_host.x=yyyy (yyyy=
Host Name, Host x from 1-4)
pducli-> set OK (or an error message)
snmp_nms_community_readonly
pducli -> set
pducli-> set OK (or an error message)
snmp_nms_community_readonly.x=yyyy
(yyyy= ReadOnly-Community, Host x from 1-4)
snmp_nms_community_readwrite
pducli -> set
pducli-> set OK (or an error message)
snmp_nms_community_readwrite.x=yyyy
(yyyy= ReadWrite-Community, Host x from 1-4)
snmp_nms_accessright
pducli -> set snmp_nms_accessright.x=y
pducli-> set OK (or an error message)
(0=readonly, 1=read/write, 2=both, Host x from 1-4)
snmp_nms_enable
pducli-> set snmp_nms_enable.x=On
pducli-> set OK (or an error message)
(or Off, Host x from 1-4)
snmp_traptarget_host
pducli-> set snmp_traptarget_host.x
pducli-> set OK (or an error message)
(x=management-server-123.company.org)
snmp_traptarget_version
pducli-> set snmp_traptarget_version.x=2
pducli-> set OK (or an error message)
snmp_traptarget_enable
pducli-> set snmp_traptarget_enable.x=On
pducli-> set OK (or an error message)
snmp_nms_traptargethost
pducli-> set snmp_nms_traptargethost.x=yyyy
pducli-> set OK (or an error message)
(yyyy= Host Name, TrapTarget x from 1-10)
snmp_nms_traptarget_community
pducli-> set
pducli-> set OK (or an error message)
snmp_nms_traptarget_community.x=yyyy
(yyyy= SNMP Trap Community, TrapTarget x from 110)
snmp_nms_traptarget_version
pducli -> set
pducli-> set OK (or an error message)
snmp_nms_traptarget_version.x=y
(1=SNMPv1, 2=SNMPv2, 3=SNMPv3, TrapTarget x from
1-10)
snmp_nms_traptarget_enable
pducli -> set
snmp_nms_traptarget_enable.x=On
156
Sun Rack II Power Distribution Units User's Guide • December 2016
pducli-> set OK (or an error message)
Understanding Administrator-Only Commands
Parameters
Syntax
Response
(or Off, TrapTarget x from 1-10)
syslogserver_host
pducli-> set OK (or an error message)
pducli -> set syslogserver_host.x=yyyy
(yyyy= SyslogServer-Host, SyslogServer x from
1-4)
syslogserver_enable
pducli -> set syslogserver_enable.x=On
pducli-> set OK (or an error message)
(or Off, SyslogServer x from 1-4)
TABLE 43
Host Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
snmp_nms_host
pducli -> get snmp_nms_host.x
pducli-> -> snmp_nms_host.x= yyyy (yyyy=
Host Name, Host x from 1-4)
snmp_nms_community_readonly
pducli -> get
pducli ->
snmp_nms_community_readonly.x=yyyy (yyyy=
ReadOnly-Community for Host x)
snmp_nms_community_readonly.x
(x= Host-Number 1-4)
snmp_nms_community_readwrite pducli -> get
snmp_nms_accessright
snmp_nms_enable
snmp_nms_community_readwrite.x
pducli -> snmp_nms_community_readwrite.x
=yyyy
(x= Host-Number 1-4)
(yyyy= ReadWrite-Community for Host x)
pducli -> get snmp_nms_accessright.x
pducli -> snmp_nms_accessright.x=y
x= Host-Number 1-4)
(0=readonly, 1=read/write, 2=both, for Host x)
pducli-> get snmp_nms_enable.x
pducli-> snmp_nms_enable.x=On (or
snmp_nms_enable.x=Off for Host x)
(x= Host-Number 1-4)
snmp_traptarget_host
snmp_traptarget_community
pducli-> get snmp_traptarget_host.x
pducli-> snmp_traptarget_host.x=yyyy
(x= TrapTarget-Number from 1-10)
(yyyy= Host Name for TrapTarget x)
pducli -> get
pducli->
snmp_nms_traptarget_community.x=yyyy
(yyyy= SNMP TrapCommunity for TrapTarget
x)
snmp_nms_traptarget_community.x
(x=TrapTarget-Number from 1-10)
snmp_traptarget_version
pducli -> get
snmp_nms_traptarget_version.x
snmp_traptarget_enable
(x= TrapTarget from 1-10)
(1=SNMPv1, 2=SNMPv2, 3=SNMPv3 for
TrapTarget x)
pducli -> get
(x= TrapTarget from 1-10)
pducli ->
snmp_nms_traptarget_enable.x=On (or
snmp_nms_traptarget_enable.x=Off for
TrapTarget x)
pducli -> get syslogserver_host.x
pducli -> syslogserver_host.x=yyyy
(x= SyslogServer-Number from 1-4)
(yyyy= SyslogServer-Host for SyslogServer
x)
snmp_nms_traptarget_enable.x
syslogserver_host
pducli ->
snmp_nms_traptarget_version.x=y
Understanding CLI Commands
157
Understanding Administrator-Only Commands
Parameters
Syntax
Response
syslogserver_enable
pducli -> get syslogserver_enable.x
pducli -> syslogserver_enable.x=On
(x= SyslogServer-Number from 1-4)
(or syslogserver_enable.x=Off for
SyslogServer x)
User Configuration Parameters
TABLE 44
User Configuration Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
user_name
pducli -> set user_name.x=yyyy (yyyy=
UserName, User-Number x from 1-5)
pducli-> set OK (or an error message)
user_password
pducli -> set password.x=yyyy(yyyy=
UserPassword, User-Number x from 1-5)
pducli-> set OK (or an error message)
user_accessright
pducli -> set accessright.x=y (1= User,
pducli-> set OK (or an error message)
2= Admin, User-Number x from 1-5)
user_snmpv3_name
pducli -> set user_snmpv3_name.x=yyyy
pducli-> set OK (or an error message)
(yyyy= SNMPv3-UserName, SNMPv3- User x from
1-10)
user_snmpv3_security_level
pducli -> set user_snmpv3_name.x=y
pducli-> set OK (or an error message)
(0= No Auth/No Priv, 1= Auth/No Priv, 2= Auth/
Priv, Userx from 1-10) SNMPv3 UserName,
SNMPv3 User x from 1-10)
user_snmpv3_auth_alg
pducli -> set user_snmpv3_auth_alg.x=y
pducli-> set OK (or an error message)
(0= MD 3, 1 = SHA, SNMPv3 User x from 1-10)
user_snmpv3_auth_password
pducli -> set
pducli-> set OK (or an error message)
user_snmpv3_auth_password.x=yyyy
(yyyy= SNMOv3-AuthPassword, SNMPv3- User x
from 1-10)
user_snmpv3_priv_alg
pducli -> set user_snmpv3_priv_alg.x=y
pducli-> set OK (or an error message)
(0= DES, 2= AES, 3= AES192, 4= AES256,
SNMPv3- User x from 1-10)
user_snmpv3_priv_password
pducli -> set
pducli-> set OK (or an error message)
user_snmpv3_priv_password.x=yyyy
(yyyy= SNMPv3-PrivPassword, SNMPv3- User x
from 1-10)
user_snmpv3__accessright
pducli -> set user_snmpv3_accessright.x=y
pducli-> set OK (or an error message)
(0=readonly, 1=readwrite, SNMPv3- User x from 110)
user_snmpv3_enable
158
pducli -> set user_snmpv3_enable.x=On
Sun Rack II Power Distribution Units User's Guide • December 2016
pducli-> set OK (or an error message)
Understanding Administrator-Only Commands
Parameters
Syntax
Response
(or Off, SNMPv3- User x from 1-10)
TABLE 45
User Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
user_name
pducli -> get user_name.x
pducli -> user_name.x=yyyy (yyyy= UserName
for x)
(x= User-Number from 1-5)
pducli -> get accessright.x
user_accessright
(x= UserName-Number from 1-5)
user_snmpv3_name
pducli -> get user_snmpv3_name.x
(x=SNMPv3-User-Number from 1-10)
user_snmpv3_security_level
pducli -> get user_snmpv3_name.x
(x= SNMPv3-User-Number from 1-10)
user_snmpv3_auth_alg
pducli -> get user_snmpv3_auth_alg.x
(x= SNMPv3-User-Number from 1-10)
user_snmpv3_priv_alg
user_snmpv3_accessright
user_snmpv3_enable
pducli -> accessright.x=y(1= User,
2=Admin for User x)
pducli -> user_snmpv3_name.x=yyyy (yyyy=
SNMPv3-UserName for SNMPv3- User x)
pducli -> user_snmpv3_name.x=y (0= No
Auth/No Priv, 1= Auth/No Priv, 2= Auth/
Priv for SNMPv3- User x)
pducli -> user_snmpv3_auth_alg.x=y (0= MD
5, 1= SHA, SNMPv3-User )x
(x = SNMPv3-User-Number from 1-10)
pducli - >user_snmpv3_priv_alg.x=y (0=
DES, 2= AES, 3= AES192, 4= AES256, for
SNMPv3- User x)
pducli -> get user_snmpv3_accessright.x
pducli ->
(x= SNMPv3-User-Number from 1-10)
user_snmpv3_priv_password.x=yyyy
(0=readonly, 1=readwrite for SNMPv3User x)
pducli -> get user_snmpv3_enable.x
pducli -> user_snmpv3_enable.x=On (or
pducli -> get user_snmpv3_priv_alg.x
(x= SNMPv3-User-Number from 1-10)
user_snmpv3_enable.x=Off for SNMPv3User x)
System Time Configuration Parameters
Note - Enabling Daylight Saving Time will add an hour to the previously set time. The time
will not automatically return to Standard Time when Daylight Saving Time ends. Set the
systime_dst_enable parameter to Off to disable this setting once Daylight Saving Time ends
for your location.
TABLE 46
System Time Configuration Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
systime_manual_date
pducli -> get systime_manual_date
pducli ->
systime_manual_date=yyyy-
mm-dd
Understanding CLI Commands
159
Understanding Administrator-Only Commands
Parameters
Syntax
Response
(yyyy= year, mm= month, dd= day)
systime_manual_time
pducli -> get systime_manual_time
pducli -> systime_manual_time=hh:mm:ss
(hh= hour, mm= minutes, ss= seconds)
systime_ntp_server_enable_
pducli -> get systime_ntp_server_enable
pducli -> systime_ntp_server_enable=On
(or systime_ntp_server_enable=Off)
systime_ntp_server
pducli -> get systime_ntp_server
pducli -> systime_ntp_server=xxxx
(xxxx= NTP-Server)
systime_ntp_server_timezone
pducli -> get systime_ntp_server_timezone
pducli -> systime_ntp_server_timezone=xx
(xx=index to Timezone-Table; 0-77 allowed. See
also WebConfiguration)
systime_ntp_server_poll_
interval
pducli -> get
systime_ntp_server_poll_interval
pducli ->
systime_ntp_server_poll_interval=xx
(xx= Poll-Interval in hours: 1-24 allowed)
systime_ntp_server_last
_sync
pducli -> get
systime_current_pdu_time
pducli -> get systime_current_pdu_time
systime_ntp_server_last_sync
pducli ->
systime_ntp_server_last_sync=yyyy-mm-dd
hh:mm:ss (yyyy= year, mm= month, dd= day,
hh= hours, mm= minutes, ss= seconds)
pducli -> systime_current_pdu_time=yyyymm-dd hh:mm:ss
(yyyy= year, mm= month, dd= day, hh= hours,
mm=minutes, ss= seconds)
systime__dst_enable
pducli -> get systime_dst_enable
pducli -> systime_dst_enable=On
(or set systime_dst_enable=Off)
TABLE 47
System Time Configuration Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
systime_manual_date
pducli -> set systime_manual_date=yyyy-mmdd (yyyy= year, mm= month, dd= day)
pducli-> set OK (or an error message)
systime_manual_time
pducli -> set
pducli-> set OK (or an error message)
systime_manual_time=hh:mm:ss (hh= hour,
mm= minutes, ss= seconds)
systime_ntp_server_enable_
pducli -> set systime_ntp_server_enable=On
pducli-> set OK (or an error message)
(or set systime_ntp_server_enable=Off)
systime_ntp_server
pducli -> set systime_ntp_server=xxxx
pducli-> set OK (or an error message)
(xxxx= NTP-Server)
systime_ntp_server_timezone
pducli -> set
systime_ntp_server_timezone=xx (xx=index
to Timezone-Table; 0-77 allowed. See
also WebConfiguration)
160
Sun Rack II Power Distribution Units User's Guide • December 2016
pducli-> set OK (or an error message)
Understanding Administrator-Only Commands
Parameters
Syntax
Response
systime_ntp_server_poll_interval
pducli -> set
pducli-> set OK (or an error message)
systime_ntp_server_poll_interval=xx (xx=
Poll-Interval in hours: 1-24 allowed)
systime_dst_enable
pducli-> set systime_dst_enable=On (or
pducli-> set OK (or an error message)
Off)
Understanding CLI Commands
161
162
Sun Rack II Power Distribution Units User's Guide • December 2016
Servicing PDUs
Perform these tasks when servicing standard and compact PDUs.
Description
Links
Replace a standard PDU.
“Disconnect the Main Input Power Cords From the Power
Source” on page 163
“Remove a Standard PDU” on page 164
“Installing Standard PDUs” on page 31
Replace a compact PDU.
“Disconnect the Main Input Power Cords From the Power
Source” on page 163
“Remove a Compact PDU” on page 166
“Installing Compact PDUs” on page 35
Disconnect the Main Input Power Cords From the Power
Source
Note - Refer to the service manuals of the equipment installed in the rack for the proper PDU
replacement procedures, if applicable.
1.
Prepare for services as you would for installation.
Servicing PDUs
163
Remove a Standard PDU
See “Preparing for Installation” on page 25.
2.
Disconnect the power cords.
3.
Remove a standard or compact PDU.
■
■
To remove a standard PDU, see “Remove a Standard PDU” on page 164.
To remove a compact PDU, see “Remove a Compact PDU” on page 166.
Remove a Standard PDU
Note - Refer to the service manuals of the equipment installed in the rack for the proper PDU
replacement procedures, if applicable.
1.
Shut down and power off the equipment installed in the rack.
Refer to the system and equipment documentation for the proper shut down and power off
procedures.
2.
Open the rear door of the rack.
3.
Attach a wrist strap to your wrist and to an ESD grounding jack on the rack.
See “Attach an Antistatic Wrist Strap” on page 28.
4.
Switch off all of the PDU circuit breakers in the rack.
Press down on the Off (0) toggle switch to power off the PDU. These circuit breakers are at
the rear of the rack cabinet. See “Circuit Breaker Locations (Standard PDU)” on page 49 or
“Circuit Breaker Locations (Compact PDU)” on page 50.
164
Sun Rack II Power Distribution Units User's Guide • December 2016
Remove a Standard PDU
5.
Disconnect the PDU's main power lead cords from the AC power source.
See “Disconnect the Main Input Power Cords From the Power Source” on page 163.
6.
Disconnect any power jumper cords connected to the PDU from equipment in
the rack.
Note where these jumper cords were attached to the PDU.
7.
Cut any tie-wraps securing the PDU power input lead cords to the tie-down
brackets.
8.
Disconnect the grounding strap connecting the top of the PDU to the rack.
9.
If the rack included a factory-installed PDU, use a T-25 wrench key to remove the
four M5 screws and washers securing the PDU to the mounting brackets.
Servicing PDUs
165
Remove a Compact PDU
These screws secured the PDU for shipping purposes. You might have already removed these
screws when you installed the rack at the installation site.
10.
Carefully lift the PDU up and off the mounting brackets. Remove the PDU from
the rack and place it on a clean work table.
11.
Install a new PDU.
See “Installing Standard PDUs” on page 31.
Remove a Compact PDU
Note - Refer to the service manuals of the equipment installed in the rack for the proper PDU
replacement procedures, if applicable.
166
1.
Shut down and power off the equipment installed in the rack.
Refer to the system and equipment documentation for the proper shut down and power off
procedures.
2.
Open the rear door of the rack.
Sun Rack II Power Distribution Units User's Guide • December 2016
Remove a Compact PDU
3.
Attach a wrist strap to your wrist and to an ESD grounding jack on the rack.
See “Attach an Antistatic Wrist Strap” on page 28.
4.
Switch off the two PDU circuit breakers in the rack.
Press down on the Off (0) toggle switch to power off the PDU. These circuit breakers at the rear
of the rack cabinet. See “Circuit Breaker Locations (Standard PDU)” on page 49 or “Circuit
Breaker Locations (Compact PDU)” on page 50.
5.
Disconnect the PDU's main power lead cord from the AC power source.
See “Disconnect the Main Input Power Cords From the Power Source” on page 163.
6.
Disconnect any power jumper cords connected to the PDU from equipment in
the rack.
Note where these jumper cords were attached to the PDU.
7.
Disconnect the PDU grounding strap connected to the rear rack rail.
Disconnect the grounding strap by pressing down on the tab of the strap's quick-release
connector and pulling the strap away from the connector. You can optionally remove the
grounding strap from the PDU. However, the replacement PDU ships with a new grounding
strap.
8.
Using a T-25 Torx wrench key, remove the screw and washer securing the top
mounting bracket to the rack's rail.
Servicing PDUs
167
Remove a Compact PDU
Leave the spring nut in the rack rail channel, and save the screw and washer for future use.
9.
10.
168
Lift the PDU slightly and slide it out of the side mounting bracket.
Using a T-25 Torx wrench key, remove the two screws and washers securing the
top mounting bracket to the PDU.
Sun Rack II Power Distribution Units User's Guide • December 2016
Remove a Compact PDU
Save the screws, washers, and top mounting bracket for future use.
11.
Consider your next step.
■
If you are replacing the old compact PDU with a new compact PDU, go to
“Installing Compact PDUs” on page 35.
■
If you are replacing the old compact PDU with a new standard PDU, go to
“Installing Standard PDUs” on page 31.
Servicing PDUs
169
170
Sun Rack II Power Distribution Units User's Guide • December 2016
Glossary
C
Compact PDU
Compact power distribution unit.
D
DHCP
Dynamic Host Configuration Protocol.
DST
Daylight saving time.
I
IPv4
Internet Protocol version 4.
IPv6
Internet Protocol version 6.
N
NMS
Network management station.
O
Oracle ILOM
Oracle Integrated Lights Out Manager.
P
PDU
Power distribution unit. There are three types of PDUs, compact PDU, standard original PDU,
and standard enhanced PDU.
Glossary
171
SNMP
S
SNMP
Simple Network Management Protocol.
SRII
Sun Rack II.
standard PDU
Standard power distribution unit. There are two types of standard PDUs, original PDU and
enhanced PDU.
172
Sun Rack II Power Distribution Units User's Guide • December 2016
Index
A
admin
changing passwords, 87, 120
Admin/User fields, 87, 120
alarms
checkbox, 91, 124
description, 85, 85, 117, 118
out of balance, 84
parameter, 81, 113
setting, 80, 113
SNMP trap descriptions, 92, 124
system log messages
description, 91, 124
enabling, 91, 124
ampere measurements, 82, 84, 114, 117
antistatic wrist strap, attaching, 31, 36
C
cable mounting brackets, securing leads to, 35
circuit breakers
capacity, facility, 18
positioning on a standard PDU, 32
power off, 50
power on, 51
resetting after a fault, 49
CLI Commands, 145
crossover cable
diagram, 66
requirements, 58
Current Measurement page
color description, 85, 117
connecting PDU to network, 56
monitoring current, 83, 116
current, monitoring, 81
D
date of manufacture, 97
Daylight Savings Time, setting, 137
depth
compact PDU, 22
standard PDU, 19
DHCP Enable checkbox, 57, 64, 70
DHCP network
connection, 54, 66, 66
disabling, 64, 70
permanently enabling, 55
temporarily enabling, 55
dimensions
compact PDU, 21, 22, 22, 22
standard PDU, 19
dladm command, 62
E
enhanced PDU
installing, 31
monitoring, 105
removing, 164
specifications, 19
ESD grounding strap, 31, 36
Ethernet
crossover cable, 58, 66
port location, 67
port, location, 54
F
facility power
connecting PDU, 51
requirements, 17
factory-reset button, 103
173
Index
firmware
downloading new version, 98, 130, 131
information, 97, 129, 129
standard PDU only, 53
update prompt, 99, 130
updating, 98, 130
version, 97, 101, 136
G
grounding strap
attaching
compact PDU,
standard PDU,
disconnecting
compact PDU,
standard PDU,
location
standard PDU,
H
42
29
167
165
29
high voltage
compact PDU specifications, 22
standard PDU specifications, 21
HTML interface
Admin/User fields, 87, 120
changing settings, 86, 119
Current Measurement page, 83
factory-reset button, 103
Firmware-Update Filename checkbox, 99, 130
HTTP enable checkbox, 93, 126
Login fields, 79, 111
module
info page, 97
information, viewing, 97, 129, 129
name and location fields, 87
monitoring current, 83, 115, 118, 119
Net Configuration fields, 57, 64, 70
NMS fields, 95
Param Configuration page, 80, 112
SNMP Enable checkbox, 93, 126
SNMP settings, 94
Syslog fields, 90, 122
Trap Host Setup fields, 93, 127
HTTP
174
enabling through SNMP, 93, 127
I
ifconfig command, 62
incoming line to neutral voltage, measuring, 17
input lead cords
connecting, 50
length
compact PDU, 22
standard PDU, 19
metering unit relationship, 76, 78, 108, 110
module relationship, 74, 106
numbering, 76, 78, 110
outlet group relationship, 74, 106
power source, disconnecting, 165, 167
routing
compact PDU, 42
standard PDU, 33
input relationship
Relationship Between Inputs and Outlet
Groups, 105
installation task overview (Compact PDU), 13
installation task overview (Standard PDU), 13
installing
compact PDU, 27, 42
standard PDU, 27
IP address, 57, 64, 70, 101, 136
J
jumper cords
avoiding overloading circuit, 51
disconnecting, 165, 167
symmetrical load, 51
L
LCD screen
background, changing, 101, 136
messages, understanding, 74, 106
module and outlet relationship, 74, 106
monitoring current, 81
reading, 82, 115
resetting metering unit, 100, 133
rotating, 101, 136
Sun Rack II Power Distribution Units User's Guide • December 2016
Index
status message, 100, 135
length
compact PDU, 22
standard PDU, 19
lifting standard PDU, 33
login prompt
admin user, 71, 113, 113
defined, 79, 111
users, 71
low voltage
compact PDU specifications, 22
standard PDU specifications, 19-21, 21
M
MAC address, 97, 101, 136
messages
SNMP traps, 92, 124
syslog messages, 91, 124
understanding, 74, 85, 106, 117
metering unit
adding users, 87, 120
changing passwords, 87, 120
Current Measurement page, 56
Ethernet port, 54, 67
firmware
information, 97, 129, 129
updating, 98, 130
HTML interface, 83, 115, 118, 119
IP address, 101, 136
LCD screen, 81
log into, 79, 111
login prompt, 79, 111
module, 74, 106
module and phase relationship, 74, 106
monitoring, 73-103, 103, 105-141, 141
incoming line to neutral voltage, 17
naming, 86, 119
network access, 79
network connection
DHCP IP address, 54, 66, 66
introduced, 53
static IP address, 57
NMS hosts, setting, 95
outlet group, 74, 106
Param Configuration page, 80, 111
phase, 74, 106
Reset button, 55
resetting, 100, 133
restore default settings, 102, 139
SNMP
configuring, 91, 124
enabling, 91, 124
traps, 92, 124
static IP address network connection, 63
syslog messages, 88, 121
thresholds, setting, 79
time, setting, 137
module
alarms, setting, 80, 112
defined, 74, 106
monitoring, 84, 117
parameters, setting, 80, 112
relationship with phases and groups, 74, 106
Module Info page, 97
Module Name & Location fields, 87, 120
monitoring
LCD screen, 81, 114
metering unit phase, 74, 106
module, 74, 106
network connection
DHCP IP address, 54, 66, 66
establishing, 53-71, 65, 69, 71
static IP address, 57
phase, 74, 106
standard PDU only, 53
N
naming PDU, 86, 119
Net Configuration page
Admin/User fields, 87, 120
enabling DHCP, 57
factory-reset button, 102, 134, 137, 139, 140
firmware-update, 99, 130
HTTP Enable checkbox, 93
module name & location, 86, 119
NMS, 96
SNMP enable checkbox, 93
static IP address network, 64, 70
syslog fields, 90, 122
trap host setup, 94, 127
175
Index
network configuration
DHCP
disabling, 64, 70
enabling, 57
page, 57, 64, 70
static IP address, 63
network connection
DHCP, 54, 66, 66
establishing, 54-71, 65, 66, 69, 71
static IP address, 57
network management station, 95
NMS hosts, 95
O
operating temperature range, 23
Oracle Solaris system, point-to-point connection, 62
original PDU
installing, 31
monitoring, 73
removing Refer to the service manuals of the
equipment installed in the rack for the proper PDU
replacement procedures, if applicable. , 164
specifications, 19
out of balance
alarm message, 84, 85
description, 81, 85, 113, 117
parameter, 81, 81, 113, 113
SNMP trap, 92, 124
outlet groups, 74, 106
incoming line to neutral voltage, measuring, 17
metering unit module relationship
single-phase PDUs, 76
three-phase PDUs, 78, 110
outlet type and number
compact PDU, 23
standard PDU, 20, 21
P
Param Configuration page, 80, 87, 111
parameter
info low, 111
Parameter Configuration page, 111
parameters, 80, 80, 81, 113, 113, 113
monitoring, 84
176
out of balance, 81
SNMP, 92, 125, 127
part number, 97
Password field, 79, 111
passwords
assigning, 87, 120
changing, 87, 120
patch cable, 58, 63, 69
PC, configuring point-to-point connection, 58
PDU
antistatic strap, attaching, 31, 36
compact
grounding strap, attaching, 42
high-voltage, 22
installing, 27
low-voltage, 22
mounting brackets, 40, 46
mounting screw locations, 47
rack template, 37, 46
removing for service, 166
specifications, 21, 22, 22, 22
date of manufacture, 97
input lead cords
connecting, 50
routing from compact PDU, 42
routing from standard PDU, 33
jumper cords
routing, 52
LCD screen, 99, 132
MAC address, 100, 135
monitoring, 73-102, 102, 105-141, 141
naming, 86, 119
network connection
DHCP IP address, 54, 66
establishing, 53
static IP address, 57
part number, 97
resetting, 100, 133
restore default settings, 102, 139
safety notices, 25
serial number, 97
shipping screws, removing from standard
PDU, 166
standard
cable mounting brackets, 35
grounding strap, attaching, 29
Sun Rack II Power Distribution Units User's Guide • December 2016
Index
installing, 27
lifting, 33
low-voltage, 19
mounting brackets, 32
removing for service, 164
tie-wraps, securing to cable routing bracket, 35
phase
alarms, setting, 80, 113
defined, 74, 106
metering unit group relationship, 74, 106
metering unit module relationship, 74, 106
thresholds, setting, 80, 113
pinouts, SER MGT port, 142
point-to-point connection
crossover cable diagram, 66
Oracle Solaris system, configuring, 62
PC, configuring, 58
port, Ethernet, 54, 67
power distribution unit See PDU
power input lead cords See input lead cords
PreWarningHigh-Trap description, 125
R
rack template, 37, 46
receptacle type
compact PDU, 23
standard PDU, 20, 21
requirements
circuit breaker capacity, facility, 18
facility power, 17
grounding, 18
reset button
cycling through modules, 82, 114
powering on PDU, 55
resetting metering unit, 100, 133
resetting
circuit breakers, 49
metering unit, 99, 133
restore default settings, 102, 139
ReturnToNormal-Trapdescription, 92, 124
routing input lead cords
compact PDU, 42
standard PDU, 33
S
safety notices, 25
SER MGT port pinouts, 142
serial number, 97
service
circuit breakers, resetting, 49
shipping screws
standard PDU
installing, 33
removing, 166
SNMP
community name, 94, 96
disabling, 92, 125, 127
Enable checkbox, 93
enabling, 92, 125, 127
enabling per module, 81, 113
host IP addresses, 94
host setup, 93, 127
NMS hosts, setting, 95
parameter settings, 92, 125, 127
setting trap values, 95, 128
trap descriptions, 92, 124
trap host setup, 93
specifications
compact PDU, 22
environmental, 23
standard PDU, 21
spring nuts, inserting, 38
static IP address
network configuration, 63
network connection, 57
syslog
Enable checkbox, 90, 123
messages, 88-91, 91, 121-124, 124
enabling, 90, 123
example, 88, 122
setting parameters, 90, 122
setting time between messages, 91, 123
system log
Alarms checkbox, 91, 124
messages
enabling, 90, 123
example, 88, 121
parameters, setting, 90
time between messages, setting, 91, 123
177
Index
T
temperature, operating range, 23
thresholds, setting, 79, 112
tie-wraps, 35
time, setting, 137
tools, assembling, 27, 27
traps
described, 92, 124
KeepAlive trap, 94, 128
setting, 95, 128
trap host setup, 93
U
unpacking
compact PDU, 36, 40
standard PDU, 31
users
adding, 87, 87, 120
changing passwords, 87
login field, 79, 111
V
voltage
compact PDU
high voltage,
low voltage,
standard PDU
high voltage,
low voltage,
23
23
21
20
W
weight
compact PDU,
standard PDU,
width
compact PDU,
standard PDU,
178
22
19
22
19
Sun Rack II Power Distribution Units User's Guide • December 2016