Complying with TÜV and
UL Standards—Designed for
improved safety, operability
and functionality
VF
-8E
Series
Functions
400V 1.5kW
n Simple vector control
• Simple vector control ensures a high torque even at low
speeds (150% torque at 1 Hz).
• The output torque characteristics for general-purpose motors
when operated by an inverter at variable speeds are shown
below.
230V 0.2kW
%
150
400V 3.7kW
Safety
Torque
Short run torque
95~100
80~90
80~100
40~65
n Product conforming to the EC Low Voltage
Directive (TÜV-approved product)
Continued run
torque
16
60
20
120Hz
~
• Conforms to DIN VDE 0160
30
Output frequency
n Product conforming to the UL standard
n Accident prevention system
• Data lock function controlled by password.
n Also conforms to the EMC Directive
• By combination use with EMI filter.
n Programmable password for operational
integrity
n Electronic thermal overload
n Auto tuning function (with slip compensation)
• This function automatically detects and controls the constant
of a motor required for vector control and is applicable to
three-phase squirrel-cage motors with 2, 4 or 6 poles.
n Speed search function
• The inverter is activated without stopping the motor (on a
free run) for a changeover from the commercial run to an
inverter run or a return from sudden power failure.
MC1
Operability
n Improved monitoring functions
Breaker
SELECT
RUN
STOP
SET
SHIFT
• Simple operation for frequency settings.
• The main display on the control panel can be altered
between command frequency, output frequency and other
settings.
• The four most recent faults are stored in the memory after a
power failure to facilitate system diagnosis.
Indication of frequency, trip cause(s), etc.
• Frequency resolution
Digital setting: Min. 0.01Hz
Analog setting: Min. 0.1Hz
• Trip cause(s)
Instantaneous overcurrent (ground fault
and high temperature), overcurrent,
overvoltage, low voltage, auxiliary
interlock, overload, operation error and
auxiliary stop
Control knob for easy
frequency setting
Motor
Hz
MODE
PROG.
MC2
MC select
button
n Improved tripless function
• This function automatically decreases the frequency when
the output current reaches the overcurrent stall level during
overload operation.
• When the load returns to normal, the function automatically
returns the frequency to its original level and continues
operation.
• The function prevents overcurrent trips in equipment such as
kneading machines that are used for viscous materials.
OCS level
(Paremeter No.63)
Output
current
Deceleration time with
the value set for
Parameter No.49
Indication of Local/External
control for operation signal and
frequency signal, parameter
number, etc.
M
VF-8E
Output
frequency
Normal acceleration time
The output frequency
does not decelerate
below 10Hz.
1
MODELS
EN Type
230V Single-Phase Series
Applied
motor
output
0.2kW
(1/2HP)
0.4kW
(3/4HP)
0.75kW
(1HP)
1.5kW
(2HP)
2.2kW
(3HP)
3.7kW
(5HP)
400V Three-Phase Series
Catalog.No.
Rated
output
current
(A)
Rated
output
capacity
(kVA)
Mass
(kG)
Catalog.No.
Rated
output
current
(A)
Rated
output
capacity
(kVA)
Mass
(kG)
BFV80022EBP
2
0.8
1.4
————
——
——
—
BFV80042EBP
2.8
1.2
1.4
————
——
——
—
BFV80072EBP
3.6
1.5
1.5
BFV80074EP
2.1
1.5
2.5
BFV80152EBP
7
2.9
2.7
BFV80154EP
3.8
2.7
2.7
BFV80222EBP
9.1
3.8
3.0
BFV80224EP
5.4
3.9
2.9
————
——
——
—
BFV80374EP
8.7
6.3
3.1
STANDARD SPECIFICATIONS
230V Single-Phase Series
400V Three-Phase Series
0.2 to 2.2kW
0.75 to 3.7kW
3-phase, 200 to 240V
3-phase, 380 to 460V (415V)
150% of rated output current for 1 minute
Input power
supply
Rated
output
Models
Applied motor output
Rated output voltage
Overload capacity
Number of phases,
voltage, frequency
Operational range
Frequency variations
Instantaneous voltage
drop resistance
Three phase, 200 to 230V (240V), 50/60Hz
Single phase, 200 to 240V, 50/60Hz
180 to 264 V
Three phase, 380 to 460V (415V), 50/60Hz
342 to 506 V
±5% of rated input frequency
Continuous operation at 165V or more, or at less than 165V for 15ms.
Continuous operation at 330V or more,
or at less than 330V for 15ms.
COMMON SPECIFICATIONS
Output
frequency
Overvoltage category
Pollution degree
Output frequency range
Frequency display
Output frequency accuracy
Frequency setting resolution
Inverter control
Operation
Carrier frequency
Start/Stop
Forward/Reverse
Jog operation
Stop select
Reset
Stop frequency
Instantaneous power failure restart
Frequency setting signal
Environment Protection Display External output Braksignal
ing
Control
Voltage/frequency characteristics
2nd voltage/frequency
characteristics
2nd torque boost level
Torque boost
Accel./Decel. time
Accel./Decel. characteristics
Accel./Decel. time 2, 3, and 4
Multispeed frequency settings
Skip frequency setting
Upper frequency setting
Lower frequency setting
Bias and gain frequency settings
External fault trip
Braking Regenerative braking
torque
DC dynamic braking
Operation frequency signal
Output signal
Operating conditions
Fault trip buffers
Current limit
Shut-off (stop)
Stall prevention
Ambient temperature and relative humidity
Storage and transport temperature, relative humidity
Vibration
Installation condition
Enclosure (JEM1030)
II
2
0.2 to 400Hz
Digital display
±0.5% of selected maximum output frequency (25 ±10˚C) for analog setting
Digital setting; 0.01Hz (0.1Hz over 100Hz)
Analog setting; 0.1Hz (50/60Hz by parameter setting)
High carrier frequency sinusoidal PWM control
(Select from V/F control method or simple vector control method)
Variable from 0.8 to 15kHz
Select with operation panel buttons, 1a contact signal (either 1a, 1b contact signal)
or wait time setting (0.1 to 100sec.)
Select with operation panel buttons, 1a contact signal (reverse operation prohibit setting possible)
Optional setting for 0.2 to 20Hz
Optional Accel./Decel. time setting for 0.04 to 1600 seconds
Select from; ramp-to-stop or coast-to-stop
Select from; rest by power supply or by inputting stop signal. External reset setting is also possible.
Select from 0.2 to 60Hz
Select from; function OFF, restart at 0Hz, or restart at the setting frequency
Digital setting; Operation panel
Analog setting; 0-5V DC, 0-10V DC, 4-20mA DC, 10kW potentiometer,
input impedance at 50kW (0-5V DC) 20kW (0-10V DC), and approx. 350W (4-20mADC)
Select from; 50Hz, 60Hz, optional base frequency setting for 45Hz to 400Hz,
constant torque, or square low torque pattern
Optional base frequency setting for 45 to 400Hz
Optional setting for 0 to 40%
Optional setting for 0 to 40%
0.04 to 1600sec. Individual accel. and decel. time setting
Linear/S-characteristics (selection switchover)
0.1 to 1600sec. Individual accel.and decel. time setting Can be linked with multispeed setting.
Up to 8 preset frequency settings (programmable) Can be linked with accel. and decel. time setting.
Up to 3 place settings (skip frequency band setting from 1 to 10Hz)
Setting for 0.2 to 400Hz
Setting for 0.2 to 400Hz
Bias: set for- 99.9 to 400Hz
Gain: set for 0 to 400Hz
Select from: auxiliary interlock fault or auxiliary stop (coast-to-stop)
20% min. (0.2kW; 100% min. 0.4kW; 80% min.)
Working at less than setting stop frequency (braking torque and braking time settings)
0-5V DC
Open collector output (50V, 50mA max.) Run signal, arrival signal, frequency detection signal,
overload alarm signal, reverse operation signal (selectable)
1c contact output (contact capacity at 250V AC, resistance load at 0.5A) Fault alarm signal, run signal,
frequency detection signal, overload alarm signal, reverse operation signal (selectable)
Output frequency, setting frequency (F1) (A2) Line speed display (selection switchover)
Output current (A0), output voltage (A1), rotation direction
Display when protective functions are activated (last 4 faults are stored).
Current limit can be set from 1 to 200% of rated output current
Instantaneous overcurrent, over temperature (SC), overcurrent (OC), low voltage (LV), overvoltage (OV),
auxiliary interlock (AU), overload/electronic thermal overload (OL), operation error (OP),
Overcurrent stall prevention, regenerative overvoltage stall prevention
–10˚C to +50˚C (non-freezing), 90% RH max (non-condensing)
–25˚C to +65˚C, 95% RH max.
5.9m/s (0.6G) max. based on JIS C0911
Altitude of 1000m or less, indoors, free of corrosive gases and dust
IP20 screen-protected type
MODE DISPLAY (RUN/FAULT)
Mode display Run signal Frequency
Local (Operation panel)
Local (Operation panel)
External (Control terminal block)
External (Control terminal block)
signal Main display
(Examples)
Local (Operation panel)
External (Control terminal block) Frequency
display
Local (Operation panel)
External (Control terminal block)
Instantaneous
overcurrent
during
acceleration or
abnormal
heating of heat
radiating fins
Excessive
Internal DC
voltage
during
acceleration
(overvoltage)
Overcurrent
during
acceleration
Auxiliary
interlock
Undervoltage
Operation
error
Overload
Auxiliary
stop
Note: When the sudden power failure function is selected, "LU" is stored in the trip cause memory and does not send an alarm signal.
PARAMETER SETTINGS
Parameter No.
Parameter name
Parameter object Setting value or code
Factory setting
1st Decel Time
Sets acceleration time: 0.2 Hz to
max. output frequency.
Sets deceleration time: max output
frequency to 0.2 Hz.
Freq. Range
Sets V/F pattern.
V/F (Volts-per-Hertz) Curve
Sets V/F curve.
DC Boost Level
Sets torque boost level.
Overload Function
Selects thermal overload functions.
0 ~40%
0
1
Overload Current
Sets current value.
0.1~100A
Local/Ext. Control
Specifies local or external control.
0~6
Local/Ext. Freq.
Specifies local or external
frequency control (Volts/Current).
1st Accel Time
0000: 40msec., 0.1~1600sec.
005.0
0000: 40msec., 0.1~1600sec.
005.0
50
50
60
FF (50:50Hz, 60:60Hz, FF:FREE)
0
1
(0: Constant torque, 1: Reduced torque)
OFF
0
05
2
without output
Freq. derating
3
with output
Freq. derating
for
special motor
2

0
0
Local
1
VR (10k)
2
0~5V
0
3
0~10V
4
4~20mA
0
Forward operation (No reverse operation)
0
1
Reverse Lockout
Specifies forward-only operation.
Stop Mode Select
Specifies ramp-to-stop or coast-to-stop.
Stop Freq.
Sets stop frequency.
0.2~60Hz
DC Brake Time
Sets DC dynamic brake time.
000:OFF, 0.1~30sec.
000
DC Brake Level
Sets DC dynamic brake level.
0~100
00
Max. Freq.
Sets maximum output frequency.
50~400Hz
Base Freq.
Sets base frequency.
Accel. Freq. Hold
Selects accel stall prevention.
45~400Hz
0
Decel. Freq. Hold
Selects decel stall prevention.
Preset Function Select
Selects multi-speed functions.
Multi-speed Accel/Decel
Multifunction Input Select
Selects functions for SW 1,2 and 3.
Values 0
SW4 Function Select
Selects a function for SW4.
Forward operation/Reverse operation
0
1
Ramp-to-stop
00.50
50.00
50.00
1
No
1
Available
0
0
0
Coast-to-stop
1
No
1
Available
1
1 2
2
Multi-speed linked to Accel/Decel
3 4
5 6
0
7
8 9 10
1
Second Characteristic 2 selected
0
0
0
Speed search
0
Auxiliary stop
0
1
Output Terminal Select
Specifies auxiliary interlock trip or
auxiliary stop.
Selects detection frequency functions.
Selects output terminal functions.
Output RY Select
Selects output relay functions.
Detect Freq.
(Output Terminal)
Sets detection frequency value.
0000,0.2~400Hz
00.50
Detect Freq. (Output RY)
Sets detection frequency value.
0000,0.2~400Hz
00.50
Jog Freq.
Sets jog frequency value.
0.2~20Hz
10.00
Jog.Accel. Time
Sets acceleration time of jog operation.
0000: 40msec., 0.1~1600sec.
005.0
Jog Decel. Time
Sets deceleration time of jog operation.
0000: 40msec., 0.1~1600sec.
005.0
Preset Freq.2
Sets Preset Frequency 2.
0000: 0V stop, 0.2~400Hz
20.00
Preset Freq.3
Sets Preset Frequency 3.
0000: 0V stop, 0.2~400Hz
30.00
Preset Freq.4
Sets Preset Frequency 4.
0000: 0V stop, 0.2~400Hz
40.00
Preset Freq.5
Sets Preset Frequency 5.
0000: 0V stop, 0.2~400Hz
15.00
Preset Freq.6
Sets Preset Frequency 6.
0000: 0V stop, 0.2~400Hz
25.00
Preset Freq.7
Sets Preset Frequency 7.
0000: 0V stop, 0.2~400Hz
35.00
Preset Freq.8
Sets Preset Frequency 8.
0000: 0V stop, 0.2~400Hz
45.00
Accel.Time 2
Sets Accel.Time 2.
0.1~1600sec.
005.0
Decel.Time 2
Sets Decel.Time 2.
0.1~1600sec.
005.0
Accel.Time 3
Sets Accel.Time 3.
0.1~1600sec.
005.0
Decel.Time 3
Sets Decel.Time 3.
0.1~1600sec.
005.0
Accel.Time 4
Sets Accel.Time 4.
0.1~1600sec.
005.0
Decel.Time 4
Sets Decel.Time 4.
0.1~1600sec.
005.0
2nd Base Freq.
Sets base frequency 2.
45~400Hz
60.00
2nd DC Boost Level
Sets boost level 2.
0~40%
Skip Freq. 1
Sets Skip Frequency 1.
0000: OFF,0.2~400Hz
Aux. Interlock
Auxiliary interlock
0
Run
0
Run
1
2
1
2
Arrival Overload
Arrival Overload
3
Frequency
detection
3
Frequency
detection
4
0
Reverse
operation
4
Reverse
operation
5
6
Fault
Fault (When
(when energized) not energized)
6
05
0000
PARAMETER SETTINGS
Parameter No.
Parameter name
Parameter object Setting value or code
Factory setting
Skip Freq.2
Sets Skip Frequency 2.
0000: OFF, 0.2~400Hz
0000
Skip Freq.3
Sets Skip Frequency 3.
0000: OFF, 0.2~400Hz
0000
Skip Freq.Band Width
Sets skip frequency bands.
0: OFF, 1~10Hz
0
Current Limit Function
Sets the current limit function.
00:OFF, 0.1~9.9
00
Wait Time
Selects restart action when the
power is turned on.
Selects instantaneous power
failure function.
Sets waiting time for parameters
50 and 51.
Accel./Decel. Pattern
Sets Accel/Decel patterns.
Lower Freq. Clamp
Sets lower frequency.
0.2~400Hz
Upper Freq. Clamp
Sets upper frequency.
0.2~400Hz
Bias/Gain Function Select
Selects enabling or disabling this function.
Bias Freq.
Sets bias frequency.
-99.9~400Hz
000.0
Gain Freq.
Sets gain frequency.
0000: 0V stop, 0.2~400Hz
60.00
0~5V Output Voltage compensation
Adjusts the 0~5V output signal.
75~125%
Monitor Select
Selects monitoring modes.
Frequency
Line Speed Multiplier
Sets line speed multiplier.
000.1~100
Max. Output Voltage
Sets maximum output voltage to
motor rating.
0:OFF, 1~500V
000
OCS Level
Sets overcurrent stall prevention level.
1~200%
140
Carrier Freq.
Sets carrier frequency.
0.8/1.1/1.6kHz, 2.5/5.0/7.5/10.0/12.5/15.0kHz
Vector Control Select
Sets control system.
V/F control Vector control
Motor Capacity Set
Sets applicable motor capacity.
0.2/0.4/0.7/1.5/2.2/3.7
2/4/6
Motor Constant
Measurement Function
Matches the number of applicable
motor poles.
Selects function for constant motor
measurement.
Voltage Compensation Constant
Sets the voltage compensation constant.
00.01~99.99
Recommended value
Slip Compensation Frequency
Sets the slip conpensation frequency.
-5.00~05.00
03.00
Password
Sets password for data input
(prevents operational errors).
0: OFF, 1~999 Mask code
Setting Data Clear
Clears factory settings.
0/1/2
Baud Rate
Sets communication speed.
300/600/1200/2400/4800/9600
Stop Bit Length
Sets stop bit length.
1/2
1
Parity Check
Sets parity bit.
0/1/2
0
No. of Communication Retries
Sets the number of communication retries.
0~10
0
CR/LF Select Validity
Selects CR or LF.
0/1/2/3
0
Power Loss Start Mode
Ride-Thru Restart
Motor Poles Select
Note: Data can be read only when the power is on.
 The same value as inverter's rating.
0
Run
0
OFF
1
Stop
1
3
Stop
2
0 Hz
restart
1
0
Continued
restart
0.1~100 sec.
0
000.1
1
Linear
Accel/Decel
0
S-shaped
Accel/Decel
0
OFF
00.50
400.0
1
ON
0
0
100
1
2
Frequency
Line speed
3
0
Line speed
030.0
0
Parameters in
2
Run after
wait time
0.8
1
0

4
0
1
OFF
2
Slip Comp.
measurement
Volt Comp.
measurement
3
0
Recommended
constant
000
0
9600
can be set during inverter operation.
FUNCTION SETTING PROCEDURE
When other data is modified.
Lock
Inverter stop
Mode display
Up/Down Shift buttons
Select button
Up/Down Shift buttons
Set button
Lock
Operation prep.
complete
Password enty
See parameter No.71. (Parameter No. modified) (Parameter No. modified)
Press the Lock.
Press the Up/
Press the Select
button to turn off
Down/Shift
button to change
the lock indicator,
buttons to display
the mode display
and the modify
the desired
to the date
display will flash.
parameter.
display.
Press the
Up/Down/ Shift
button to display
the desired
parameter.
Press the Lock.
button to return to
the operation
mode and turn on
the Lock indicator.
Press the Set
button to snter
the value.
Main display
The value disappears
and reappears, and the
mode display flashes.
Operation prep.
completed
Terminal Function Selection by Parameter No.20
on setting parameters
•1. Notes
While the inverter is in operation, only values for the numbers in the
of
parameter settings can be modified.
2. No values can be modified unless the Lock indicator is off.
3. While the inverter is stopped, it cannot be operated unless the Lock indicator
is ON.
4. If the function setting returns to the "Operation Prep. Complete” state during
data modification while an external start signal is received, the error code
"OP” will be displayed, and the inverter will remain inoperative.
5. The values set by pressing the Set button are stored in the memory even if the
Parameter
No.20
Control
terminal
No.14
Control
terminal
No.15
Control terminal
No.16
SW1
SW2
SW3
Multi-speed
function
0
1
2
3
4
Multispeed
function
Multispeed
function
Parameter
No.20
5
Reset input
6
Resetlockout
7
Jog function
Auxiliary stop
output
8
9
10
Control
terminal
No.14
Control
terminal
No.15
SW1
SW2
Multispeed
function
Analog
input
changeover
Control terminal
No.16
SW3
Reset input
Reset lockout
Auxiliary
stop
input
Jog function
Reset input
Reset lockout
Jog function
DIMENSIONS
VF-8E
Single-Phase 230V
1.5 – 2.2 kW
Single-Phase 230V
0.2 – 0.75 kW
4 – ø5 (Mounting hole)
Three-Phase 400V
0.75 – 3.7kW
4 – ø5 (Mounting hole)
WIRING DIAGRAM
VF-8E
h The built-in electronic thermal
relay is for overload protection.
Use the thermal relay with open
phase protection for this purpose.
Th-Ry
MC
MCB
R
S
Inverter
Main circuit
V
+
+
2
2
-
3
3
Current Setting
4-20mA Input
-
-
3
+
+
4
+ -
Voltage Setting
0-5V
0-10V Input
-
SW1
h
1 2 3 4 5 6 7 8 9
17
4
SW4
18
6
13
Relay output
NC COM NO
COM
Control
Protection circuit
10 11 12 13 14 15 16 17 18
Operation status output
Open collector outputs with
50V DC, 50mA max.ratings
h When an inductive load is to be
driven by an open-collector output,
be sure to use a freewheel diode.
C
Run
14
Forward/
reverse
SW2
15
SW3
16
Forward/
stop
Reverse
Reverse/
stop
Stop
Forward/
reverse
Run/
stop
Run
10
Forward/
reverse
11
Stop
12
7
8
9
Fault warning output
No-voltage contact output
250V AC, 0.5A resistance load
h
VF-8X 11-37kw
Bus +
Brake U/T
Bus -
6
+
Brake resistor
DB
5
Set the functions
of switch 1,2,3
and 4 with
parameter No.19,
20 and 21.
Forward
+
4 to 20mA
Input
DB
2
1
DC 0-5V
Output
0 to 5V
0 to 10V
Input
Speed pot
(10kW ,1/4
watt min)
Frequency setting
Volume 10kW
1/4 watt min.
0 to 5V
Output
-
IM
W
T
3
• Control Circuit Wiring
U
Stop
SW4
SW1
SW2
SW3
E
Operation status outputs
Open-collector outputs
with 50V DC, 50mA max.
ratings
OPTION
Product
External frequency
meter (0-5V)
Product number · Specifications · Application · Dimensions
• Dimensions
• Standard specifications
BFV912U
Product No.
Name Plate
Control
specification
5V in full scale
Ambient
temperature and
humidity
–10°C to 50°C +14°F to +122°F
(no freezing)
Max. 90% (no condensation)
Atmosphere
No corrosive gases; no dust (indoors)
Vibration
Max. 0.6G
10
0
0
20
30
40
50
40 60 80
60
20 80120 160 100
200 120
40
240
Hz
0
Input terminal
M3
.118
42
1.654
14.5
.571
38
32
1.496 1.260
2-M2.3 .091
4.5
8±1
Screw
.177 .315±.039
7.6
12.4
.299
.488
45
1.772
32
1.260
Panel cutting drawing
(for installation)
0.5 or less 8 22 MAX.
.020
.315 .866
2-2.8 hole
2-.110
Max. 0.6G
32
1.260
39 hole
1.535
32
1.260
External v olume
• Dimensions
• Standard specifications
Product No.
BFV914U
Method
B special volume
Output
2W
Resister
10k
2.5
.098
10
.394
M9(P=0.75)
M.354(P=.030)
ø2.8
.110
ø24
.945
10
.394
1.5 .059
or more
1
.039
ø6
.236
1.6
.063
20
.787
1.5 .059
or less
22 .866
or less
24 .945
or less
Panel cutting drawing
(for installation)
10
.394
ø9.5
.374
ø3
.118
• Dimensions
Brake resistor
Inverter
Product number
Capacity
200V
400V
Dimensions
L1
L2
W
L1
L2
H
130 122 43.5 20
0.75 to 1.5kW BFV 9161UBFV9164U 5.118 4.803 1.713 .787
182
172 42.5
BFV 9162UBFV9165U 7.165 6.772 1.673 .787
3.7kW
BFV 9163UBFV9166U 9.055 8.661 2.520 .827
220
64
• Standard specifications
Input voltage
Supplied from DB+and
DB–terminals (DC Voltage)
Brake torque
100% (Max. braking time:5 secs)
Repeating rate
Max. 5%
Protection function Protection by means of fuse
7
Ambient
temperature
and humidity
–10°C to 50°C +14°F to +122°F
(no freezing)
Max. 90%RH (no condensation)
Storage
temperature
and humidity
–25°C to 65°C –13°F to +149°F
Max. 95%RH
Max. 90%RH
Vibration
Max. 5.9m/s2 {0.6G}
Atmosphere
No corrosive gases;
no dust (Indoors)
400
15.748
20
2.2kW
230
H
4.2
W .165
21
• Wiring diagram
Power source
Inverter
Main circuit terminal block
screw size M4 screw
∑∑∑
Circuit
breaker
R S T DB DB U V W
L1 L2 L3
T1 T2 T3
+ -
Motor
Grounding
M
Brake resistor
• Installation
5cm
.197 inch
or more
10cm 3.937 inch
or more
5cm
.197 inch
AC
or more
Inverter
Brake resistor
M4 .157 screw
10cm 3.937 inch
or more
1. Install the brake resistor firmly with M4 size screws
2. Allow enough space around the inverter, as shown
above.
3. Install the brake resistor on a metal plate measuring
at least 50cm x 50cm.
Do not install the unit on combustible material such
as wood, and avoid direct contact as it becomes hot
during operation. (Maximum 150°C)
OPTION
Product
Panel holder
Product number · Specifications · Application · Dimensions
Product No.
BFV9060U
n Using the operation panel remotely from the
inverter unit
• The operation panel can be removed from the inverter and mounted
on a remote wall, etc.
(The optional extension cable and panel holder are r equired.)
Extension cable
Inverter
Mounting
screw
Panel holder
Mount base
Extension cable
Cable length
Product No.
1m 3.281ft
BFV9061U
3m 9.843ft
BFV9063U
5m 16.404ft
BFV9065U
Cable band
Operation panel
<Connection>
• Connect one end of the extension cable to the inverter (at the point
where
the operation panel was removed) and the other end to the now
remote operation panel. See diagram.
Caution: Incorrect connector orientation may result in damage to the
inverter.
• Dimensions
• Panel holder
ø4.1
ø.161
ø4.1 ±0.1
ø.161±.004
88
3.465
80
3.150
65
2.560
5.0±0.2
.197±.008
75
2.953
75.0±0.5
2.953±.020
2
.079
33
1.299
61.0±0.5
2.402±.020
61
2.402
Mounting hole dimensions
• Extension cable
L
©
1997 Matsushita Automation Controls Group Europe
PDF-File generated December 5th, 1997,
Data published may change due to technical improvements
7