P-1 Type Fire Alarm Control Panel (Time Delay Type) : RPR-AAS
Features
1. Multi purpose zone configuration
- Versatile zone configuration to suit various alarm needs
2. Easy installation
- By means of ‘Wire Insertion’ terminals
- Wide internal cabinet space of easy wiring
- 180 degree wide panel door opening
3. High reliability
- Improved lightning surge protection
- Improved noise immunity
- Self-diagnostic function (zones open circuit monitored, battery fault warning, etc…)
4. Time delay function
- Designed to minimize any false fire alarm and ensure increased reliability of automatic fire
alarm systems
- False fire alarm is found to often come from heat and/or smoke at the moment during cooking,
smoking or exhaust. Then, the fire alarm signal from every detector is checked if it lasts a
predetermined period of time, based on which true fire alarm is issued
5. More functions
- Easy configuration of local bell and interlock release control which can be monitored from the
zone panel.
- ‘Hands-free’ intercom communication at control panel
- Voltage display for ‘Standby Battery’ test
- Visual representation of fire alarm status by symbolic indication lamp
- Indication lamp alert during ‘Time Delay’ operation
- Zone open circuit monitored
HOCHIKI CORPORATION
SINGAPORE BRANCH OFFICE
629 Aljunied Road #03-16 Cititech Industrial Building
Singapore 389838
Tel : 65-6841-9728 Fax : 65-6841-9781
Email : [email protected]
HEAD OFFICE
10-43 Kamiosaki 2-Chome. Shinagawa-Ku,
Tokyo 141-8660, Japan
Tel : 81-(3)-3444-4116 Fax : 81-(3)-3444-4167
URL : www.hochiki.co.jp
Hochiki Conventional System
Specifications
Type
Model Name
Main
Stand-by Battery
Main Sounder
Operating Temperature Range
Operating Humidity
Material
Color
Number of Zones
Weight
Dimension
Made
RPR-AAS
P1-Type Fire Alarm Control Panel (with Time Delay Function)
RPR-AASZ (60, 70, 80, 90, A0, A1, A2, A3)
AC220V, 50/60Hz
DC 24V, 3.5 AH
Voice synthesis system (speaker : DC15V, 80mA, ø77)
0°C – 40°C
95% or less (No condensation)
Main frame rear panal : Electro-galvanizing steel plate (Thickness : 2.3mm)
Enclosure other than the main frame : Steel plate (Thickness : 1.6mm, Baking finish)
Enclosure : Equivalent color to Munsell 2.5Y9/1, Semi-gloss
Panel : Equivalent color to Munsell 5Y6/0.5, 30%-gloss
60,70,80,90,100,110,120 or 130 Zones
Approx. 125Kg ~ 250Kg
600mm(W) X 2000mm(H) X 450mm(D)
JAPAN
Wiring hole (with cover)
400 X 160
Equipment name plate
100
400
100
2-anchor bolt hole
(Open area)
(Open area)
160
50
70
Fire alarm panel
200
ø15
Fire indication led (red)
Acrylic resin (transparency)
Operation and
indication panel
6-1-034-0193-031
Handle
2000
Takigen A-240-I
1000
Cover
Wiring hole (with cover)
80
400 X 80
4-anchor bolt hole
ø15
3
100
3
400
600
100
50
120
Channel base
35
40
70
250
450
90