FLOWCOMPUTER
WITH TEMPERATURE COMPENSATION FOR
DATASHEET F126-EL – FLOWCOMPUTER
CORRECTED LIQUID VOLUME
Advantages
Signal output
• Robust IP67 (NEMA Type4X) field enclosure.
It is so rugged, you can even stand on it!
• Intrinsically Safe available - ATEX and IECEx
approval for gas and dust applications.
• Programming can be done by your own crew, with
the sensible menu-driven structure, saving cost
and irritation. Know one, know them all!
• Very diverse mounting possibilities: walls, pipes,
panels or directly onto outdoor sensors!
• (0)4 - 20mA / 0 - 10V DC according to
compensated flow rate.
• Scaled pulse output according to accumulated
total.
Signal input
Features
• Calculates compensated flow rate, total and
accumulated total.
• Displays actual line temperature.
• Selectable on-screen engineering units; volumetric
or mass.
• 7 digit resettable total.
• 11 digit accumulated total.
• Explosion/flame proof available.
• Full Modbus communication RS232/485/TTL.
• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.
• Sensor supply 3 / 8.2 / 12 / 24V DC.
1
Flow
• Ability to process all types of flowmeter signals:
Reed-switch, NAMUR, NPN/PNP pulse, Sine wave
(coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC.
Temperature
• PT100 - 2 or 3 wire.
• (0)4 - 20mA / 0 - 10V DC.
Applications
• The F-Series is your first and safest choice for field
mount indicators in safe and hazardous area
applications. Especially in harsh weather
conditions like rain, snow, salty atmosphers and
temperatures between -40°C up to +80°C
(-40°F up to 176°F).
• Applications where nett flow calculation at base
conditions is desired without the influence of
thermal product expansion. For DIN panel mount
indicators, check our D-Series.
General information
Introduction
Signal input
The flowcomputer Model F126-EL has been
developed to calculate corrected liquid volume at
normal conditions for generic products.
The corrected volumetric flow is calculated by
using the thermal expansion coefficient algorithm
stored in the flowcomputer. The reference
temperature can be defined as desired, e.g. 15°C,
20°C or 60°F. A typical application is flow
calculation of water, fuel or chemicals at base
conditions.
The flowcomputer measures the uncorrected
volumetric flow and actual line temperature.
The F126-EL will accept most pulse and analog
input signals for flow. The analog flow input is
available with lineair and square root calculation
and even as 4 - 20mA input loop powered. For
temperature measurement, 2 or 3 wire PT100
elements or sensors with a (0)4 - 20mA / 0 - 10V
DC output signal can be used.
Communication
Display
All process data and settings can be read and
modified manually or through the Modbus
communication link (RS232 / RS485).
Full Modbus functionality remains available for the
Intrinsically Safe version (TTL).
The display has large 17mm (0.67”) and 8mm
(0.31”) digits which can be set to show flow rate,
total and temperature. On-screen engineering
units are easily configured from a comprehensive
menu. The accumulated total can register up to 11
digits and is backed-up in EEPROM memory every
minute.
Hazardous areas
This model has been ATEX and IECEx certified
Intrinsically Safe for gas and dust applications,
with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof
Configuration
All configuration settings are accessed via a
simple operator menu which can be password
protected. Each setting is clearly indicated with an
alphanumerical description, which avoids
confusing abbreviations and baffling codes. Once
familiar with one F-series product, you will be able
to program all models in the series without a
manual. All settings are safely stored in EEPROM
memory in the event of sudden power failure.
Ex d enclosure with ATEX certification is also
available.
Enclosures
Various types of enclosures can be selected, all
ATEX and IECEx approved. As standard the F126-EL
is supplied in an GRP panel mount enclosure,
which can be converted to an IP67 / NEMA Type4X
GRP field mount enclosure by the addition of a
back case. Most popular is our rugged aluminum
field mount enclosure with IP67 / NEMA Type4X
rating. Both European or U.S. cable gland entry
threads are available.
Analog output signal
The calculated flow rate is re-transmitted with the
(0)4 - 20mA or 0 - 10V DC output signal. The
output signal is updated eight times per second
with a filter function being available to smoothen
out the signal if desired.
The output value is user defined in relation to the
flow rate, e.g. 4mA equals to 15Nm3/Hr and 20mA
equals to 2000Nm3/Hr. The output signal can be
passive, active or isolated where the passive
output type will loop power the F126-EL as well.
Overview application F126-EL
Pulse output
Pulse output
The scaleable pulse output, reflects the count
on the accumulated display. The pulse length is
user defined from 0.001 second up to 9.999
seconds. The maximum output frequency is
500Hz. The output signal can be passive NPN,
active PNP or an isolated electro-mechanical
relay.
Temperature
input
2
Analog output
Communication link
Flowmeter
input
F126-EL
0.9"
0.9"
14mm
1 2
/ "NPT
15mm
38mm
F126-EL
24mm 24mm
36mm
36mm
1 2
/ "NPT
15mm
HP
1 2
/ "NPT
HT
6 x M12
HJ
Ø22 ( 7/8") Ø22 ( 7/8") Ø22 ( 7/8")
HK
1.18" 1.18"
Flat bottom, no holes available.
1
/2"NPT
HU
4 x M20 x 1.5
HV
HZ
3
+
Display example - 90 x 40mm (3.5” x 1.6”)
+
+
PL: input loop powered
(terminals GND - 1 - 2 are not available)
PB / PC: battery powered
Internal long life Lithium battery
AP: 8 - 30V DC
Output loop powered
-
ZB: Backlight: 12 - 24V DC
-
PX: 8 - 30V DC
30mm (1.18") 30mm (1.18")
-
Ø12
PM: 115 - 230V AC
24mm 24mm
36mm
36mm
PF: 24V DC
HH
+
M20 x 1,5
Ø20
+
12mm 12mm
-
Ø20
PF: 24V AC
M20 x 1,5
+
+
=
Note: Only available
with Type:P
=
OR: mech. relay
HG
07
08
I+
I+
I+
I+
I+
U
U+
AU: 0 - 10V
I
AP: 4 - 20mA
I-
AI: 4 - 20mA
I-
AF: 4 - 20mA
I
AB: 0 - 20mA
I
-
-
+
I+
I+
A - PL: 4 - 20mA
U+
U: 0 - 10V
A: (0)4 - 20mA
+
P: active signal
P: namur
P: PNP
+
+
+
+
P: reed switch / NPN
11
U+
TU: 0 - 10V
I+
TA: (0)4 - 20mA
12
+
+
14
13
Ø16
10
09
P: coil
Ø22 ( 7/8")
OT: passive trans.
25mm 25mm
-
HO
HF
AA: 4 - 20mA
M16 x 1,5
Ø20
06
30mm 30mm
05
HN
15
HD
OA: active 24V DC
M20 x 1,5 PG9
PD - XI: 16 - 30V DC
12mm 12mm
16
GRP
PD: 8 - 24V DC
M20 x 1,5
Ø16
04
25mm
HM
HE
03
25mm
HL
17
112 mm (4.40")
02
/2"NPT
18
19
21
+
TP: PT100 3-wire
+
TP: PT100 2-wire
20
22
TEMPERATURE INPUT
Ø 7mm (0.27")
TEMPERATURE INPUT
Aluminum & GRP field / wall mount enclosures
01
30mm 30mm
23
24
panel cut-out
00
M20 x 1,5
25
26
27
A
A
DTR
+12V
RXD
CT: TTL Intrinsically Safe
CI: RS485 - 4 wire
28
RXD
CH: RS485 - 2 wire
DTR
+12V
CB: RS232
TXD
B
B
TXD
29
COMMUNICATION
98 (3.86")
115 (4.53")
FLOWMETER INPUT
60 mm (2.36")
130 mm (5.12")
PD: 8 - 24V AC
1
ANALOG OUTPUT
1.18"
22,50mm
Aluminum
PULSE OUTPUT
M16 x 1,5
Ø 7mm (0.27")
POWER REQUIREMENTS
/ "NPT
HA
22,50mm (0.9")
75 mm (2.95")
22,50mm
30mm 30mm
22,50mm
HB & HC enclosures
17mm
0.9"
130 mm (5.12")
14mm
1 2
22,50mm
29 mm
(1.14")
22,50mm (0.9")
22,50mm
1.18"
22,50mm
PG9
17mm
31 mm
(1.22")
15mm
120 mm (4.72")
Y
30
Z
31
Aluminum & GRP panel mount enclosure
+
16mm
120 mm (4.72")
Dimensions enclosures
Terminal connections
Typical wiring diagram F126-P-(AP)-CH-EL-(OT)-PB-(PX)-TP
Typical wiring diagram F126-P-AP-CH-EL-OT-PX-TA
BATTERY POWERED
TERMINAL CONNECTORS
F100-series
OUTPUT LOOP POWERED
TERMINAL CONNECTORS
F100-series
Modbus communication type CH: RS485 - 2 wire
29
29
A
28
Common ground
26
Common ground
28
A
B
26
B
Modbus communication type CH: RS485 - 2 wire
22
Signal
Temperature input
type TP:
PT100 3 - wire
21
Signal
20
Supply
Common ground
10
14
Supply *
11
Circuit depends on
type of signal
11
Flowmeter input
type: P
pulse
Signal
Signal
Common ground
09
Circuit depends on
type of signal
Common ground
Supply *
12
13
Signal
Flowmeter input
type: P
pulse
10
AP-PX will power the unit;
(the battery will be disabled
automatically untill power
is disconnected).
Temperature input
type TA:
(0)4 - 20mA
Supply *
09
Circuit depends on
type of signal
Please note: AP-PX may be used
in combination with the battery!
08
123456
Common ground
*Supply voltage: 1.2 / 3.2V DC to sensor
00
01
Power supply type PX:
8 - 30V DC
(not used in this example)
Pulse output
type OT:
passive transistor
05
Common ground
8 - 30V DC
Analog output type AP: passive 4 - 20mA (loop powered)
e.g. counter
06
07
07
Pulse output type OT:
passive transistor
(not used in this example)
05
06
Common ground
00
01
Common ground
indicator
Common ground
-
08
+
Common ground
Analog output type AP:
(not used in this example)
Power supply type PX:
8 - 30V DC
(not used in this example)
*Supply voltage: 1.2 / 3.2V DC to sensor
4
F126-EL
Typical wiring diagram F126-P-AI-CI-EL-OA-PD-TA
24V AC / DC POWER SUPPLY
RXD
28
DTR
+12V
26
Common ground
29
TXD
26
Common ground
Modbus communication type CB: RS232
27
31
A
Modbus communication type CI: RS485 - 4 wire
29
B
115 - 230V AC POWER SUPPLY
TERMINAL CONNECTORS
F100-series
28
Y
30
TERMINAL CONNECTORS
F100-series
Z
Typical wiring diagram F126-A-AA-CB-EL-OX-PM-TP
22
Signal
Temperature input
type TP:
PT100 3 - wire
21
Signal
14
Supply *
Signal
13
12
08
8 - 30V DC
00
Analog output type AA:
active 4 - 20mA
11
Note: Digital output not available with Type: A / U
02
Power supply type PM:
115 - 230V AC
01
Power supply type PD:
8 - 24V AC / DC
8 - 24V DC
-
-
02
Main supply
8 - 24V AC
+
+
01
10
06
Pulse output type OA:
active 24V DC pulse
Common ground
*Supply voltage: 1.2 / 3.2 / 8.2 / 12 / 24V DC to sensor
F126-EL
indicator
05
e.g. counter
05
06
07
-
Common ground
-
Common ground
123456
Common ground
Analog output type AI:
passive isolated 4 - 20mA
09
09
Common ground
indicator
Flowmeter input type A:
(0)4 - 20mA
Signal
08
Flowmeter input
type: P
pulse
+
Common ground
10
Signal
Supply *
07
11
Circuit depends on
type of signal
Supply *
00
Common ground
Circuit depends on
type of signal
Temperature input
type TA:
(0)4 - 20mA
+
Circuit depends on
type of signal
20
Supply
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
5
N
L1
Hazardous area applications
Configuration example IIB / IIIC and IIC
F126-P-(AP)-(CT)-EL-(OT)-PC-TP-XI - Battery powered unit
The F126-EL-XI has been certified according
ATEX and IECEx by DEKRA for use in Intrinsically
Safe applications with an ambient temperature
of -40°C to +70°C (-40°F to +158°F).
• The ATEX markings for gas and dust
applications are:
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dust
applications are: Ex ia IIC/IIB T4 Ga and
Ex ia IIIC T100 °C Da.
It is allowed to connect up to four barriers in
IIB/IIIC applications or one barrier in IIC
applications. Consult the certificate for the
maximum input and output values of the
circuits. Full functionality of the F126-EL remains
available, including 4 - 20mA output according
to the flow rate and Modbus communication
(type CT). Power supply type PD-XI offers a 8.2V
sensor supply e.g. for one Namur sensor and a
temperature sensor. An ATEX approved flame
proof Ex d enclosure is available as well. Please
contact your supplier for further details.
HAZARDOUS AREA
29
RXD
28
DTR
+12V
Common ground
SAFE AREA
Modbus communication type CT: TTL
Possible for battery powered applications
(not used in this example).
Please note: communciation type CT
is not allowed in IIC applications.
26
TXD
27
TERMINAL CONNECTORS
F100-series
22
Signal
Temperature input
type TP:
PT100 3 - wire
21
Signal
20
Supply
11
Supply *
Common ground
Ci is negligibly
small
Flow meter input
type: P
pulse
Analog output type AP:
passive 4 - 20mA
(not used in this example).
Pulse output type OT:
passive transistor
(not used in this example)
05
06
Common ground
07
08
Common ground
10
Signal
09
Circuit depends on
type of signal
Certificate of conformity KEMA 03ATEX1074 X
• IECEx DEK 11.0042X
Please note: type AP may be used
in combination with the battery
(type PC), but only in IIB applications!
Common ground
00
01
AP will power the unit
(output loop powered);
the battery will be disabled
automatically till power
is disconnected).
* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.
6
F126-EL
Configuration example IIB / IIIC and IIC - F126-P-AP-(CT)-EL-OT-(PX)-TP-XI - Output loop powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F100-series
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
Please note: communciation type CT is not allowed in IIC applications.
+
27
26
Common ground
Po=max 850mW
e.g. PC
For example: MTL5051
-
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
* Note: Communication only allowed when configured as IIB / IIIC.
22
Signal
Temperature input
type TP:
PT100 3 - wire
21
Signal
11
Supply *
Flow meter input
type: P
pulse
09
Analog output type AP:
passive 4 - 20mA (output loop powered)
06
Pulse output type OT:
passive transistor
123456
e.g. counter
05
Ci is negligibly
small
Uo=max 30V
Io=max 100mA
07
08
Ci = 17nF
Po=max 750mW
Uo=max 30V
-
Common ground
e.g. indicator
-
Common ground
Ci is negligibly
small
+
Common ground
10
Signal
+
Circuit depends on
type of signal
20
Supply
Po=max 750mW
Io=max 100mA
POWER SUPPLY
e.g. MTL 5525
and / or
REPEATER
e.g. MTL 5541
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. indicator
123456
e.g. counter
01
Note: above values are safety values.
Consult the technical specification for operational values.
PX: Not used in this example
00
Common ground
* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.
F126-EL
7
Configuration example IIB / IIIC and IIC - F126-A-AF-(CT)-EL-OX-PD-TA-XI - Power requirement 16 - 30V DC
HAZARDOUS AREA
TERMINAL CONNECTORS
F100-series
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
Please note: communciation type CT is not allowed in IIC applications.
Po=max 850mW
e.g. PC
For example: MTL 5051
26
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
* Note: Communication only allowed when configured as IIB / IIIC.
14
Supply *
13
Ci is negligibly
small
12
Common ground
11
Supply *
Flow meter input type: A
(0)4 - 20mA
Signal
Ci is negligibly
small
Ci = 17nF
Analog output type AF:
passive floating 4 - 20mA
e.g. indicator
07
08
Common ground
10
Circuit depends on
type of signal
Temperature input type: TA
(0)4 - 20mA
Signal
09
Circuit depends on
type of signal
TOTAL Co OF ALL CONNECTED
ANALOG APPARATUS IN IIC
APPLICATIONS MAY NOT
EXCEED 66nF MINUS 17nF
(17nF IS USED BY THE ANALOG
OUTPUT SIGNAL TERMINAL 7 + 8).
02
Note: Digital output not available with Type: A / U
Power supply type PD: 16 - 30V DC
(please note: PD and battery supply (type PC) is NOT allowed in IIC applications).
00
Uo=max 30V
Io=max 100mA
-
Common ground
01
+
Main supply
Po=max 750mW
POWER SUPPLY
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).
8
F126-EL
Configuration example IIB / IIIC - F126-A-AF-CT-EL-OX-(PC)-(PD)-TA-XI - Power requirement 16 - 30V DC or battery powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F100-series
SAFE AREA
TXD
29
Modbus communication type CT: TTL
28
Uo=max 30V
RXD
26
14
12
Supply *
11
Ci is negligibly
small
+
09
e.g. indicator
Ci = 17nF
Uo=max 30V
Io=max 100mA
-
10
Po=max 750mW
REPEATER
For example
MTL 5541
Flow meter input type A:
(0)4 - 20mA
Signal
Analog output type AF:
passive floating 4 - 20mA
Po=max 750mW
Uo=max 30V
Io=max 100mA
07
-
08
Uo=max 30V
Io=max 100mA
+
Circuit depends on
type of signal
Ci is negligibly
small
-
13
Signal
Common ground
For example: MTL5051
Temperature input type TA:
(0)4 - 20mA
+
Circuit depends on
type of signal
Supply *
Common ground
Po=max 850mW
e.g. PC
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
REPEATER
For example
MTL 5541
REPEATER
e.g. MTL 5541
Po=max 750mW
e.g. indicator
Note: above values are safety values.
Consult the technical specification for operational values.
01
00
Common ground
Uo=max 30V
Io=max 100mA
Power supply type PD: 16 - 30V DC
-
Main supply
Due to analog output type AF, the unit has to be powered with
battery type PC or with external power supply type PD.
+
02
Note: Digital output not available with Type: A / U
Po=max 750mW
POWER SUPPLY
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).
F126-EL
9
Data protection
Technical specification
Type
General
Display
Type
Dimensions
Digits
Refresh rate
Option ZB
Note ZB
Password
High intensity reflective numeric and
alphanumeric LCD, UV-resistant.
90 x 40mm (3.5” x 1.6”).
Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.
User definable: fast, 1sec , 3sec, 15sec, 30sec, off.
Transflective LCD with white LED-backlight.
Good readings in full sunlight and darkness.
Only available for safe area applications.
Enclosure
General
Window
Sealing
Control keys
Polycarbonate window.
Silicone.
Three industrial micro-switch keys. UV-resistant
silicone keypad.
Aluminum wall / field mount enclosures
Ambient temperature
General
Safe areas
-40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Dimensions
Weight
Power requirements
Analog output loop powerd, 8 - 30V DC.
Power consumption max 0.5 Watt.
Type PB
Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.
(requires PD, PL or PX)
Type PC
Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5
years. (requires XI and PD or PX)
Type PD
8 - 24V AC / DC ± 10%. Power consumption max. 10
Watt. Intrinsically Safe: 16 - 30V DC; power
consumption max. 0.75 Watt.
F
Type P
24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type PL
Input loop powered from sensor signal 4 - 20mA
(type “A”) - requires types AI and OT (not Xi).
Type PM
115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type PX
8 - 30V DC. Power consumption max. 0.5 Watt.
Type ZB
12 - 24V DC ± 10%. Power consumption max. 1 Watt.
Note PB/PF/PM Not available Intrinsically Safe.
Note PF/PM
The total consumption of the sensors and outputs
may not exceed 400mA @ 24V.
Note
For Intrinsically Safe applications, consult the safety
values in the certificate.
EEPROM backup of all settings. Backup of running
totals every minute. Data retention at least 10 years.
Configuration settings can be password protected.
Type HA
Type HL
Type HM
Type HN
Type HO
Type HP
Type HT
Type HU
Type HV
Type HZ
Type AP
Die-cast aluminum wall/field mount enclosure IP67 /
NEMA Type4X with 2-component UV-resistant coating.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
1100 gr.
Cable entry: 2 x PG9 and 1 x M20.
Cable entry: 3 x 1/2" NPT.
Cable entry: 2 x M16 and 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2" NPT.
Cable entry: 3 x 1/2" NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
GRP wall / field mount enclosures
General
Dimensions
Weight
Type HD
Type HE
F
Type H
Type HG
Type HH
Type HJ
Type HK
GRP wall/field mount enclosure IP67 / NEMA Type4X,
UV-resistant and flame retardant.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
600 gr.
Cable entry: no holes.
Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8").
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8").
Flat bottom, cable entry: no holes.
Sensor excitation
Type PB/PC/PX
Note
Type PD
Type PD-XI
Note
Type PF / PM
3V DC for pulse signals and 1.2V DC for coil pick-up.
This is not a real sensor supply. Only suitable for
sensors with a very low power consumption like coils
(sine wave) and reed-switches.
1.2 / 3 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.
1.2 / 3 / 8.2V DC - max. 7mA @ 8.2V DC and mains
power supply voltage (as connected to terminal 1).
In case PD-XI and signal A or U: the sensor supply
voltage is according to the power supply voltage
connected to terminal 1. The sensor supply of the
second analog input is fixed 8.2V DC.
1.2 / 3 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.
Panel mount enclosures
Dimensions
Panel cut-out
Type HB
Weight
Type HC
Weight
Hazardous area
Intrinsically Safe (Type XI)
ATEX
certification
IECEx
certification
Ambient Ta
Terminal connections
Type
Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Directives & Standards
EMC
Low voltage
RoHS
ATEX / IECEx
IP & NEMA
Directive 2014/30/EU, FCC 47 CFR part 15.
Directive 2014/35/EU
Directive 2011/65/EU
Directive 2014/34/EU, IEC 600079-0, IEC 60079-11.
EN 60529 & NEMA 250
130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
115 x 98mm (4.53" x 3.86") L x H.
Die-cast aluminum panel mount enclosure IP65 /
NEMA Type4X.
600 gr.
GRP panel mount enclosure IP65 / NEMA Type4X,
UV-resistant and flame retardant.
450 gr.
II 1 G Ex ia IIB/IIC T4 Ga.
II 1 D Ex ia IIIC T100 °C Da.
Ex ia IIC/IIB T4 Ga.
Ex ia IIIC T100 °C Da.
-40°C to +70°C (-40°F to +158°F).
Explosion proof (Type XF)
ATEX certification
F
Type X
Weight
Note
10
II 2 G / Ex d IIB T5 Gb.
II 2 D / Ex t IIIB T100 °C Db.
Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.
Appr. 15kg.
IECEx available on request.
F126-EL
Signal inputs
Flowmeter
Digital output
Function
Frequency
Type P
Coil / sine wave (HI: 20mVpp or LO: 80mVpp sensitivity selectable), NPN/PNP, open collector, reedswitch, Namur, active pulse signals 8 - 12 and 24V DC.
Frequency
Minimum 0Hz - maximum 7kHz for total and flow rate.
Maximum frequency depends on signal type and
internal low-pass filter. E.g. reed switch with
low-pass filter: max. frequency 120Hz.
K-Factor
0.000010 - 9,999,999 with variable decimal position.
Low-pass filter Available for all pulse signals.
Option ZF
coil sensitivity 10mVpp.
Type A
(0)4 - 20mA. Analog input signal can be scaled to any
desired range within 0 - 20mA.
Type U
0 - 10V DC. Analog input signal can be scaled to any
desired range within 0 - 10V DC.
Accuracy
Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.
Span
0.000010 - 9,999,999 with variable decimal position.
Update time
Four times per second.
Voltage drop
Type A: 2.5V @ 20mA.
Load impedance Type U: 3kOhm.
Relationship
Linear and square root calculation.
Note
For signal type A and U: external power to sensor is
required; e.g. type PD.
Temperature
Accuracy
Update time
Type TA
Span
Offset
Voltage drop
Type TP
Range
Option ZV
Type TU
Type OA
Type OR
Type OT
Note:
Communication option
Function
Protocol
Speed
Addressing
Type CB
Type CH
Type CI
Type CT
Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.
Four times per second.
(0)4 - 20mA. Analog input signal can be scaled to
any desired range within 0 - 20mA.
0.000010 - 9,999,999 K with variable decimal position.
Digits
11 digits.
Units / decimals According to selection for total.
Note
Can not be reset to zero.
Line temperature
Digits
Units
Decimals
0.00 - 99,999.99 K.
2.5V @ 20mA.
2 or 3 wire PT100.
-100°C to +200°C (-148°F to 392°F).
Accuracy 3°C (5.4°F).
Range: -200°C to +800°C (-328°F to 1832°F).
Accuracy 3°C (5.4°F).
0 - 10V DC. Analog input signal can be scaled to
any desired range within 0 - 10V DC.
0.000010 - 9,999,999 K with variable decimal position.
Update time
Type AA
Type AB
F
Type A
Type AI
Type AP
Type AU
F126-EL
6 digits.
°C, °F or K.
1.
Operator functions
Displayed
functions
• Compensated flow rate.
• Compensated total and accumulated total.
• Actual line temperature.
• Total can be reset to zero by pressing the CLEARkey twice.
Total
Digits
Units
Decimals
Note
For signal TA and TU: power supply to temperature
sensor is required; e.g. PD.
7 digits.
L, m3, GAL, USGAL, kg, lb, bbl, no unit.
0 - 1 - 2 or 3.
Total can be reset to zero.
Flow rate
Signal outputs
Analog output
Function
Accuracy
Reading display information, reading / writing all
configuration settings.
Modbus RTU.
1200 - 2400 - 4800 - 9600 baud.
Maximum 255 addresses.
RS232
RS485 2-wire
RS485 4-wire
TTL Intrinsically Safe.
Operational
Accumulated total
Span
Offset
0.00 - 99,999.99 K.
Load impedance 3kOhm.
Note 1
Pulse output - transmitting accumulated total.
Max. 500Hz. Pulse length user definable between
0.001 second up to 9.999 seconds.
One active 24V DC transistor output (PNP);
max. 50mA per output (requires -PD, PF, PM or PX).
One electro-mechanical relay output - isolated;
max. switch power 230V AC (N.O.) - 0.5A per relay
(requires PF or PM).
One passive transistor output (NPN) - not isolated.
Max. 50V DC - 300mA per output.
Digital output only available for Type: P
(pending for Type: A / U)
Digits
Units
Transmitting compensated flow rate.
10 bit. Error < 0.05%. Analog output signal can be
scaled to any desired range.
Eight times per second.
Active 4 - 20mA output (requires PD, PF, PM or PX).
Active 0 - 20mA output (requires PD, PF, PM or PX).
Passive floating 4 - 20mA output for Intrinsically
Safe applications (requires XI + PD or PX).
Passive galvanically isolated 4 - 20mA output - also
available for battery powered models.
Passive 4 - 20mA output - not isolated. Unit will be
loop powered.
Active 0 - 10V DC output (requires PD, PF, PM or PX).
Decimals
Time units
7 digits.
mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf,
Nm3, Nl, igal - no units.
0 - 1 - 2 or 3.
/sec - /min - /hr - /day.
Flow equations
Type EL
Formula
Normal temp.
11
Corrected liquid volume.
Qnormal = Q x (1 + _ (Tnormal - T)) where _ = thermal
expansion coefficient.
Default: 273.15 K - any temperature can be set.
Ordering information
Standard configuration: F126-P-AP-CX-EL-HC-OT-PX-TA-XX-ZX.
Ordering information:
F126
-_ -A _
Flowmeter input signal
A
P
U
-C _
-EL
-H _
-O _
-P _
-T _
-X _
-Z _
(0)4 - 20mA input. (Digital ouput is pending)
Pulse input: coil, npn, pnp, namur, reed-switch.
0 - 10V DC input. (Digital ouput is pending)
Analog output signal
AA
AB
F
A
AI
AP
AU
Active 4 - 20mA output - requires PD, PF, PM or PX.
Active 0 - 20mA output - requires PD, PF, PM or PX.
I.S. floating 4 - 20mA output - requires XI + PD or PX.
Isolated 4 - 20mA output.
Passive 4 - 20mA output, loop powered unit.
Active 0 - 10V DC output - requires PD, PF, PM or PX.
Communication
CB
CH
CI
CT
CX
Communication RS232 - Modbus RTU.
Communication RS485 - 2wire - Modbus RTU.
Communication RS485 - 4 wire - Modbus RTU.
Intrinsically Safe TTL - Modbus RTU.
No communication.
EL
Corrected liquid volume.
HB
HC
Aluminum enclosure.
GRP enclosure.
Flow equations
Panel mount enclosures - IP65 / NEMA Type4X
GRP field / wall mount enclosures - IP67 / NEMA Type4X
HD
HE
F
H
HG
HH
HJ
HK
Cable entry: no holes.
Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8”).
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8”).
Flat bottom, cable entry: no holes.
Aluminum field / wall mount enclosures - IP67 / NEMA Type4X
HA
HL
HM
HN
HO
HP
HT
HU
HV
HZ
Cable entry: 2 x PG9 + 1 x M20.
Cable entry: 2 x 1/2”NPT.
Cable entry: 2 x M16 + 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2”NPT.
Cable entry: 3 x 1/2”NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
OA
OR
OT
One active transistor outputs - requires PD, PF, PM or PX.
One mechanical relay outputs - requires PF or PM.
One passive transistor outputs - standard configuration. requires P
Digital output signal
Power requirements
PD
F
P
PL
PM
PX
8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.
24V AC/DC + sensor supply.
Input loop powered from sensor signal type “A” - requires AI (not XI).
115 - 230V AC + sensor supply.
Basic power supply 8 - 30V DC (no real sensor supply).
Additional battery supply (optional)
PB
PC
Lithium battery powered - requires PD, PL or PX.
Lithium battery powered - Intrinsically Safe - requires XI, and PD or PX.
TA
TP
TU
(0)4 - 20mA input.
PT100 input.
0 - 10V DC input.
Temperature input signal
XI
F
X
XX
Intrinsically Safe, according ATEX and IECEx.
Ex d enclosure - 3 keys according ATEX.
Safe area only.
ZB
F
Z
ZV
ZX
Backlight.
Coil input 10mVpp.
PRTD-range -200°C / +800°C.
No options.
Other options
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
Specifications are subject to change without notice.
Fluidwell bv
P.O. Box 6
5460 AA - Veghel - The Netherlands
Telephone: +31 (0)413 343 786
Telefax: +31 (0)413 363 443
email: [email protected]
Internet: www.fluidwell.com
12
Copyright: Fluidwell bv - 2017 - F126EL-DATA-EN-V1704
Hazardous area
Related documents