Annex (AA)
Compliance Technical Sheet
The following Technical data shall be furnished and filled by the bidders:
1-General
UNDP Specifications
Ambient temperature :
Maximum:55/C
Minimum:-10/C
Relative Humidity : around 60% at maximum temperature
Altitude: 1000M above MSL
System Voltage : 33/11KV
No of phase : 3PH
Frequency: 50Hz
Make: Original manufacturer (Local Assembled Not acceptable)
Type: ABB, Schneider, Siemens or equivalent
1-a 33KV system
UNDP Specifications
Norma Voltage :
33000 Volt
Highest system voltage :36000 Volt
System : 3Ph , 3wire , 50Hz
Short circuit level : 25KA r.m.s at 33000 volts
1-b) 11KV system
UNDP Specifications
Norma Voltage :
11000 Volt
Highest system voltage :12000 Volt
System : 3Ph , 3wire ,with natural earthed through an earthing
resistance of 21.1 ohm to limit earth fault current to 300amps
Short circuit level : 25KA r.m.s at 11000 volts
1-c) L.T system
UNDP Specifications
Norma Voltage :
416volt +6%-10%
System : 3Ph , 4wire ,with natural solidly earthed
Short circuit level : 25KA r.m.s at 11000 volts
Short circuit level : 35KA r.m.s at 400Volt
Bidders Offered specification
Bidders Offered specification
Bidders Offered specification
Bidders Offered specification
2- Circuit breaker
UNDP Specifications
1. Manufacturer/Make: ABB, Schneider, Siemens or equivalent
2. Type: Vacuum type
12KV
36KV
3. Normal rated voltage
4. Normal current rating
1250/630
1250
Breaking capacity:
5.
25
25
a- Symmetrical KA (r.m.s)
Bidders Offered specification
11kv C.B
33KV C.B
6.
7.
8.
9.
10.
11.
b- Symmetrical MVA
c- Symmetrical KA (r.m.s)
Making capacity : KA peak
Rated short time current : in 1sec
Capacitive breaking current: Amps
Capacitive making current
Impulse voltage withstand 1.2/50
wave: kV crest
Standard 1 min 50 Hz withstand
voltage: kV (rms)
500
25 to 28
62----65
25KA
10-25KA
20-25 kA
1500
25 to 28
62---65
25KA
10-50KA
20-62.5 kA
28
70
28
70
12.
Temp rise of main contacts continuous
operation at rated current :Amps
45-69 K
45-69 K
13.
Opening time:
a- Without current: m sec
b- At 100% breaking current: m sec
35-60
35-60
35-60
35-60
Spring
powered
stored
energy
Spring
powered
stored
energy
14.
Type of closing mechanism:
15.
16.
17.
Submit Manufacturer certification :
Submit Single line diagram :
Submit Detail drawing brochure catalogue :
3-Current Transformer (C.T)
1.
2.
3.
4.
5.
UNDP Specifications
Manufacturer/Make: ABB, Schneider, Siemens or equivalent
Type: Resin Cast Dry type
Standard: IEC
Ambient temperature : -5-------+40
Insulation Class : E
11KV
6.
Impulse voltage withstand (1.2/50
wave) :kV (peak)
7.
9.
10.
11.
Normal current rating
Breaking capacity:
a- Symmetrical KA (r.m.s)
b- Symmetrical MVA
c- Symmetrical KA (r.m.s)
Making capacity : KA peak
Rated short time current : in 1sec
Capacitive breaking current: Amps
12
Capacitive making current
13
Impulse voltage withstand 1.2/50
wave: kV crest
8.
Bidders Offered specification
33KV
75
170
1250/630
1250
25
500
25 to 28
62----65
25KA
10-25KA
20-25 kA
25
1500
25 to 28
62---65
25KA
10-50KA
20-62.5
kA
28
70
11kv
33KV
C.B
14.
Standard 1 min 50 Hz withstand
voltage: kV (rms)
15.
Temp rise of main contacts continuous
operation at rated current :Amps
28
70
45-69 K
45-69 K
Opening time:
35-60
a- Without current: m sec
35-60
b- At 100% breaking current: m sec
17 Submit Manufacturer certification :
18. Submit Single line diagram :
19. Submit detailed drawing brochure catalogue :
16.
35-60
35-60
4-Voltage transformer
UNDP specifications
1. Manufacturer/Make: ABB, Schneider, Siemens or equivalent
2. Type: Resin Cast Dry type
3. Standard: IEC
4. Ambient temperature : -5-------+40
5. Insulation Class : E
11KV
33KV
#
50
100
6. Rated output: VA
7. Rated Frequency:
50
50
(3phase/si (3phase/
ngle
8. Number of phases:
single
phase)
phase)
9.
10.
Accuracy class:
Fuse protection: Rated primary side
1
1
17.5 kV-2
A
36 kV-2
A
25
170
28
70
Bidders offered specifications
11kv
33KV
Insulation level:
11.
a- Impulse withstand voltage: kV
(peak)
b- I min. power frequency
withstand voltage :kV (rms)
12.
13.
Submit Manufacturer certification :
Submit Detail drawing brochure catalogue :
4-Switchgear
1.
2.
3.
4.
5.
#
UNDP specifications
Make: ABB, Schneider, Siemens or equivalent
Type: original manufacturer, not assembly type
Bidders offered specifications
Standard: IEC
Ambient temperature : 55C
Insulation Class :
11KV
33KV
11kv
33KV
UNDP specifications
6.
7.
8.
9.
Bus Bar Rating Current A
Frequency :Hz
Insulation of Bus bars
Min clearance between phases: mm
Min clearance between phases &
10.
earth: KV
11. Service voltage: KV
12. Highest voltage: KV
13.
14.
15.
16.
17.
Bidders offered specifications
1250
630
50
Air
110
50
200
28
70
11
12
75
33
36
170
impulse withstand voltage: KV (peak)
Min. power frequency withstand
28
voltage: KV (rms )
Submit Manufacturer certification :
Submit Single line diagram :
Submit Detail drawing brochure catalogue :
Air
70