CONSTRUCTING WITH KNOWLEDGE.
SERVICE WITH INTEGRITY AND SAFETY.®
12/20/2016
SINCE 1920
Cranes and Electricity
LOOK UP !
5500 BINGHAM STREET
PHILADELPHIA, PA 19120
TEL: 215-722-1000
FAX: 215-745-6229
Power distribution lines are a major hazard in electrocution of equipment operators. When
power lines are in the area, care must be taken. Below are just a few of the many items to
check for crane operation.
If any part of the crane operating within the work zone, could get within 20 feet of a power line
(50 feet if >350kV), then one of the following 3 requirements must be met.
1) Contact the utility owner/operator and obtain documentation that the power line has been
de-energized and visibly grounded at the worksite.
2) Ensure that no part of the equipment (crane, load line, and load) operates within 20 feet of
the power line and implement the Encroachment Prevention Plan Checklist (Attachment A);
or
3) Determine the minimum approach distance allowed under the Minimum Clearance
Distances Table and determine the lines voltage. If any part of equipment operating within
its maximum working radius in the work zone could get closer to the minimum approach
distance then implement the Encroachment Prevention Plan Checklist (Attachment A).
Minimum Clearance Distances Table: Set-Up
Voltage (nominal, kV, AC)
up to 50
over 50 to 200
over 200 to 350
over 350 to 500
over 500 to 750
over 750 to 1,000
over 1,000
Minimum clearance distance
(feet)
10
15
20
25
35
45
***
*** As established by operator or registered professional
engineer who is a qualified person for electrical power
transmission and distribution.
CONSTRUCTION MANAGEMENT
GENERAL & MECHANICAL CONSTRUCTION
HVAC SERVICE / FACILITIES MAINTENANCE & OPERATION
EXCHANGER HYDROBLASTING / EXTRACTION SERVICES
API TANK CONSTRUCTION & REPAIR
ELECTRICAL, SOLAR & RENEWABLE ENERGY
www.jjwhiteinc.com
PHILADELPHIA, PA
NEW CASTLE, DE
SOUTH BEND, IN
TOLEDO, OH
CONSTRUCTING WITH KNOWLEDGE.
SERVICE WITH INTEGRITY AND SAFETY.®
SINCE 1920
5500 BINGHAM STREET
PHILADELPHIA, PA 19120
TEL: 215-722-1000
FAX: 215-745-6229
CONSTRUCTION MANAGEMENT
GENERAL & MECHANICAL CONSTRUCTION
HVAC SERVICE / FACILITIES MAINTENANCE & OPERATION
EXCHANGER HYDROBLASTING / EXTRACTION SERVICES
API TANK CONSTRUCTION & REPAIR
ELECTRICAL, SOLAR & RENEWABLE ENERGY
www.jjwhiteinc.com
PHILADELPHIA, PA
NEW CASTLE, DE
SOUTH BEND, IN
TOLEDO, OH