Download Electrical Earth Faults

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Electrical substation wikipedia , lookup

Stray voltage wikipedia , lookup

Single-wire earth return wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Fault tolerance wikipedia , lookup

Ground (electricity) wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
Earth Faults
If an earth fault occurs on the insulated pole of an ‘EARTHED DISTRIBUTION
SYSTEM’ it would be equivalent to a ‘short circuit’ fault across the load via the
ship’s hull.
The resulting large earth fault current would immediately ‘blow’ the fuse in the
line conductor. The faulted electrical equipment would be immediately isolated
from the supply and so rendered SAFE, but the loss of equipment could create a
hazardous situation, especially if the equipment was classed ESSENTIAL, e.g.
loss of steering gear. The large fault current could also cause arcing damage at
the fault location.
An earth fault ‘A’ occurring on one line of an ‘INSULATED DISTRIBUTOIN
SYSTEM’ will not cause any protective gear to operate and the system would
continue to function normally. This is the important – equipment still operates.
The single earth fault does not provide a complete circuit so no earth fault
current will exist.
If an earth fault ‘B’ developed on another line, the two earth faults together
would be equivalent to a short-circuit fault (via the ship’s hull) and the resulting
large current would operate protection devices and cause disconnection of
perhaps essential services creating a risk to the safety of the ship.
An insulated distribution system requires TWO earth faults on TWO different
lines to cause an earth fault current.
An earthed distribution system requires only ONE earth fault on the LINE
conductor to create an earth fault current.
An insulated system is, therefore, more effective than an earthed system in
maintaining continuity of supply to equipment. Hence its adoption for most
marine electrical systems.
Note: Double-pole switches with fuses in both lines are necessary in an insulated
single-phase circuit.
High voltage systems (3.3 kV and above) on board ship are normally ‘earthed’.
Such systems are normally earthed via resistor connecting the generator neutrals
to earth as shown below.
The ohmic value of each earthing resistor is usually chosen so as to limit the
maximum earth fault current to not more than the generator full load current.
Such a Neutral Earthing Resistor (NER) is often assembled with metallic plates in
air but liquid (brine) resistors have also been used. The use of such an earthed
system means that a single earth fault will cause that circuit to be disconnected
by its protection device.
Certain essential loads (e.g. steering gear) can be supplied via a transformer
with its secondary unearthed to maintain security of supply in the event of a
single-earth fault. Regulations insist that tankers have only insulated distribution
systems. This is intended to reduce danger from earth fault currents circulating
in the hull in hazardous zones which may cause an explosion of the flammable
cargo.
An exception allowed by regulating bodies occurs where a tanker has a 3.3 kV
earthed system. Such a system is permitted providing that the earthed system
does not extend forward of the engine room bulkhead and into the hazardous
zone area. Electrical supplied forward of the engine room bulkhead are usually 3phase 440V insulated and obtained from a 3-phse 3.3 kV/440V transformer.