SYSTEM OF SELF-SUFFICIENCY OF ELECTRICITY IN PEAK HOURS
The generation system has a design capacity of 7.24 MW, to operate
during peak hours and during times when there is no provision for the
commercial network, composed of four generators operated with diesel
and synchronization boards.
MODES OF OPERATION
Peak shaving operation mode (peak times):
- The system turns on automatically according to a schedule based on the
times
tips
the
utility.
Generators are synchronized by a 4160 V and the voltage transformer
rises to 23 KV and connected to the commercial network in transferring the
load smoothly generators such that there are no changes in energy
parameters (voltage, frequency and current) during the transition between
the commercial network and the autogenous group.
Emergency mode:
-In case there is a power outage in the commercial network, the generators
start at eight seconds and synchronized taking charge 100%
Upon return of utility power, the system synchronizes with the network
generators transferring the load smoothly without any variation in energy
parameters (voltage, frequency and current)
Peak Shaving System
Tablero eléctrico de
sincronización
10
MVA
Carga Site
Tultitlan
23 KV
Red comercial
23 KV
Transformador
23
kv
4 kv
TC 1
SINCRONIZACIÓN
TC 2
TC 3
Tablero eléctrico de
transferencia
TC 4
10 000 lt
2000’KW
2000’KW
MOTOGENERADOR 4
MOTOGENERADOR 3
MOTOGENERADOR 2
MOTOGENERADOR 1
10 000 lt
2000 KW
10 000 lt
10 000 lt
2000’KW
Tanques de Diesel
Grupo de generadores