Download Generator protection and control REG630 Flexibility for

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground (electricity) wikipedia , lookup

Power inverter wikipedia , lookup

Relay wikipedia , lookup

Electrification wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Electric power system wikipedia , lookup

Control theory wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stray voltage wikipedia , lookup

History of electric power transmission wikipedia , lookup

Resilient control systems wikipedia , lookup

Triode wikipedia , lookup

Rectifier wikipedia , lookup

Automation wikipedia , lookup

Buck converter wikipedia , lookup

Power engineering wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage optimisation wikipedia , lookup

Islanding wikipedia , lookup

Distributed control system wikipedia , lookup

Control system wikipedia , lookup

Power electronics wikipedia , lookup

Electrical substation wikipedia , lookup

Opto-isolator wikipedia , lookup

Earthing system wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Protective relay wikipedia , lookup

Transcript
Relion ® 630 series
Generator protection and control
REG630
Flexibility for demanding utility and
industrial power distribution systems
Complete generator protection and
control with extensive interconnection
protection for distributed generation
REG630 is a comprehensive generator management relay
for protection, control, measurement and supervision of
small and medium-sized power generators and generatortransformer units in utility and power distribution
systems.
Application
REG630 has been designed to be the main protection for
synchronous generators, offering full protection during startup and normal run for both the generator and the prime
mover. The generator management relay is typically used in
small and medium-sized diesel, hydroelectric, combined heat
and power (CHP), and steam power plants. The pre-defined
configuration is intended for directly connected generator
sets and can either be used as such or easily tailored to
application-specific requirements with freely selectable
functions.
REG630 can be used in either single or double-busbar
applications with one or two breakers and numerous
switching devices. It also supports a substantial number
of both manually and motor-operated disconnectors and
earthing switches. Consequently, REG630 can be used to
control various types of switchgears.
REG630 has been extended with low-voltage ride-through,
reactive power undervoltage and voltage vector shift protection to further ensure grid stability and reliability, and thus
avoid grid collapse. The low-voltage ride-through protection
allows monitoring of distributed generation during low-voltage
fault ride-through, in order to determine whether and when to
disconnect, for instance, a solar or wind farm from the grid.
Also the reactive power undervoltage protection does the
same but specifically at the grid connection point, whereas
the voltage vector shift protection detects islanding from the
grid.
An optional RTD/mA module offers eight analog RTD or mA
measuring inputs and four mA outputs. The RTD and mA
inputs can be used for temperature measurement of generator
bearings and stator windings, thus extending the functionality
of the thermal overload protection and preventing premature
aging of the generator windings. They can also be used for
measuring the ambient air or coolant temperature. The four
mA outputs can be used for transferring freely selectable
measured or calculated analog values to devices provided
with mA inputs.
The pre-configurations can be tailored to meet the application
requirements using the IEC 61850-compliant protection and
control IED manager PCM600.
2 Generator protection and control | REG630
Human-machine Interface (HMI)
As a member of the Relion® product family, REG630 shares
the same Human Machine Interface (HMI) look and feel as the
other Relion protection and control relays and IEDs. The same
look and feel includes the location of a push button with a
certain function and the menu structure.
The 630 series relays are equipped with a large graphical
display which can show customizable single-line diagrams
(SLD) with position indication for the circuit breaker, disconnectors and the earthing switch. Also measured values
can be displayed. The SLDs can be flexibly adjusted to meet
user requirements using PCM600.
The 630 series HMI is distinguished by fifteen three-color
LEDs and five configurable push buttons, which can be
used as control buttons for various tasks such as blocking,
adjusting setting groups or triggering the disturbance
recorder. The five push buttons can also be conveniently
used as menu shortcuts. Another distinguishing feature is
the detached HMI, as an option to the integrated HMI which
is highly beneficial from a wiring perspective due to the large
number of IOs the 630 series relays are equipped with.
Standardized communication
REG630 fully supports the IEC 61850 standard for
communication in substations. The generator management
relay also supports the DNP3 (TCP/IP) and 60870-5103 communication protocols, and is able to use two
communication protocols simultaneously. The supported
communication protocols, including IEC 61850, offer
seamless connectivity to various station automation and
SCADA systems.
The implementation of the IEC 61850 standard in REG630
covers both vertical and horizontal communication, including
GOOSE messaging according to IEC 61850-8-1 with both
binary and analog signals. Analog GOOSE messaging enables
fast transfer of analog measured values over the station bus.
This facilitating, for example, sharing of RTD input values
such as surrounding temperature with other relays. GOOSE
messaging is also an alternative to traditional hardwiring
signaling for exchanging interlocking information between
the relays. For time-critical applications, REG630 supports
synchronization over Ethernet using SNTP or over a separate
bus using IRIG-B.
630 series
REG630 is a member of ABB’s Relion product family and
part of its 630 protection and control series. The 630 series
relays are characterized by functional scalability and flexibile
configurability, and have been designed to unleash the full
REG630
GENERATOR PROTECTION AND CONTROL IED
For directly connected generator set
LOCAL HMI *)
PROTECTION
ALSO AVAILABLE
- 5 × prog. push buttons on LHMI
- Disturbance and fault recorders
- IED self-supervision
- Local/Remote push button on LHMI
- Sequence event recorder
- User management
- WebHMI
1× 1×
I→O
94
2× 1×
2× 1×
P>
P<
32R/32O
32U
3I
2×
X<
40
2×
3Ith>T/G
49T/G
3U
AND
I(U)>
51V
3I
2×
3I>/Io>BF
51BF/51NBF
I2>G/M
46G/46M
COMMUNICATION
CONDITION MONITORING
AND SUPERVISION
2×
1× 1×
3I>
51P-1
OR
* Fixed or detached LHMI is available.
)
3dl>G/M
87G/87M
Io
FUSEF
60
1× 1×
CBCM
CBCM
MCS 3I
MCS 3I
OPTS
OPTM
1× 1×
3I>>
51P-2
Protocols:
IEC 61850-8-1
IEC 60870-5-103
DNP3
E
E
3I
Io>→
67N-2
Object
Io
3U>
59
2× 2×
df/dt>
81R
2× 2×
f<
81U
2×
2×
3×
2×
Z<GT
21GT
U<RT
27RT
U1>
47O+
U/f>
24
2× 1×
Uo>
59G
2× 2×
f>
81O
0
1
0
1
0
1
0
0
1
0
0
0
0
0
1
1
0
0
1
1
1
1
1
1
1
0
0
0
1
0
8
2)
Check availability of binary inputs/outputs
from technical documentation
Control and indication function for
primary object
- I, U, Io, Uo, P, Q, E, pf, f
- Sequence current/voltage measurement
- Limit value supervision
- RTD/mA measurement (optional)
Analog interface types
B
Current transformer
7
Voltage transformer
3
SYNC
25
dUo(3H)>/Uo(3H)<
27/59THD
2×
2×
Q>→, 3U<
32Q, 27
2×
1)
2)
2
ES
3U<
27
1
1
0
1
1
1
MEASUREMENT
Ctrl
CB
DC
2×
0
0
1
0
0
0
U<>
U<>
Uo
2×
1
1
1
1
1
1
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass fiber (ST),
Serial plastic fiber
(snap-in connector)
2× 1×
TCS
TCM
CONTROL AND INDICATION 1)
1× 1×
Io>→
67N-1
∆Io
A
PRECONFIGURATION
U1<
47U+
Io>>>
50N/51N
Io>
51N-1
Io>>
51N-2
Io>R
64R
3I>>→
67-2
3I2f>
68
VS
78V
U2>
47O-
3I>>>
50P/51P
2×
3I>→
67-1
REMARKS
3dlHi>G/M
87GH/87MH
dIoHi>
87NH
3dI>T
87T
16×
MAP
MAP
Optional
function
2× No. of instances
enabled by default
Function(s) not enabled by
default in preconfiguration,
can be enabled afterwards
1× No. of instances not enabled
by default in preconfiguration,
can be enabled afterwards
Io/Uo
Calculated
value
Protection function overview of the Pre-configuration A for REG630.
potential of the IEC 61850 standard for communication and
interoperability of substation automation devices. In addition
to REG630, the 630 series includes the following relays:
• REF630 Feeder protection and control
• RET630 Transformer protection and control
• REM630 Motor protection and control
REG630 | Generator protection and control 3
REG630 generator protection and
control pre-configurations
Pre-configurations
Preconfiguration
Description
Pre-configuration A for directly connected generator set
A
Number of instances available
n
Supported functions with codes and symbols
IEC 61850
IEC 60617
ANSI
A
n
Three-phase non-directional overcurrent, low stage
PHLPTOC
3I>
51P-1
1
1
Three-phase non-directional overcurrent, high stage
PHHPTOC
3I>>
51P-2
1
2
Three-phase non-directional overcurrent, instantaneous stage
PHIPTOC
3I>>>
50P/51P
-
1
Voltage dependent overcurrent
PHPVOC
I(U)>
51V
2
2
Three-phase directional overcurrent, low stage
DPHLPDOC
3I> →
67-1
-
2
Three-phase directional overcurrent, high stage
DPHHPDOC
3I>> →
67-2
-
1
Non-directional earth-fault, low stage
EFLPTOC
I0>
51N-1
-
1
Non-directional earth-fault, high stage
EFHPTOC
I0>>
51N-2
-
1
Non-directional earth-fault, instantaneous stage
EFIPTOC
I0>>>
50N/51N
-
1
Directional earth-fault, low stage
DEFLPDEF
I0> →
67N-1
1
2
Directional earth-fault, high stage
DEFHPDEF
I0>> →
67N-2
1
1
High-impedance based restricted earth-fault
HREFPDIF
dI0Hi>
87NH
-
1
Residual overvoltage
ROVPTOV
U0>
59G
2
3
Third harmonic-based stator earth-fault
H3EFPSEF
dUo(3H)>/Uo(3H)< 27/59THD
-
1
Rotor earth-fault
MREFPTOC
Io>R
64R
-
1
Negative-sequence overcurrent protection for machines
MNSPTOC
I2>G/M
46G/46M
2
2
Three-phase current inrush detection
INRPHAR
3I2f>
68
-
1
Three-phase thermal overload, two time constants
T2PTTR
3Ith>T/G
49T/G
1
1
Stabilized differential protection for machines
MPDIF
3dI>G/M
87G/87M
1
1
Transformer differential protection for 2-winding transformers
TR2PTDF
3dI>T
87T
-
1
MHZPDIF
3dIHi>G/M
87GH/87MH
-
1
Three-phase underexcitation
UEXPDIS
X<
40
2
2
Three-phase overvoltage
PHPTOV
3U>
59
2
2
Three-phase undervoltage
PHPTUV
3U<
27
2
2
Positive-sequence overvoltage
PSPTOV
U1>
47O+
-
2
Positive-sequence undervoltage
PSPTUV
U1<
47U+
-
2
Negative-sequence overvoltage
NSPTOV
U2>
47O-
-
2
Overexcitation
OEPVPH
U/f>
24
-
2
Three-phase underimpedance
UZPDIS
Z< GT
21GT
-
2
Directional reactive power undervoltage
DQPTUV
Q>-->,3U<
32Q, 27
-
2
Reverse power / Directional overpower
DOPPDPR
P> →
32O / 32R
2
3
Underpower
DUPPDPR
P<
32U
2
3
Frequency gradient
DAPFRC
df/dt>
81R
2
4
Overfrequency
DAPTOF
f>
81O
2
4
Underfrequency
DAPTUF
f<
81U
2
4
Low voltage ride through
LVRTPTUV
U<RT
27RT
-
3
Voltage vector shift
VVSPPAM
VS
78V
-
1
Circuit breaker failure
CCBRBRF
3I>/I0>BF
51BF/51NBF
1
2
Tripping logic
TRPPTRC
I→O
94
1
2
Multipurpose analog protection
MAPGAPC
MAP
MAP
-
16
Functionality
Protection
High-impedance or flux-balance based differential protection
for machines
4 Generator protection and control | REG630
Supported functions with codes and symbols
IEC 61850
IEC 60617
ANSI
A
Bay control
QCCBAY
CBAY
CBAY
1
1
Interlocking interface
SCILO
3
3
3
10
Circuit breaker / disconnector control
GNRLCSWI
I ↔ O CB/DC
I ↔ O CB/DC
3
10
Circuit breaker
DAXCBR
I ↔ O CB
I ↔ O CB
1
2
Disconnector
DAXSWI
I ↔ O DC
I ↔ O DC
2
8
Local remote switch interface
LOCREM
R/L
R/L
-
1
Synchrocheck
SYNCRSYN
SYNC
25
-
1
Single point control (8 signals)
SPC8GGIO
-
-
-
5
Double point indication
DPGGIO
-
-
-
15
Single point indication
SPGGIO
-
-
-
64
Generic measured value
MVGGIO
-
-
-
15
SLGGIO
-
-
-
10
Selector mini switch
VSGGIO
-
-
-
10
Pulse counter for energy metering
PCGGIO
-
-
-
4
Event counter
CNTGGIO
-
-
-
1
Runtime counter for machines and devices
MDSOPT
OPTS
OPTM
-
1
Circuit breaker condition monitoring
SSCBR
CBCM
CBCM
1
2
Fuse failure supervision
SEQRFUF
FUSEF
60
1
1
Current circuit supervision
CCRDIF
MCS 3I
MCS 3I
-
2
Trip-circuit supervision
TCSSCBR
TCS
TCM
2
3
Station battery supervision
SPVNZBAT
U<>
U<>
-
1
Energy monitoring
EPDMMTR
E
E
1
1
Measured value limit supervision
MVEXP
-
-
-
40
Three-phase current
CMMXU
3I
3I
1
2
Three-phase voltage (phase-to-earth)
VPHMMXU
3Upe
3Upe
-
2
Three-phase voltage (phase-to-phase)
VPPMMXU
3Upp
3Upp
1
2
Residual current
RESCMMXU
I0
I0
1
1
Residual voltage
RESVMMXU
U0
Vn
1
1
Power monitoring with P, Q, S, power factor, frequency
PWRMMXU
PQf
PQf
1
1
Sequence current
CSMSQI
I1, I2
I1, I2
1
1
Sequence voltage
VSMSQI
U1, U2
V1, V2
1
1
Analog channels 1-10 (samples)
A1RADR
ACH1
ACH1
1
1
Analog channel 11-20 (samples)
A2RADR
ACH2
ACH2
-
1
Analog channel 21-30 (calc val)
A3RADR
ACH3
ACH3
-
1
Analog channel 31-40 (calc val)
A4RADR
ACH4
ACH4
-
1
Binary channels 1-16
B1RBDR
BCH1
BCH1
1
1
Binary channels 17-32
B2RBDR
BCH2
BCH2
1
1
Binary channels 33-48
B3RBDR
BCH3
BCH3
1
1
Binary channels 49-64
B4RBDR
BCH4
BCH4
1
1
Binary receive
GOOSEBINRCV
-
-
-
10
Double point receive
GOOSEDPRCV
-
-
-
32
Interlock receive
GOOSEINTLKRCV
-
-
-
59
Integer receive
GOOSEINTRCV
-
-
-
32
Measured value receive
GOOSEMVRCV
-
-
-
60
Single point receive
GOOSESPRCV
-
-
-
64
Functionality
n
Control
Generic process I/O
Logic Rotating Switch for function selection and
LHMI presentation
Supervision and monitoring
Measurement
Disturbance recorder function
Station communication (GOOSE)
REG630 | Generator protection and control 5
ABB Oy Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone: +358 10 22 11
Fax:
+358 10 22 41094
www.abb.com/substationautomation
1MRS 757640 B
For more information see REG630 Product Guide
or contact us:
© Copyright 2014 ABB. All rights reserved.
Contact us