Download AUTOMATIC VOLTAGE REGULATOR R630

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
Réf. 2352 - 4.33 / a - 6.96
parallel
running CT
3 booster
CT
GS
3Ø
2 measure
VT
Power
VT
2 or 3 measure
VT
Out of supply
Optional
Booster
board
or
De-energizing
or
(Power)
(Control)
AVR
Mains measure
Out of supply
Rotating
diode
failure
detector
(OPTION)
Command
inputs
Fault outpu
Potentiometer
inputs
Alarm output
AUTOMATIC VOLTAGE
REGULATOR
R630
Installation and maintenance
AVR
Model R630
TABLE OF CONTENT
AVR CONSTITUTION ............................................................................................................................ 3
GENERAL DESCRIPTION : NT1950000 /a ........................................................................................... 4
CARDS DESCRIPTION : NT1950xxx .................................................................................................. 12
START-UP : NT1959000 /a .................................................................................................................. 45
NOTE
THE ELECTRICAL CONNECTION DIAGRAM ARE ONLY GIVEN
AS AN INDICATION. PLEASE REFER TO THE SPECIFIC DIAGRAMS
OF YOUR ALTERNATOR.
WARNING
TO PREVENT PERSONNAL INJURY OR EQUIPMENT DAMAGE,
ONLY QUALIFIED TECHNICIANS/OPERATORS SHOULD
INSTALL AND OPERATE THIS DEVICE.
CAUTION
MEGGERS AND HIGH POTENTIAL TEST EQUIPMENT MUST NOT BE
USED. INCORRECT USED OF SUCH EQUIPMENT COULD
DAMAGE THE SEMICONDUCTORS CONTAINED IN THE AVR.
2
AVR
Model R630
DESIGNATION
Constitutive
elements
N° printed
circuit board
N° complete N° instruction
REMARKS
card
manual
Wired empty rack
C51950250
NT1950000/c-02/95
SHUNT (+booster)
Wired empty rack
C51950251
NT1950001/b-10/94
PMG
Complete Generator I/O board
C51950200
NT1950010/b-10/94 100 / 120V - 50 / 60Hz
Complete Generator I/O board
C51950202
NT1950010/b-10/94 400 / 450V - 50 / 60Hz
3F Complete Mains I/O board
C51950220
NT1950020/b-10/94 100 / 120V - 50 / 60Hz
3F Complete Mains I/O board
C51950222
NT1950020/b-10/94 400 / 450V - 50 / 60Hz
2F Complete Mains I/O board
C51950210
1F Complete Interface board
C51950215
Rack supply
CP1950040
C51950041
NT1950040/a-11/92
Sensing
CP1950050
C51950051
NT1950050/a-11/92
PID, limitation
CP1950060
C51950061
NT1950060/a-11/92
Driver
CP1950070
C51950071
NT1950070/b-11/93
CosØ, KVAR
CP1950080
C51950081
NT1950080/b-10/94
Limit Istator
CP1950090
C51950091
NT1950090/a-11/92
Manual mode 1
CP1950100
C51950101
NT1950100/a-02/93
Digital U / P.F potentiometer
CP1950110
C51950111
NT1950110/a-01/94
Digital Ified pot and Follower
CP1950115
C51950141
NT1950115/a-01/94
Mains P.F régulation
CP1950120
C51950121
NT1950120/a-04/94
Rotating diode fault detector
CP1950130
C51950131
NT1950130/a-06/96 Available June 1996
= Neccessary
= Optionals
IMPORTANT : The informations given by this sheet must be used to order spare parts. Take care of it.
3
AVR
Model R630
General
description
1 - APPLICATION
5 - SPECIFICATIONS
- The AVR model R600 can be used with brusless selfexcited type generators, "SHUNT", "SHUNT with BOOSTER" or "SHUNT with PMG" excitation. In case of
"SHUNT with BOOSTER the booster current is totally
monitored by the AVR.
- Sensing voltage :
• 100/110Vac 50Hz
• 120/130Vac 60Hz
• 380/420Vac 50Hz
• 430/450Vac 60Hz
- The AVR is able to ensure, depending of its constitution, solo operation, parallel operation between equivalent generators or parallel operation with the mains with
cosØ or KVAR regulation.
- Power supply :
• Depend of generator(Adaptation by transformer).
Maximum 180Vac 50/60Hz
2 - DESCRIPTION
- The AVR model R631 is composed of electronic cards
wich are included in a rack 19" .
- Except the necessary "Generator I/O", the optional
"mains I/O" located on the left of the rack and the "driver"
card located on the right, all the other cards can be plugged anywhere in the rack. Future optional cards could be
added without any internal wiring modification.
- The rear flat cable (BUS 64 points) is given more long
as it can be connected to an optional interface terminal
block wich gives all the internal test points or in the
future the possibility to connect another rack if the cards
number will become too important.
3 - INTERCONNECTIONS
- External interconnections are located on the top of the
rack in form of two terminal blocks:
- A power / voltage terminal block (19 terminals, one with
a fuse )
- A command / control terminal block (41 terminals)
- A conventional wiring connect this terminal blocks to
the power block fitted on a heatsink and also to the
"generator I/O" and "mains I/O" to give an interface with
the flat cable BUS 64 points.
- In the same manner a 8 points connector connects
directly the driver card to the power block.
4 - OPTIONAL CARDS
- CosØ / KVAR regulation (2F)
- Voltage equalization with the mains (3F)
- Voltage and P.F digital potantiometers
- Manual operation
- Ifield digital potentiometer with follower
- Istator limitation
- Mains P.F or KVAR regulation from 4-20mA sensor
- Rotating diodes fault monitor
NT1950000/c-02/95 f:1/8
4
- Field output :
• 12 Amperes nominal, 24Amp maximum during 10s on
6Ω minimum
- Accuracy :
• +/-1% of the means of the three phases on linear load
and without droop
- Voltage setting range :
• +/-10% of the nominal voltage by means of external
optionnal potentiometer .
- Droop setting range :
• - 7% of the nominal voltage at cosØ =0
- Under-frequency protection :
• Adjustable threshold and slope from V/Hz to 2V/Hz
- Field ceiling :
• 110% of If nominal permanently, unlocked in case of
voltage decrease
- Protection :
• Heatsink overheating, exciter short-circuit
- Alarm output :
• Heatsink overheating, too much ceiling unlocked time
- Environnement :
• Maximum ambiant temperature -10°C to +50°C
• Fitting in control panel without excessive vibrations
6 - SCHEMATICS AND DRAWINGS
Following schematics give all the usual informations on
the interconnexions between the terminal block, the I/O
connectors and the power block.
AVR
Model R630
General
description
MIMIC DIAGRAM EXCITATION - REGULATION
TERMINAL BOX
parallel
running CT
3 booster
CT
GS
3Ø
2 or 3 measure
VT
Out of supply
2 measure
VT
Power
VT
Optional
Booster
board
or
De-energizing
or
(Power)
(Control)
AVR
Mains measure
Out of supply
Rotating
diode
failure
detector
(OPTION)
Potentiometer
inputs
Command
inputs
Alarm output
Fault output
VOLTAGE / POWER TERMINAL BLOCK
Power supply (fuse)
Auxiliary voltage
Auxiliary voltage
Power supply
W MAINS
V MAINS
U MAINS
// CT
// CT
+ Booster
- Booster
- Field
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
+ Field
4
+ Field flash
V MACHINE
W MACHINE
U MACHINE
1 2 3
COMMAND / CONTROL TERMINAL BLOCK
Réserve
Réserve
Réserve
Réserve
Réserve
Réserve
Réserve
COSØ / KVAR CMD
Ifield Pot
Manual pot
Info Auto / Manu
Auto / Manu
Auto / Manu
Info Auto / Manu
-Iexc CMD
Commun
+Iexc CMD
- CMD U / P.F
- 24Vdc ext
+ CMD U / P.F
+ 24Vdc ext
ALARM
ALARM
ALARM
U/U CMD
COSØ CMD
COSØ CMD
U/U CMD
KVAR POT
KVAR POT
KVAR POT
COSØ POT
COSØ POT
Measure If
COSØ POT
Measure If
VOLTAGE POT
VOLTAGE CMD
SHIELDS
VOLTAGE POT
VOLTAGE POT
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 53
57 58 59 53
60
NT1950000/c-02/95 f:2/8
5
AVR
Model R630
TERM N°
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
General
description
VOLTAGE / POWER TERMINAL BLOCK
Phase 1 (U) machine (measure)
Phase 2 (V) machine (measure)
Phase 3 (W) machine (measure)
+ fiel flashing or pre-excitation input (optional)
+ field output
- field output
+ booster input
- booster input
Paralleling CT phase 2 (V) S1
Paralleling CT phase 2 (V) S2
Not connected
Phase 1 (U) mains (measure)
Phase 2 (V) mains (measure)
Phase 3 (W) mains (measure)
Not connected
Auxiliairy voltage input
Auxiliairy voltage input
Power supply input
Power supply input (fused)
0F
1F
2F
3F
N
N
N
O
N
N
O
O
N
N
N
O
N
N
O
O
N
N
N
N
N
O
N
N
O
O
N
N
N
N
N
O
N
N
O
O
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
N
N
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
N
N
N
N
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
COMMAND / CONTROL TERMINAL BLOCK
20,20,20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
Potentiometer shield (3 terminals)
External voltage potentiometer maximum CW)
External voltage potentiometer (10KΩ-2W) (cursor)
External voltage potentiometer ( minimum CCW)
External voltage input (10Vdc, 0V to terminal 20)
Fied current measurement output (+Vdc)
Fied current measurement output (0V)
External cosØ potentiometer maximum CW)
External cosØ potentiometer (10KΩ-2W) (cursor)
External cosØ potentiometer ( minimum CCW)
External KVAR potentiometer maximum CW)
External KVAR potentiometer (10KΩ-2W) (cursor)
External KVAR potentiometer ( minimum CCW)
cosØ regulation command input
cosØ regulation command input
Voltage equalization command input
Voltage equalization command input
Overheating or ceiling unlocked time alarm (common)
Overheating or ceiling unlocked time alarm output (NC)
Overheating or ceiling unlocked time alarm output (NO)
External +24Vdc supply input ( relay locking)
External 24Vdc supply input ( relay locking) common
Upper command voltage and P.F
Lower command voltage and P.F
Common
Upper command Ifield (manu)
Lower command Ifield (manu)
"AUTO / MANU" command input (Open = "AUTO")
"AUTO / MANU" command input (Open = "AUTO")
"AUTO / MANU" image output
"AUTO / MANU" image output
Ifield direct manual setting potentiometer
Manual mode 1 card Ifield setting potentiometer (10KΩ)
CosØ / KVAR selection command input (/ terminal 48)
Reserve
Reserve
Reserve
Reserve
O = Optional
N = Neccessary
Nothing = Not applicable
NT1950000/c-02/95 f:3/8
6
O = Optional
N = Neccessary
Nothing = Not applicable
AVR
Model R630
General
description
POWER TERMINALS
Power supply
5
+ Field
18 19
Power supply
5
5
4
7
+ Booster
19
47Ω 50W
4
+ Field flashing
18
RBD
7
Booster
monitor
7
C1
7
E1
8
+VDC
Power supply
5
5
G1
HALL 8
sensor
B 64
5
+15
LEM
Card
C2
B
63
G2
7
8
4
3
2
1
5
6
E2
8
OVDC
Power supply
7
8
6
5
4
3
2
1
OPTION
Thermocontact
-15
8
1 2 3 4 5 6 8 7
To LMI 8 points connector
on driver card
POWER TERMINALS
Auxiliary supply
1
POWER BLOCK REF: C5 195 2100
Power wiring
Connectors wiring 32pts
J1 bac
15c Generator
I/O 2a
13c
2c
11c
14c
13a
16c
2c
10c
12c
8c
15a
1a
2c
1c
9c
11a
10c
5c
8a
6a
12a
4c
5a
14a
2c
7c
9a
10a
+If CMD
-If CMD
Auto / Manu
Auto / Manu
Info Auto / Man
Info Auto / Man
P4 MAINS I/O
15c
11c
7c
16a
2c
1a
3a
3c
4c
2c
2a
4a
5a
6a
7a
8a
9a
5c
POWER TERMINALS
U MAINS
V MAINS
W MAINS
CONTROL TERMINALS
Ifield POT
Manual POT
COSØ / KVAR
U/U CMD
U/U CMD
RESERVE
RESERVE
RESERVE
RESERVE
RESERVE
RESERVE
RESERVE
RESERVE
51 52 53 36 35 54 55 56 57 58 59 60 61
10c
7a
3c
6c
3a
4a
CONTROL TERMINALS
+ 24Vdc ext
- 24Vdc ext
+U CMD
-U CMD
Commun
12 13 14
ALARM
ALARM
ALARM
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 37 38 39
CONTROL TERMINALS
SHIELDS
VOLTAGE POT
VOLTAGE POT
VOLTAGE POT
VOLTAGE CMD
Measure If
Measure If
COSØ POT
COSØ POT
COSØ POT
KVAR POT
KVAR POT
KVAR POT
COSØ CMD
COSØ CMD
P4
9c 10c
To 32 points connector
P4 on "MAINS I / O"
40 41 42 43 44 45 46 47 4849 50
Auxiliary supply
9 10 11 16 17
// CT
// CT
3 4
V MACHINE
W MACHINE
1 2
U MACHINE
C
M
Connector LMI 8pts
8
R
+
60
60
6
ON HEATSINK
2x1000µF
350V in //
or
2200µF 400V
8
70
6
1µF
400V
69
6
- Field
Free
wheeling
diode
8
- Booster
8
NT1950000/c-02/95 f:4/8
7
AVR
Model R630
General
description
+ Field
- Field
18 19
- Booster
4
+ Booster
4
7
+ Field flashing
19
18
7
8
Power supply
8
5
Power supply
5
6
R630 POWER BLOCK SHUNT (+ BOOSTER)
6
ARCOL 47Ω 50W
7
To MAINS I / O P4
9c 10c
7
18
60
8
LEM board 74mm x 78mm
8
2200µF 400V
64
5
120mm
5
63
1µF
400Vac
5
19
LEM
8
60
8
76
76
6
132mm
Booster
IGBT
Main
IGBT
- The following tables give interconnections between
each card and the 64 points flat cable.
- Grey cases give signals origine.
- Other cases where they go.
- On the left we have two numbers :
• First the connector numering
• Second test block terminal number
- On the right we have a recapitulative of all the informations wich can be found on the test terminal block.
NT1950000/c-02/95 f:5/8
8
8
Connector
LMI 8points
300mm
1
5
Rectifier
bridge
3
4
5
6
7 Vac puiss 1
8 Vac puiss 2
9
2c
2a
3c
3a
4c
4a
5c
GND
GND
Vac-dm1
Vac-dm2
Vac-dm3
7c 13
7a 14
8c 15
8a 16
9a 18
GND
GND
GND
GND
GND
GND
16a 32
GND
cde Iexc
cde Iexc
16c 31
Sauto
Uref
GND
GND
+Vcc
+Vcc
Smanu
Sauto
15c 29
IcosØ
Uregl
GND
GND
+Vcc
+Vcc
15a 30
IcosØ
14a 28
Statisme D Statisme D
cosØ, KVAR cosØ, KVAR
IsinØ
Déphasage
TI//
Vac-dm2
GND
GND
+Vcc
+Vcc
GND
cde Iexc
Smanu
Sauto
Correct PID
V-10%
GND
GND
Vac puiss 1
+Vcc
+Vcc
CosØ,KVAR Pot digital U Pot digital Iexc Manu mode
14c 27
Uregl
Correct PID
Uref
Um
Ures
V-10%
GND
GND
+Vcc
+Vcc
PID, limit
13a 26
13c 25
12a 24
12c 23
Uref
11a 22
TI//
Vac-dm3
Vac-dm2
Vac-dm1
GND
GND
+Vcc
+Vcc
Sensing
Um
GND
GND
GND
-Vdc alim
-Vdc alim
+Vdc alim
+Vdc alim
+Vcc
+Vcc
Supply
11c 21
10a 20
10c 19
Ures
Vac-dr3
6a 12
TI//
Vac-dr2
9c 17
Vac-dr1
6c 11
GND
+Vcc
+Vcc
Mains I/O
5a 10
GND
-Vdc alim
-Vdc alim
+Vdc alim
+Vdc alim
+Vcc
2
1a
+Vcc
1
Gen I/O
1c
PIN PIN
GND
cde Iexc
Smanu
Sauto
V-10%
GND
GND
Vac puiss 2
Vac puiss 1
+Vcc
+Vcc
Driver
GND
cde Iexc
Smanu
Sauto
IcosØ
cosØ,KVAR
Statisme D
Uregl
IsinØ
Correct PID
Uref
Um
Ures
Déphasage
TI//
V-10%
Vac-dm3
Vac-dm2
Vac-dm1
GND
Vac-dr3
Vac-dr2
Vac-dr1
GND
Vac puiss 2
Vac puiss 1
-Vdc alim
-Vdc alim
+Vdc alim
+Vdc alim
+Vcc
+Vcc
test output
AVR
Model R630
General
description
NT1950000/c-02/95 f:6/8
9
NT1950000/c-02/95 f:7/8
10
GND
Mes Iexc
synchro
I limit
GND
Fin rampe
U cosØ
17c 33
17a 34
18c 35
18a 36
19c 37
19a 38
20c 39
Pot tension
U tension
+Iexc
-Iexc
+Uauto
-Uauto
21a 42
22c 43
22a 44
23c 45
23a 46
24c 47
-Vcc
-Vcc
Cde U=U
Cde reg cosØ
U tension
Pot tension
Fin rampe
GND
GND
U cosØ
GND
GND
-Vcc
U KVAR
Max pot
-Uauto
+Uauto
U KVAR
P.F/KVAR P.F/KVAR
U cosØ
GND
GND
GND
GND
Mes Iexc
GND
test output
Fin rampe
GND
I limit
Cde U=U
Cde reg cosØ
-Uauto
+Uauto
-Iexc
+Iexc
U tension
Pot tension
U KVAR
P.F/KVAR
U cosØ
Fin rampe
GND
I limit
Perte synchro Perte synchro
Mes Iexc
GND
Driver puiss
Cde U
Cde U
Défaut T°C
-Vcc
-Vcc
-Vcc
-Vcc
-Vcc
-Vcc
-Vcc
-Vcc
32a 64
-Vcc
-Vcc
32c 63
-Vcc
-Vcc
-Vcc
Alarm
Alarm
31a 62
-Vcc
reserve
31c 61
-Vcc
30c 59
-Vcc
reserve
Max pot Iexc
29a 58
-Vcc
reserve
29c 57
Max pot U/P.F
reserve
28a 56
30a 60
reserve
28c 55
Max pot
reserve
27a 54
Alarm
Défaut T°C
Cde A/M cde auto/manu cde auto/manu cde auto/manu
-Iexc
+Iexc
GND
GND
Manu mode
Cde U
-Vcc
GND
GND
CosØ, KVAR Pot dig U Pot dig Iex
27c 53
-Vcc
GND
GND
PID, limit
reserve
Défaut T°C
Cde U=U
P.F/KVAR
GND
GND
Mains I/O Supply Sensing
26a 52
26c 51
25a 50 cde auto/manu
25c 49
24a 48 Cde reg cosØ
U KVAR
21c 41
20a 40
Gen I/O
PIN PIN
AVR
Model R630
General
description
=
1
1
Bac
réseau
mains
I/O
option
2
Bornier
Terminal block
Bac
alternateur
alternator
I/O
3
4
5
436
482,6
466,7
19
37,7
57,1
37,7
7
8
9
Bornier
Terminal block
Bloc puissance
Power components
6
10
power
control
option
Driver
puiss.
11
40
I stator
limit
60
Limite
I stator
Radiateur
Heatsink
Aliment. Détect. KVAR PID et
cos Ø limite
supply sensing
option PID and
limit
12
=
3
14
Bornier
Terminal block
132,5
370
Bornier
Terminal block
20
Verif : L . D
Date : 30/12/92
ENCOMBREMENT REGULATEUR de TENSION
AUTO. VOLTAGE REGUL.GENERAL ARRANGEMENT
-------------------------SHUNT - - - Serie ::R630
R 600 N °EN 182 2511
Des. : P . B
356
9,5
15
d'Orléans
FRANCE
45005 ORLEANS
ACEO
Ateliers de Constructions Electriques
AVR
Model R630
General
description
NT1950000/c-02/95 f:8/8
11
165
AVR
Model R630
Generator
I/O
1 - FUNCTIONAL
- This unit is mainly an interface between external signals
and low power electronics.
- It is composed by :
• The adaptation three phases transformer between input
voltage and measurement circuits.
• The burden resistor of parallel CT.
• The adaptation transformer between input voltage and
low power electronic supplies.
2 - ADJUSTMENTS
- Setting of the auxiliary input voltage (terminals 16,17) :
(110 or 220Vac) by jumpers.
3 - INPUT / OUTPUT
See following table
INPUT
TERMINAL
Connector
32 PTS
Type
I/O
Interface
Connector
26 PTS
Connector
BUS 64 PTS
1
1
2
2
3
3
9
10
16
17
15c
15c
13c
13c
11c
11c
16c
10c
1a
1c
measure
alim
measure
alim
measure
alim
measure
measure
alim
alim
transfo 3Ø TP4
transfo TP2
transfo 3Ø TP4
transfo TP1/2
transfo 3Ø TP4
transfo TP1
resistance RTI
GND
transfo TP3
transfo TP3
4
7a
2
8c
3
8a
5
1
9a
7c
4c
4a
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
37
38
39
40
41
42
43
44
45
46
47
48
49
50
10c
7a
3c
6c
3a
4a
10c
5c
8a
6a
12a
4c
5a
14a
2c
7c
9a
10a
2a
2c
14c
13a
2c
12c
8c
15a
2c
9c
11a
shield
signal
signal
signal
signal
signal
signal
signal
signal
signal
signal
signal
signal
cmd input
cmd input
cmd output
cmd output
cmd output
ext supply
ext supply
cmd input
cmd input
common
cmd input
cmd input
cmd input
cmd input
cmd output
cmd output
GND
resistance
direct
resistance
direct
direct
GND
resistance
direct
resistance
resistance
direct
resistance
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
1
13
14
15
16
21
1
6
17
23
6
19
23
8
7c
11a
21a
7c
22c
17a
7c
1c
20c
32a
1c
21c
32a
24a
25
25
25
31a
31a
31a
9
10
23a
24c
11
12
7
22a
23c
25a
12
23c
NT1950010/b-10/94 f:1/3
12
• The interface input relays between command / control
terminals and internal circuits.
• The interface between 64pts BUS and the analogic input / output terminals
AVR
Model R630
1
2
3
U alt
V alt
W alt
9
// CT
10
// CT - GND
Generator
I/O
15c
4
13c
2
3
1
5
16c
R1
TP2
2
3
}
1
40
Alim auxil
Alim auxil
+24Vdc ex
-24Vdc
1a
7
1c
8
110V
2a
2c
CR21
to 24
9
C2
10
15a
14a
34 33
CR3
14c
CR4
44 42
CR5
-I exc
44 46
50
49
Info Man
Info Man
12c
CR6
8c
11a
CR7
K7
9c
6
7
R14
+Vcc 1c
25a
DS1
K2
R13
R18
K3
8
24a
DS2
R12
13a
44 43
44 45
04/10/94
PT1
K1
R17
+I exc
3c,3a
16a,17c
4c
4a
Q1
+24Vdc U/U 16a
-U
CR17 to 20
PT2
TP3
CR1
2c,2a
CR5 to 10
CR11 to 16
CR2
+U
6
220V
48 47
cosØ cmd
5
4
TP1
C1
Auto/Man
8a
7c
9a
PT3
10c
}
17
8c
TP4
11c
Terminal N°
16
7a
9
23a
DS3
K4
10
R11
24c
DS4
K5
11
R10
22a
DS5
K6
R9
CR8
DS6
12
23c
+Vcc
+Vcc
21
22
23
24
Pot U
Pot U
Pot U
cmd by U
27
28
29
cosØ pot
cosØ pot
cosØ pot
30
31
32
KVAR pot
KVAR pot
KVAR pot
7a
3c
6c
3a
5c
8a
6a
13
14
15
16
R8
R7
R6
17
23
R5
11a
21a
7c
22c
20c
-Vcc 32a
04/10/94
12a
4c
5a
R4
19
21c
R3
R2
7c
38
39
Info Alarm
Info Alarm
Info Alarm
9a
10a
25
Measure If
4a
37
}
Terminal N°
K8
R16
Male Connector
DIN41612 32Pts
CR9
DS7
R15
25
21
Connector
HE10 26Pts
31a
17a
Male Connector
DIN41612 64Pts
Wiring by connector HE10 26pts and flat cable
Wiring by connector LMI 10pts and normal cables
NT1950010/b-10/94 f:2/3
13
AVR
Model R630
Generator
I/O
TP1
15VA
TP3
28VA
relai
TP2
TP2
15VA
TP4
TP3
28VA
Connect
TP1
Connect
TP2
TP4
ALTERNATEUR E / S
GENERATOR E / S
auto/manu
Cde cosØ
+U auto
-U auto
+I exc
-I exc
PT2
PT3
NT1950010/b-10/94 f:3/3
14
TP4
Capa
7812
TP3
28VA
PT1
R TI//
TP1
Alarm
LED
AVR
Model R630
Supply
card
1 - FUNCTIONAL
2 - ADJUSTMENTS
- This card, from not regulated symetrical voltage, generates +15Vdc and -15Vdc voltages with 0V common to both
named +Vcc for +15V and Vdd for -15V in the following.
- The non regulated voltages are first filtered (C01, C02),
pre-regulated to 20dc with ballast stages Q01 et Q02
and finally decreased to15V by means of RG01 et RG02
regulators.
- Its permanent current capability is 0,5 Amp on both
polarity.
None
3 - INPUTS / OUTPUTS
- 2a, 2c : Input +30Vdc not regulated
- 3a,3c : Input -30Vdc not regulated
- 1a,1c : Output +15Vdc regulated (Vcc)
- 32a,32c : Output -15Vdc regulated (Vdd)
- 16a,17c : Common electronic ground
MIMIC DIAGRAM OF ELECTRONIC SUPPLY CARD
+V not
regulated
2a,2c
Filter
Pre-regul
Regulator
+15Vdc
1c,1a
+Vcc
LED
+15V
0v
16a,17c
16a,17c
0V
LED
-15V
-V not
regulated
3a,3c
Filter
Pre-regul
Regulator
-15Vdc
32c,32a
-Vdd
NT1950040/a-11/92 f:1/2
15
AVR
Model R630
Supply
card
TIP41
Q01
3,4
RG01
TP1
1,2
7815
R03
3,3KΩ
C03
R01 330Ω
C05
0,33µF 63v
C01
CR03
0,33µF 63v
1N4007
CR01
1000µF 40V
DS1
BZX85C20
32,33
TP2
R04
1000µF 40V
3,3KΩ
CR02
C02
R02 330Ω
BZX85C20
C04
0,33µF 63v
0,33µF 63v
63,64
7915
Q02
TIP42
RG02
TP3
ALIMENTATION
SUPPLY
+15V
-15V
PT1
PT2
PT3
16
C06
DS2
5,6
NT1950040/a-11/92 f:2/2
CR04
1N4007
AVR
Model R630
Sensing
card
1 - FUNCTIONAL
2 - ADJUSTMENTS
- This card elaborates from the three phases voltage
image of the generator given by the "ALTERNATOR I/O" :
- A rectified, calibrated, filtered voltage Vm proportional
to the stator voltage of the generator. Vm could be affected by droop depending of adjustment.
- A voltage function of the generator frequency, a part of
which gives the reference set point named Vref.
- Vref is a constant above the underfrequency threshold
set point (signaled by LED) and decreases below this
threshold following a function depending of the position
of the strap CV1:
• In fixed V/Hz mode
• In adjustable kVolt / Hz (see curve below)
- P1 : Reactive droop adjust for parallel operation between equivalent machine.
- P2 : Vm adjust for nominal voltage. (9Vdc at Un)
- P3 : Underfrequency threshold adjust (normally Fn 5%) signaled by LED.
- P4 : Underfrequency slope adjust ( k ) in kVolt / Hz mode
(1≤ k ≤2)
- P5 : Voltage set point Vref for the nominal voltage
(10Vdc at Un and Fn)
Volt
Un
Mode Volt / Hz
3 - INPUTS / OUTPUTS
- 7a, 8a, 8c : Voltage inputs image of the generator (3 x
21Vac between each and the GND)
- 9a
: Current input image of the generator stator
current (1Vac pour In)
- 1a,1c
: +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- 11c
: Voltage output image of the generator (Vm)
10Vdc at Un
- 11a
: Voltage set point output (Vref) 10Vdc at
Un and Fn
Mode k x Volt / Hz
Fn - 5%
Fn
Hz
MIMIC DIAGRAM OF SENSING CARD
TI //
9a
AC / DC
Reactive
droop
Um
Vm
Wm
7a
8c
8a
1c,1a
16a,17c
32c,32a
Σ
AC / DC
AC / DC
+Vcc
k
Filter
11c
Vm
Threshold
U/F
0V
-Vdd
F -> kV
11a
Vref
Voltage
set point
LED
NT1950050/a-11/92 f:1/2
17
AVR
Model R630
Sensing
card
C1
8a
D1
R20
MN1
R1
R4
R3
R16
Z1
R2
D2
MN1
Z2
R22
R24
11c
P2
MN2
R19
R18
R5
Vm
C2
R21
8c
C3
R23
MN2
R17
R25
D3
MN1
R6
R9
R8
Vcc
Z3
R7
Ur
D4
MN1
R28
Z4
R10
8
7
6
5
D7
7a
MN4
D6
CV1
MN2
R11
1
R14
R13
2
3
R30
MN3
P4
LED
4
C4
9a
Z5
R12
D7
MN2
Z6
P1
R27
R15
R26
11a
P5
C5
P3
Vref
C9
R29
Vcc
1c,1a
C6
C8
16a,17c
32c,32a
Ur
Reg 1
C10
C11
C7
Principle diagram
R600 DETECTION
SENSING card
Vdd
22/06/92
DETECTION
SENSING
Vref
P5
U/kf
P4
U/f
FRONT VIEW
P3
SENSING CARD
Vm
P2
Statisme/Droop
P1
Sous vtesse
Underfrequency
NT1950050/a-11/92 f:2/2
18
AVR
Model R630
PID, LIMIT
card
1 - FUNCTIONAL
2 - ADJUSTMENTS
- This card, from Vm (machine voltage image), Vref
(voltage set point) and complementary informations
given in the following, elaborates the voltage command
of the power driver card, which is the field current set
point.
- P1 : Ceiling unlocked voltage threshold adjust (normally 90% Un).
- P2 : Proportionnal branch gain adjust (large signal)
- P3 : Proportionnal branch gain adjust
- P4 : Integrative branch time constant adjust
- P5 : Derivative branch gain adjust
- P6 : Derivative branch time constant adjust
- P7 : Minimum field limitation adjust
- P8 : Minimum field limitation, active power correction
adjust
- Three operating modes are possible, depending of external informations :
• Solo operation or parallel operation between equivalent machines (1 Fonction)
(this is the normal mode)
3 - INPUTS / OUTPUTS
• Parallel operation with the mains with power factor
(COSØ) or KVAR regulation (2 Fonction)
(only if COSØ / KVAR card is fitted)
• Operation in voltage equalization mode between
machine and mains before coupling (3 Fonction)
(only if "MAINS I / O" CARD is fitted)
1F : Machine image Vmis compared with the sum of
Vref, Pext, etc voltages depending of used options and
the resultant voltage (error voltage ) feeds the PID.
2F : When cosØ cmd input is activated (+Vcc), the
machine voltage Vm is compared to the voltage given
from the cosØ/KVAR card and the result (error voltage)
feeds the PID.
3F : When U/U cmd input is activated (+Vcc), the machine voltage Vm is compared to the voltage given from
the "MAINS I / O" card and the result (error voltage)
feeds the PID.
A compensation external input, given for specific applications is added to the error voltage and the resultant
voltage is the real PID input. Each branch (P, I, D) of the
PID, independently adjustable from the others, set the
time constants of the AVR in regard to the generator.
The integrator branch can be short-circuited, for example
when starting-up.
These three outputs are added, limited to 10Vdc and
then give the field current set voltage of the "automatic
channel" which is the driver card input.
The minimum value of this signal can be limitated to
avoid total loss of excitation of the generator. In case of
parallel operation with the mains (cosØ/KVAR card), this
limitation is a function of the active power supply by the
generator, this information is given by the COSØ / KVAR
card.
A separate stage detect if the generator voltage is below
an adjustable value to unlock the normal field ceiling voltage from 110% of nominal to 160% (adjustable).
- 11a : Voltage reference set point input. Vref
- 13c : Added signal to voltage reference set point input
(option)
- 22c : Added signal to voltage reference set point input
(external voltage option)
- 21a : Added signal to voltage reference set point input
(external potentiometer option)
- 13a : Added signal to voltage reference set point input
(differential droop option; with cosØ/KVAR card)
- 19a : Integrator short-circuit command input
- 10a : Mains image voltage input (3F) (with "MAINS I /
O" card only)
- 14c : CosØ error voltage input (2F) (with cosØ/KVAR
card)
- 25c : Voltage equalization command input (3F) (with
"MAINS I / O" card only)
- 24a : CosØ regulation command input (2F) (with
cosØ/KVAR card)
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common electronic ground
- 14a
: Minimum field limitation, active power correction input
- 15c
: Field current voltage control output "AUTO"
channel
NT1950060/a-11/92 f:1/3
19
AVR
Model R630
PID, LIMIT
card
MIMIC DIAGRAM PID, LIMIT CARD
Vref
11a
Vpot dig
13c
+
+
Vstat
13a
-
CdeU
22c
+
+
Pext
21a
Vres
10a
CdeU/U
Vm
CosØ
+
-
static
relay
∑
+
P
-
25c
I
11c
14c
CdeCosØ
24a
V Externe
12c
Cct integ
19a
Vm -10%
∑
static
relay
static
relay
D
9c
∑ ++
+
Vm
11c
-
Vref
11a
+
IcosØ
14a
If min
limit
PID &
LIM Iexc
P1
Vm
min
P3
P
P4
I
P5
D
FRONT VIEW
PID CARD
LIM Iexc min
P7
Limit
Iexc min
NT1950060/a-11/92 f:2/3
20
10V
15c
AUTO output
- 15V
0V
+ 15V
Fim da
rampa
Cct Int
Vref
-10%
Cmd P.F
P.F /
KVAR
Corr ext
Vm
Cmd U/U
U mains
Droop
Pot ext
Cmd U
Pot dig
Vref
32c,32a
16a,17c
1c,1a
19a D8
25a D7
11a
9c
24a
12c
14c
11c
25c
10a
13a
21a R40
22c R39
13c R2
11a R1
C10
C9
ST1
R23
C8
C7
R3
R6
R7
CI1
R8
Vdd
Vcc
C5
R43
R25
A
CI1
R24
Vcc
(Positive = desexcitation)
D11
D10
R22
R21
P1
D6
R4
CI1
R5
C6
R9
VL
8
2
14a
6
4
Vcc
3
1
IcosØ
P7
L1
P8
8
R13
R17
10
9
MN2
R30
10
9
R14
MN3
CI1
R12
R45
R28
R29
D10
Lim Iexc min
R31
R11
Vcc
R27
R46
R26
R10
C1
Vdd
CI4
7
5
VL
8
2
8
6
4
Vcc
D9
R18
C2
Vdd
7
CI5
5
VL
3
1
12
13
R42
MN3
D
I
P
C4
R19
R41
D2
D1
14
R34
R33
R32
R20
D4
7
P3
CI2
P5
CI2
D3
1
6
Z1
5
3
R37
R36
D
I
P
Principle diagram
PID, limit card
CI2
C11
2
4
Vcc VL
CI1
R35
C3
8
CI6
D5
Vdd
A
P4
P6
R16
P2
R15
CI3
R38
19c
15c
Min
Iexc
S auto
AVR
Model R630
PID, LIMIT
card
NT1950060/a-11/92 f:3/3
21
AVR
Model R630
Driver
card
1 - FUNCTIONAL
2 - ADJUSTMENTS
This card controls from "AUTO" and "MANU" voltage
reference and some additional informations detailed in
the following, the exciter field current supply by the regulator and the booster (if used).
- P1 : Integrator time constant adjust.
- P2 : Unlocked ceiling time delay adjust. (generally 5s)
- P3 : Alarm time delay adjust after ceiling unlock.
- P4 : Permanent ceiling value adjust (generally 1,1If nominal)
- P5 : HALL sensor range adjust.
- P6 : Initial ramp-up adjust
- P7 : Maximum field current adjust (machine short-circuit)
- P8 : Maximum fieeld current in case of heatsink overheating.
- Three operating mode are possible, depending of external informations :
• Normal mode with 110% ceiling of If nominal.
• Ceiling unlocked mode (160% minimum Ifield nominal) depending of the command input from the PID card
with limited delay and alarm output in case of sustained
undervoltage.
• Maximum ceiling mode if the synchronisation voltage
desappears ( machine short-circuit) with limited (adjustable) field current.
- The "AUTO" or "MANU" reference voltage depending of
the associated command input and also of the active
limitations, is compared to the field current measurement
and gives the error voltage which is after integration,
compared to a sawtooth feed by the synchronisation voltage. The output of this stage is a variable duty cycle
signal which controls the power transistors throught isolating optocouplors.
- This card can be supplied in three manners :
• From the general supply of the rack in normal operation
• Throught an isolated supply taken from the field
voltage during start-up or generator short-circuit (Rack
supply not present)
• Directly from the field voltage for power transistor
command.
The permanent limitation (110% de Iexc nominal) can
be modified by the following conditions:
- Field ceiling unlocking on machine undervoltage condition. It inccreases from 110% (normal operation) to a
minimum of 160% of the nominal field current during an
adjustable time delay and then go back to 110%. An
alarm is activated if this undervoltage is sustained afterward.
- Field ceiling unlocking on synchronisation voltage abcence. It increases to the maximum given by the sett-ing
of P7.
- Field ceiling limitation caused by power heatsink overheating. On thermocontact action the ceiling is reduced
to a value given by the setting of P8.
A separate circuit monitors the instantaneous current of
the power transistor and reduces immediatly the command signal if its value increases above a fixed value.
(Exciter or wiring short-circuit protection ).
NT1950070/b-11/93 f:1/3
22
3 - INPUTS / OUTPUTS
Flat cable (BUS 64points)
- 15c
: If reference set point input "AUTO" channel
- 15a
: If reference set point input "MANU" channel
- 25a
: "AUTO / MANU" command input (0V = "AUTO")
- 9c
: Unlocking ceiling command input
- 4a, 4c : Synchronisation voltage input
- 26c
: Heatsink thermocontact input
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- 17a
: Field current measure output
- 19a
: End of ramp-up output signal
- 31a
: Alarm output
Card connector (8 points)
- 1 : Field voltage
- 2 : Main transistor drain
- 3 : Main transistor gate
- 4 : Booster transistor gate
- 5 : Power ground
- 6 : +Vcc HALL sensor
- 7 : -Vcc HALL sensor
- 8 : HALL sensor measure output
AVR
Model R630
Driver
card
MIMIC DIAGRAM DRIVER CARD
Driver card
8pts connector
Supply +/-15Vdc
32a
32c
16a
17c
1a
1c
Auxiliairy
isolated supply
supply
+Vcc
-Vdd
Measure
0 - VDC
Synchro
Loss of synch
15c
AUTO input
15a
Auto / Manu cm
25a
If set point outp
16c
Alarm outpu
+Vcc
-Vdd
Converter I/U
short-circuit
monitoring
4a,4c Synchronisatio
Synchro loss
18c
MANU input
Unlock ceilin
input
0V
17a
9c
Static Relay
+
+
PID
Opto
+
Ipl
+Vdc Power supply
6
7
8
}
HALL sensor
2
Transistor Drain
4
Booster transistor cmd
3
Principal transistor cmd
5
Power GND
HALL sensor supply
PWM
GND
Ts
1
Ramp
Limit 1
31a
Lim max
If limit valu
18a
End of ramp
19a
Heatsink
thermocontac
26c
DRIVER
Iexc max
P7
Iexc lim
P4
FRONT VIEW
DRIVER CARD
T ramp
P6
T Iexc lim
P2
Vm min
Ramp end
NT1950070/b-11/93 f:2/3
23
9c
Vmin
16c
Cmd
25a
M
15a
15c
A
18c
4c
R19
3
8
2
4
Vcc
C2
D5
R26
D8
R61
I
6
C17
Vcc
5
9
8
CI 2
CI 2
R22
R21
Vdd
7
R18
R17
R15
P1
14
2
C4
3
2
D3
1
D9
11
10
7
C11
CI 2
CI 2
8
C1
D4
R10
CI 1
T alarme
6
R24
Vcc
CI 1
C5
9
10
D7
R16
R27
R23
Vcc
C3
Ts
Q2
14
Z6
Q1
CI 1
R5
R60
12
18
Vcc
1
R12
D26 4
5
R2
CI 4
D2
R3
R4
R8
R9
C20
13
1
5
6
R25
Q3
7
7
OPT1
ALARME
31a
R30
CI 1
3
2
Vcc
P4
Lim Iexc
110%
R29
R28
Vcc
C6
R31
-15V
R11
5
6
8
19c
D10
Z1
18V
C15
C13
Vdd
C14
R63
Z5
Vcc
D20
D21
D22
1a
1c
R51
D11
Z2
Q4
R55
+Vcc
Lim I
18a
R34
R1
R14
0V
R32
+15V
R33
Sync
0 -10V
R13
1
4
Qxx
14
Rxx
Zx
8
F R 19a
2
5
4
CI 3
CI 3
1
R52
Q6
12
13
9
10
CI 3
C9
Q7
D18
R46
C12
R49
C8
R45
CI 3
5
Maxi
iexc
Z4
Gamma Iexc
P5
7
Q11
3
2
1
P8
Lim TC
R47
6
5
Vcc
6
8
C hall
Principle diagram
DRIVER card
R58
D17
D25
D24
Vcc
I
R39
D16
R57
Q10
R37
D15
Vcc
Q12
R59
Rampa
R50
3
2
Q9
C7
C16
18V
18V 18V
R62
Q13
D14
Q8
C18
Cmd
booster
D12
Q5
18V
C/C1
OPT3
R56
32a 16a
32c 17c
R35
D1
R20
R40
4a
LED1
R36
D13
R38
R41
R6
P2
R42
Z3
R43
Vcc
P3
OPT2
LED2
P6
24
R44
NT1950070/b-11/93 f:3/3
P7
C10
R48
Vdd
7
Vexc
Tc
26c
17a
I
-A
E-
+A
+E
AVR
Model R630
Driver
card
AVR
Model R630
Cos Ø - kVAR
Optional card
1 - FUNCTIONAL
per (CAV) on the card (internal).
This card elaborates from generator current and voltage
informations, the following signals:
2 - ADJUSTMENTS
- An image of the reactive current of the generator
named (KVAR) used for KVAR regulation.
- An image of the phase shift between the voltage and
the current of the generator named (Ø) used for cosØ
(PF) regulation.
- P1
- P2
- P3
- P4
- P5
- P6
- P7
: KVAR internal setting.
: PF (cosØ) internal setting.
: Voltage phase shifter (internal)
: PF (cosØ) gain setting
: KVAR gain setting.
: Différential droop setting
: Pulse width setting (internal)
- Jumper CAV : Selection of droop type
- An image of the active current of the generator named
(KW) used for compensate the minimum Ifield limit of the
PID card.
- The principle of measurement is to sample and hold the
instantaneous value of the current when the instantaneous voltage reaches zero on positive slope.
- First the current image of the stator current is filtered
and used directly for KVAR measure. Then it is derivated
and used for KW measure. And then it is amplified to
obtain square waves and integrated to give a sawtooth
used to Ø measure.
- The voltage image is phase-shifted to compensate the
phase shift of the current input filter and after amplification is fed to a monostable which gives the pulse signal
(about 100µs) used by all the sample and hold circuits.
- KVAR and Ø values are compared with an internal and
external (if used) setting and the difference is send to
the PID card as an error signal. An external contact
control an analog switch to select what information between KVAR and Ø will be regulated.
- Three informations (Ø, ∆Ø, ∆KVAR) can be used as an
alternative droop for solo operation.
• Ø gives no droop at cosØ=1 and the voltage decreases
at lagging PF.
• ∆Ø gives no droop at the cosØ setting and the voltage
decreases at more lagging PF and opposite for more leading PF.
• ∆KVAR gives no droop at the KVAR value setting and
the voltage decreases with more KVAR and increases if
less.
No
: Reactive droop adjusted by P1 (sensing card)
CAV1 : No droop for cosØ=1 and droop if lagging.
CAV2 : No droop for KVAR setting (P1), voltage decreases if more KVAR (lagging) and opposite if less.
CAV3 : No droop for PF setting (P2), voltage decreases
if more lagging and opposite if less or leading.
Nota : If the droop is used from this card, potentiometer
P1 of the sensing card must be set to zero.
3 - INPUTS / OUTPUTS
Flat cable (BUS 64points)
- 8c
: Generator voltage image input
- 9a
: Generator current image input
- 20a
: Command input "cosØ / KVAR"
(0V = "cosØ")
- 21c
: External KVAR setting input
- 20c
: External cosØ setting input
- 1a,1c : +15Vdc supply (Vcc)
- 32a,32c : -15Vdc supply (Vdd)
- 16a,17c : Common electronic ground
- 14c
: Error signal output to PID card
- 13a
: Droop signal output to sensing card
- 14a
: KW signal output to PID card
- 12a
: KVAR signal output
- 10c
: Ø signal output
- The selection between these is made by mean of jum-
NT1950080/b-10/94 f:1/3
25
AVR
Model R630
Cos Ø - kVAR
Optional card
MIMIC DIAGRAM COSØ - KVAR CARD
IsinØ
CosØ
12a
10c
external
KVAR setting
21c
Vac
8c
Phase shifte
external
cosØ setting
20c
Monostable
CosØ/KVAR
cmd
20a
KVAR
CT //
9a
Sample
and hold
Filter
IsinØ
Gain
KVAR
KVAR
KVAR
Ø
14c
1c,1a
+Vcc
d( )/dt
∫ ( ) dt
Sample
and hold
Gain
COSØ
Ø
2
3
1
CAV
-Vcc
32c,32a
16a, 17c
0V
Sample
and hold
COSØ, KVAR
KVAR
P1
Gain kvar
P5
FRONT VIEW
COSØ - KVAR card
Cos Ø
P2
Gain cosØ
P4
Statisme D
P6
NT1950080/b-10/94 f:2/3
26
IcosØ
CosØ
Diff droop
13a
KW
14a
CR02
CR01
R50
0V
-Vcc
+Vcc
0V
C01
R04
U V W
8c
32c,32a
1c,1a
17c
16a
TR1
0V
S2
TI//
S1
9a
R01
CR04
CR03
C05
0V
TP2
MA1
R51
R28
R26
R06
C06
R21
C11
R20
R05
MA1
C02
0V
C12
P03
R52
C25
R22
R08
MA1
R07
TP8
MA4
R53
R30
R55
R54
C13
2
3
2
1
C04
4
MA5
7
R56
C14
C15
6
TP9
R41
MA3
R47
TP5
R42
2
6
MA10
CR10
R44
-Vcc
T1
R32
MA4
+Vcc
R18
TP6
R17
R16
MA3
R19
3
MA7
2
C16
4 1
R35
R34
R33
P05
Ø
C17
3
5
16
7
P07
TP10
R39
2
8
6
Cde
UcosØ
20c
IcosØ
14a
Erreur
14c
0V
R38
20a
21c
Ukvar
R38
+Vcc
HR
P04
R29
13a
HR
P06Stat D
R27
10c
12a
CAV1-3
MA8 1
C26
to 30
Gain Ø
R36
MA3
R37
Gain K
HR
IsinØ
principle diagram
COSØ - KVAR card
8
R59
R43
HR
P02
COSØ
R31
MA3
HR
R15
R14
TP7
+Vcc
C10
1
R46
R57
Cde
2
1
C09
Cde
6
MA9
-Vcc R13
P01
KVAR
+Vcc R12
MA2
TP4
MA2
C07
Cde
6
MA6
R40
R25
C24
R24
TP1
C20-21
MA2
R11
MA1
R10
TP3
C08
MA2
R23
R09
C03
C31
R03
CR05
R02
R58
AVR
Model R630
Cos Ø - kVAR
Optional card
NT1950080/b-10/94 f:3/3
27
AVR
Model R630
Optional mains
I/O
1 - FONCTIONNAL
input / output terminals.
- This unit is mainly an interface between external signals
and low power electronics.
- It is composed by :
• The adaptation three phases transformer between
input voltage and measurement circuits.
• The AC/DC converter to give an image voltage of the
mains voltage.
• The interface input relays between command / control
terminals and internal circuits.
• The interface between 64pts BUS and the analogic
- P01 : Ur setting for mains nominal voltage. (10Vdc for
nominal value)
3 - INPUT / OUTPUT
See following table.
INPUT
TERMINAL
Connector
32 PTS
Type
I/O
Interface
Connector
26 PTS
Connector
BUS 64 PTS
12
13
14
15c
13c
11c
sensing
sensing
sensing
3Ø transformer TP4
3Ø transformer TP4
3Ø transformer TP4
13
17
21
5a
6c
6a
51
52
54
55
56
57
58
59
60
1a
3a
2a
4a
5a
6a
7a
8a
9a
signal
signal
spare
spare
spare
spare
spare
spare
spare
direct
direct
3
5
7
2
4
6
8
10
12
15a
27c
27a
28c
28a
29c
29a
30c
30a
36
4c
2c
3c
2c
cmd input
cmd input
cmd input
cmd input
relay
relay
relay
relay
1
9
14
9
25c
1c
20a
1c
10c
9c
GND
thermocontact
direct
direct
25
26
16a, 17c
26c
53
NT1950020/b-10/94 f:1/3
28
2 - ADJUSTMENTS
AVR
Model R630
Optional mains
I/O
12
U mains
15c
13
Terminal
N° 13
V mains
11c
17
W mains
7c
21
14
5a
6c
6a
25
16a, 17c
TP4
+Vcc 1c
AC
10a
DC
L1
L2
L3
-Vcc 32a
3c
P.F / Kvar
48 53
Terminal Bl
CR16
14
35 36
Terminal Bl
K1
9
1
2c
+12Vdc U/U
25c
R26
CR15
5c
Reserve
20a
R27
4c
Cmd U/U
2c 16a
To 32pts J1
generator I/O
K2
K3
11
Thermostat
51 Cmd Ifield
52 Pot MANU
Reserve
54
55
Reserve
Terminal 56
Reserve
N°
57
Reserve
58
Reserve
59
60
10c
9c
25
26
3
5
7
2
4
6
8
10
12
1a
3a
2a
4a
5a
6a
JUMPERS
Thermostat
7a
8a
9a
Reserve
Reserve
Connector male
DIN41612 32Pts
2
11
MA1/1
0V
1c,1a
R02
26c
15a
27c
27a
28c
28a
29c
29a
30c
30a
Connector
HE10 26Pts
16a
17c
31c
R31
CR17
R22
3
PRINCIPLE DIAGRAM
CR1
1
4
R07
MAINS I/O AC/DC
PT4
C01
+Vcc
6
CR9
MA1/2
CR10
CR2
7
R10
MA2/3
5
R13
MA1/3
R01
R23
R03
PT2
PT3
CR11
R05
R04
CR3
8
13
MA1/4
11
MA2/1
3
10a
Ur
12
R18
R15
0V
+Vcc
R12
CR13
C05
14
R11
12
R24
C02
13
CR4
14
0V
2
R17
P01
PT5
R08
5a 6c 6a
R25
R21
10
CR12
8
MA2/4
9
0V
R16
9
10
PT1
PT7
R14
32c,32a
-Vcc
Connector
41612 64Pts
CR8
R20
CR5
1
L1
4
R09
PT6
R06
6
CR14
MA2/2
0V
Q01
CR6
7
5
R19
TP4
U V W
0V
NT1950020/b-10/94 f:2/3
29
AVR
Model R630
Optional mains
I/O
10TE
LED
TP4
P01
Connect
Connect
relais
LED
relais
LED
relais
LED
INTERNAL VIEW
MAINS I / O
RESEAU E/S
MAINS I/O
Reseau
P01
FRONT VIEW
MAINS I / O
PT1
PT2
PT3
PT4
PT5
PT6
S1
PT7 CosØ / Kvar
U/U
NT1950020/b-10/94 f:3/3
30
AVR
Model R610 / R630
Digital pot U / P.F
Optional card
1 - FUNCTIONAL
2 - ADJUSTMENTS
This card replace two conventional motorized potentiometers :
• One for the remote voltage setting.
• One for power factor or reactive current setting.
- P1 : Clock speed (total range time)
- P2 : Voltage range value
- P3 : P.F or KVAR range value
- SW1 : Voltage range polarity (0/+ or +/-)
- SW2 : P.F or KVAR range polarity (0/+ or +/-)
- Switch between the two modes is made by the external
P.F regulation order (terminals 33, 34) and switch between P.F and KVAR setting is made by the external order (terminals 48,53)
- Each last position is memorized when the control is
switched or when the machine is stopped.
- Jumps (SW1 and SW2) allow the choice between
unipolar or bipolar voltage output and the range is adjusted
by means of potentiometers P02 and P03.
- Jumps SW3 and SW4 must be open for normal operation and are only used for special applications.
- Speed of all adjustments is controled by potentiometer
P01.
3 - INPUTS / OUTPUTS
Flat cable (BUS 64 points)
- 24c
: Cmd lower
- 23a
: Cmd upper
- 16c
: If reference set point input
- 15c
: If reference set point input "AUTO" channel
- 24a
: External P.F regulation order
- 20a
: External P.F or KVAR regulation order
- 13c
: Voltage setting output to PID card
- 20c,21c : P.F or KVAR setting output to P.F card
- 30a
: Maximum position of settings
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- Two LED's (L1,L2) indicate the command orders + or and four other LED's (L3,L4 and L5,L6) indicates the
maximum and minimum position of voltage and P.F
settings
NOTE : When this card fitted, the internal voltage
setting (P05 on sensing card) must be used to give
the center position of the range (if bipolar range) or
the minimum setting in case of unipolar range (idem
for P.F and Kvar internal setting on P.F card). An
external setting potentiometer must not be used, the
settings are made only by mean of push-buttons on
terminals 42, 43, 44.
NT1950110/a-01/94 f:1/3
31
AVR
Model R610 / R630
Digital pot U / P.F
Optional card
Digital pot U / P.F CARD MIMIC DIAGRAM
UP
Cmd +
INC
Logic
static
relay
DOWN
Cmd -
24c
Cmd P.F
24a
Max
U/D
23a
30a
CS
0V
SW1
SW2
-Vref
U/D
Clock
Min
Max Pos
Digital
pot U
P01
Speed
INC
Max
Digital
pot P.F /
KVAR
Min
CS
U range
+
P.F / Kvar
range
-
static
relay
P.F Output
Kvar Output 20c
Kvar Cmd
DIGITAL
SETTINGS
HAUT
UP
BAS
DOWN
MAX
Voltage
FRONT VIEW
MIN
Digital pot U / P.F
MAX
CosØ - Kvar
MIN
P1
SPEED
NT1950110/a-01/94 f:2/3
32
21c
20a
R45
R47
R44
R43
R46
R42
0V
16c
Cde Iexc
Sauto
15c
Cde +
Cde -
R17
R16
R11
23a
6 - P2
5 - P2
MIN
L4
L3
Voltage
MAX
15c
Sauto
16c
CR11
CR10
MIN
L6
L5
CR8
R7
R4
R3
R9
R25
30a
R41
C2
MN2
R24
MN2
R40
C1
R8
MN2
pot end
R20
R19
CR8
Cde Iexc
+Vcc
-Vcc
R2
R1
cosØ kvar
MAX
CR9
CR7
-Vcc
3 - P2
5 - P1
6 - P1
MN3
R18
SW4
CR5
-Vcc
+Vcc
3 - P1
MN3
R23
MN2
R22
SW3
CR4
R10
-Vcc
+Vcc
24c
32c,32a
1c,1a
R21
CR3
R6
R5
CR2
T2
CR1
T1
R49
R51
R48
R50
L2
L1
MN6
C08
AND
AND
R15
R13
+5V
MN10
P03
MN10
P02
R32
R30
R31
MN1
HR
AND
AND
MN6
+5V
HAUT / HIGHT
+Vcc
R14
R12
BAS / DOWN
+Vcc
P01
R33
MN7
AND
AND
MN7
CR06
S4
U/D
7805
Range
+/-5V à +/-10V
Range
+/-5V à +/-10V
S2
S1
0V
+Vcc
REG1
0V
Vref
0V
C3
R26
C7
11a
R29
3
1
-Vcc
R34
AND
AND
7
1
R36
3
8
2
4
5
0V
7
4
R38
+Vcc
8
8
POT1
VOLT
4
R54
R53
R39
0/+ +/SW1
6
5
3
+/- 0/+
SW2
CosØ / kvar
20a
20c UcosØ
21c Ukvar
13c
Pot Tension
MN1
5
3
6
POT2
COSØ
0V +5V
1
7
2
R37
INC
CS
U/D
INC 1
CS
U/D 2
Principle diagram
Digital pot U / P.F / KVAR
R52
6
MN4
MN1
AND
AND
+Vcc
-Vcc
R35
S4
MN8
2
8
R28
7 45
MN9
6
24a
Cde cosØ
+5V
R27
AVR
Model R610 / R630
Digital pot U / P.F
Optional card
NT1950110/a-01/94 f:3/3
33
AVR
Model R630
Manual mode 1
Optional card
1 - FUNCTIONAL
2 - ADJUSTMENTS
This card elaborates from internal setting (PO2) and
external setting informations, the Ifield command signal
given to "MANU" channel of the driver card.
- P1
- P2
- P3
- P4
- The Ifield output signal is limited or reduced if the generator voltage exceeds the limitation value sets by the
potentiometer P01 (trip of the main breaker on load for
example).
- This case of operation is indicated by the LED "LIMIT"
and the Ifield setting must be decreased to a point under
control.
- On MANU operation, the difference between MANU
output and AUTO channel output gives a compensation
signal which is used to compensate the PID to have
always the MANU and AUTO channels outputs identical.
With this circuit a smooth switching between MANU to
AUTO is possible and operation will go back to the
AUTO channel own settings.
- The ceiling can be unlocked on this operation, that is
why it can be necessary to wait some seconds after the
switching to return on MANU operation.
- On AUTO operation, these two channels are also monitored and the difference is indicated by three LEDs.
• HIGH says that MANU channel is higher than AUTO
• LOW says that MANU channel is lower than AUTO
• OK says that MANU and AUTO channels are identical
and smooth AUTO ---> MANU switching is possible.
NOTE : If a Ifield digital potentiometer is used, the
internal setting (P02) must be set to 0 or under the
no load field value and an external setting potentiometer must not be used. In that case the setting is
made only by mean of push-buttons on terminals 44,
45, 46.
NT1950100/b-10/94 f:1/3
34
: Voltage limitation setting
: Internal Ifield value setting
: PID compensation gain setting
: Internal compensation setting
3 - INPUTS / OUTPUTS
Flat cable (BUS 64points)
- 4c
: 24Vac input image of the generator
from "generator I/O" card
- 25a
: "AUTO / MANU" command input
(0V = "AUTO")
- 16c
: If reference set point input
- 15c
: If reference set point input "AUTO" channel
- 27c
: External Ifield setting input
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- 15a
: If set point output "MANU" channel
- 12c
: PID compensation output
- 9c
: Ceiling locked output
AVR
Model R630
Manual mode 1
Optional card
MANUAL MODE 1 CARD MIMIC DIAGRAM
24Vac
4c
AC / DC
Filter
+
PI ampli f
-
1c,1a
-
S manu
15a
+
External If Control
+Vcc
27c
Voltage
limitation
-Vcc
32c,32a
Ifield
setting
0V
16a, 17c
Ceiling
locked
9c
Limitation
ET
+
If setting
too high
Cmd
auto/manu
PID
Correct
25a
S manu
+
S auto
-
12c
relais
statique
Ifield
Cmd
16c
-
S auto
15c
+
Gain
If setting
too low
+
ET
If setting OK
-
MANUAL
MODE
LIMIT
HAUT
HIGH
LOW
BAS
OK
FRONT VIEW
Manual mode
P3
Seuil
P2
Iexc
P1
Gain
NT1950100/b-10/94 f:2/3
35
36
NT1950100/b-10/94 f:3/3
4c
CR01
CR02
R01
R35
R36
Cde Iexc 16c
Sauto 15c
7
P03
MA2/2
5
R38
6
6
7
R33
MA1/2
R04
MA1/1
1
3
MA3
5
6
3
2
-Vcc
+Vcc
R37
R30
8
4
R03
R02
R32
R31
-Vcc
+Vcc
25a
9c
Correction
12c
Integrale
du PID
+ = désexcité
Cde
auto / manu
inhibition
déblocage
plafond
16a, 17c
0V
24Vac
32c,32a
1c,1a
R34
R05
HR
7
CR04
CR03
1
C01
R07
R08
Sauto
Smanu
Smanu
Sauto
T01
R06
R51
R50
R41
R40
R42
4
MA2/3
10
R53
9
R52
12
R43
MA2/4
R10
P01
13
14
-Vcc
MA1/4
R09
12
13
C02
R44
CR10
P02
R54
11 CR20
8
14
HR
MA1/3
C03
R55
CR21
R45
CR11
HR
R15
R11 +Vcc
R12
R13
CR05
R56
R57
R46
1K
R47
R28
R29
R14
R16
CR06
CR12
T03
CR23
BAS
T04
OK
LIMIT
R23
0V
+Vcc
-Vcc
27c
Cde U
Smanu
15a
Principle diagram
Manual mode 1 card
R61
R62
CR31
CR08
T05
R27
MA3/1
R25
R26
CR30
R60
R21
R22
P04
R24
CR09
HAUT
MA3/1
R39
CR07
CR13
T02
R17
R19
MA2/1
R20
R18
AVR
Model R630
Manual mode 1
Optional card
AVR
Model R630
1 - FUNCTIONAL
Digital pot Ifield
Optional card
This card replace one conventional motorized potentiometer in "MANU" mode and sets the "MANU" channel
output always equal to the "AUTO" one to allow the
smooth switching between the "AUTO" and "MANU" operation at any load (follower in "AUTO" mode).
2) ADJUSTMENTS
- P1
: Clock speed (Time delay in follower mode)
- P2
: Clock speed (range time in "MANU" mode)
- P3
: Ifield range value
- SW1
: Voltage range fixed or U/F monitored
- SW3/4 : Normal (open) or follower (closed) operation
- Switch between the two modes is made by the external
"AUTO / MANU" order (terminals 47,48)
3 - INPUTS / OUTPUTS
- Jumps SW1 allows the choice between voltage output
taken from U/F control of the sensing card or from a 5V
fixed reference and the range is adjusted by means of
potentiometer P03.
- Jumps SW3 and SW4 must be open for normal operation and closed for follower operation.
- Speed of the adjustment is controled by potentiometer
P01 in manual setting and by P02 in follower operation.
P02 acts as a delay between an "AUTO" output variation
and the "MANU" output response.
Flat cable (BUS 64points)
- 23c
: Cmd lower
- 22a
: Cmd upper
- 25a
: Cmd "AUTO / MANU"
- 11a
: U/F voltage reference
- 16c
: If reference set point input
- 15a
: If reference set point input "MANU" channel
- 27c
: Ifield setting output to Manual mode card
- 30a
: Maximum position of settings
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- Two LED's (L1,L2) indicate the command orders + or and two other LED's (L3,L4) indicates the maximum and
minimum position of Ifield settings
NOTE : When this card is fitted, the internal Ifield
setting (P02 of manual mode card) must be set to 0
or under the no load field value and an external
setting potentiometer must not be used. The Ifield
setting is made only by mean of push-buttons on
terminals 44, 45, 46.
NT1950115/a-01/94 f:1/3
37
AVR
Model R630
Digital pot Ifield
Optional card
Ifield digital pot CARD MIMIC DIAGRAM
UP
Cmd I+
U/D
22a
INC
Logic
DOWN
Cmd I-
CS
23c
Out
Digital
pot 2
In
Max Pos
SW4
30a
SW3
+5V
Vref
P01
Follower Speed static
SW1
U/D
relay
INC
Clock
In
Digital
pot 1
Max
Min
Out
CS
P02
Manu Speed
Cmd
Auto/Manu
25a
Iexc range
16c
Smanu
Iexc set Output
-
+
+
15a
Cmd Ifield
+
Iexc DIGITAL
SETTING
HAUT
UP
BAS
DOWN
MAX
Iexc
FRONT VIEW
MIN
Digital pot Ifield
P1
SPEED
NT1950115/a-01/94 f:2/3
38
27c
R16
22a
R43
R46
R42
0V
16c
Cde Iexc R17
Smanu
15a
+I
-I
23c
32c,32a
1c,1a
R23
SW4
CR5
-Vcc
R18
6 - P2
5 - P2
-Vcc
CR9
CR7
+Vcc
3 - P2
MN2
R22
SW3
CR4
R11
R10
-Vcc
+Vcc
MIN
L4
L3
MAX
15a
Smanu
16c
CR8
R20
Cde Iexc R19
+Vcc
-Vcc
R2
R1
MN2
R40
pot end
R9
R8
R21
30c
MN2
MN2
C2
R24
R25
R7
R4
R3
C1
CR3
R6
R5
0V
Cde A/M
25a
+Vcc
-Vcc
CR2
T2
CR1
T1
R1
7
4
5
2
8
R30
6
R15
R13
3
1
P01
C08
AND
R48
HR
MN6
HIGHT
HAUT
R14
R12
DOWN
BAS
AND
MN9
L2
L1
R31
R32
MN1
AND
AND
MN6
+5V
+Vcc
+5V
+Vcc
HR
P2
S2
S1
R33
MN7
AND
AND
MN7
S4
U/D
CR06
0V
+Vcc
REG1
0V
C3
R26
R49
R51
0V
+5V
Vref
7805
0V
11a
AND
SW1
R34
S4
MN8
AND
C7
+5V
46
R52
27c
Pot Manu
3
5
3
5
8
+5V
8
POT1
0V
1
7
POT2
64
Range
+/-5V à +/-10V
MN1
INC
CS
2
1
7
2
+5V
Principle diagram
Ifield digital potentiometer
P03
R36
R35
AND
AND
U/D
INC
CS
U/D
0V
AVR
Model R630
Digital pot Ifield
Optional card
NT1950115/a-01/94 f:3/3
39
AVR
Model R610 / R630
1 - DESCRIPTION
This card is used when the P.F or KVAR regulation is
wanted not at the generator terminals but at the mains
input. For this a P.F or KVAR sensor with 4-20mA output
is necessary and it must be located at the place where
the regulation must be made.
2 - FONCTIONAL
This card elaborates from setting informations and 420mA signal image of P.F (or KVAR) of the mains, the
errorvoltage dending to the PID of the PID card.
- The error signal have an ajustable gain and can be inversed depending of the 4-20mA sensor output.
- This kind of operation is indicated by the LED "L3" and
by a contact (potential free) on the front connector.
- This operation is selected by mean of a contact on front
connectort and will be active on coupling when contact
between terminals 33, 34 of main terminals will be closed.
If the contact on front connector remains open, the regulation (P.For KVAR) will be made at the generator output,
if it is closed, this is the 4-20mA information wich is regulate function of the internal settings (P2 or channel 2 420mA) or/and external by the front connector.
- If during operation, the measuring 4-20mA signal
deseappears, control is automatically return to regulation
on the generator output side and this failure is indicated
by LED L1 ou L2 and by a contact on front connector.
- A second channel can be used as set point of the first
channel or as a remote adjustment of voltage, P.F or
KVAR on generator side. As on channel 1 if the 4-20mA
deseappears, output is inhibited and indicated by LED
L2.
- A field current limitation is given, active when a contact
(front connector) is closed and indicated by LED L4. The
limitatio is adjusted by P7 (Limit 2 set) and can be set
between a maximum value preset by P7 on driver card
and a minimum value preset by P8 on driver card.
- An signaling contact on the front connector gives (if
they are used) the indication that one or more of the digital potentiometers are at maximum position .
3 - ADJUSTMENTS
Potentiometers
- P1 : Channel 1 range adjustment
- P2 : Reference set point channel 1
- P3 : Gain channel 1
- P4 : Channel 2 range adjustment
- P5 : Reference set point channel 2
- P6 : Gain channel 2
- P7 : Limit 2l adjustment
NT1950120/a-04/94 f:1/3
40
Mains P.F Regulation
Optional card
Jumpers - CV1 A
: Channel 1 used
- CV1 B : Channel 1 not used
- CV2 A : Channel 1 used
- CV2 B : Channel 2 not used
- CV3 A : Non inverting error channel 1
- CV3 B : Inverting error channel 1
- CV4 A : Non inverting error channel 2
- CV4 B : Inverting error channel 2
- CV5 A : Channel 1 in 4-20mA regulation channel 1
- CV5 B : Channel 1 in voltage setting
- CV5 C : Channel 1 in generator P.F setting
- CV5 D : Channel 1 in generator KVAR setting
- CV6 A : Channel 2 in 4-20mA regulation channel 2
- CV6 B : Channel 2 in voltage setting
- CV6 C : Channel 2 in generator P.F setting
- CV6 D : Channel 2 in generator KVAR setting
- CV6 E : Channel 2 in channel 1 setting
4 - INPUTS / OUTPUTS
Flat cable (BUS 64points)
- 12c
: Error output to PID
- 21a
: Output to voltage setting
- 20c
: Output to generator P.F setting
- 21c
: Output to generator KVAR setting
- 30a, c : Digital pot at maximum position
- 1a,1c : Supply +15Vdc regulated (Vcc)
- 32a,32c : Supply -15Vdc regulated (Vdd)
- 16a,17c : Common ground
- 23a
: Cmd + U or + P.F
- 24c
: Cmd - U or - P.F
- 14c
: Output of generator side P.F card
- 24a
: P.F regulation order
- 26c
: Limitation 2 output to driver card
Front connector (DB25 points)
- 13
: + 4-20mA input channel 1
- 25
: 4-20mA output channel 1
- 20
: 12V to external setting potentiometer ch 1
- 12
: External setting potentiometer cursor ch 1
- 24
: Ground to external setting potentiometer
- 11
: + 4-20mA input channel 2
- 23
: 4-20mA output channel 2
- 20
: 12V to external setting potentiometer (ch 2)
- 10
: External setting potentiometer cursor ch 2
- 22
: Ground to external setting potentiomete
-9
: 4-20mA failure (NO)
- 21
: 4-20mA failure (NF)
-8
: 4-20mA failure (Commun)
-3
: Digital pot at max position (NO)
- 15
: Digital pot at max position (NF)
-2
: Digital pot at max position (Common)
- 7,19
: Contact regulation ch 1 active (mains P.F)
- 14,1
: Contact limitation 2 active
LED
- L1, L2 : 4-20mA failure channel 1 or 2
- L3
: Channel 1 active
- L4
: Ifield limitation 2 active
AVR
Model R610 / R630
Mains P.F Regulation
Optional card
MAINS P.F REGULATION CARD MIMIC DIAGRAM
Connector
DB 25 points
Connector
64 points
20
24
4 -20mA
/ 0-10V
10Hz
Filter
-
FRONT CONNECTOR I / O
+12V
22
4 - 20mA
failure
0V
B
C
D
CV3
A
B
B
C
D
E
CV4
Open : reg
generator P.F
20c
21c
Ifield
Limit 2
12c
21a
Ref P.F
20c
Ref Kvar
21c
A
CV2
A
L2
K1
K1
9
8
16a, 17c
0V
-Vcc
15
K2
3
K2
K5
2
K1
24c
Limitation
Ifield 2
+Vcc
14
30c
23a
7
19
1c,1a
32c,32a
30a
Adapt
L3
Closed : reg
mains P.F
21a
Ref Kvar
+Vcc
Pot dig
at max
position
12c
Ref P.F
CV6 Corr PID
R
A Ref U
Int setting
channel 2
CV1
L1
21
4 - 20mA
failure
CV5 Corr PID
R
A Ref U
MA9
-
+
20
A
B
Gain
External setting 2
10
Pot ext
Ref 2
K5
Int setting
channel 1
0V
23
-
+
+12V
11
Chan 2
4 -20mA
External setting 1
12
Pot ext
Ref 1
Gain
10Hz
Filter
4 -20mA
/ 0-10V
25
REAR FLAT CABLE I / O
13
Chan 1
4 -20mA
0V
14c
24a
0V
26c
L4
1
aux I / O
25 13
MAIN
P.F ON
FRONT VIEW
MAINS P.F REG
4-20mA
1
OFF
2
Limit 2
14 1
ON
P2
Main
P.F
set
P5
Ref 2
set
P7
Limit
2
set
NT1950120/a-04/94 f:2/3
41
Limit 2
active
Reg P.F
gen
or
mains
+12V
1
14
19
7
20
Pot dig 15
3
at max
position 2
21
4 - 20mA 9
8
failure
LED
Failure
4 - 20mA
0V 24
0 - 10V 10
Ref 2
Channel 2
4 -20mA
23
11
0V 24
0 - 10V 2
Ref 1
Channel 1
4 -20mA
25
Front connector I / O
+Vcc
0V
+Vcc
0V
0V
L1 R24
L2 R51
CR6
R36
CR5
Converter
4 -20mA
/ 2-12V
R25
Converter
4 -20mA
/ 2-12V
K2
K1
CV1A
Q2
R58
C14
R43
R45
R71
R10
R09
R32
Q3
R61
+Vcc
P02
hr
R33
P05
hr
R11
R41
MA8
C15
+Vcc
MA7
C08
R12
R62
R63
+Vcc
R31
L4
R70
+Vcc
hr
Limitation
Ifield 2 adj
P7
CR7,8,14,15 : Relays free wheeling diodes
R60
R59
R57
R44
C07
R08
R15
42
CV2A
NT1950120/a-04/94 f:3/3
R39
13
R13
R34
R14
R16
C18
CR16
0V
K1
R64
CR10 CR12
CR09 CR11
R37
MA8
P06
R19
MA7
P03
R38
R66
Q4
CR13
MA8
R35
R18
MA7
R17
R53
R67
R65
R54
1
7
L3
20c
21a
-Vcc
+Vcc
0V
Q5
R69
26c
-Vcc
14c
24c
23a
24a
30c
30a
32c,32a
1c,1a
16a, 17c
Ref Kvar 21c
Ref P.F
Ref U
R52
12c
0V
Corr PID
K5 K51
R68
R56
D
C
B
20c
Ref Kvar 21c
21a
Ref P.F
12c
Ref U
R26
Corr PID
-Vcc
E
CV6
A
D
C
B
CV5
A
Principle diagram
mains P.F reg card
6
K5
MA9
4
5
3
2
R55
Q1
+Vcc
A
B
CV4
CV3
A
B
AVR
Model R610 / R630
Mains P.F Regulation
Optional card
Rear flat cable I / O
AVR
Model R610 / R630
LIMIT Istator
Optional card
1 - FUNCTIONAL
2 - REGLAGES
- A voltage, image of the stator current of the machine,
fed from the "ALTERNATOR I / O" card is rectified, filtered
and compared to a reference voltage. The error signal gives a voltage correction which is added to the main PID
input to maintain the stator current equal to the adjusted value.
- P1 : Stator current limit adjust. (about 2In to 4In )
- P2 : Ramp-up time adjust. (0,5 à 4s environ)
- P3 : Output signal gain
3 - INPUTS /OUTPUTS
- 9a
: Stator current image input (1Vac for In)
- 1a,1c : +15Vdc regulated (Vcc)
- 32a,32c : -15Vdc regulated (Vdd)
- 16a,17c : Common ground (GND or 0V)
- 12c
: Voltage correction output to PID.
- The reference voltage is applied with an initial ramp
ajustable from 0,5 to about 4s.
- A front LED signals stator current limitation operation.
- When this card is used for soft-start operation, the AVR
power transformer must be fed from a separate source
during the start operation and can be switched on the generator output when the voltage have reached the nominal value. The switching must be as fast as possible
(by relay, not by manual switch).
MIMIC DIAGRAM Istator limit card
TI //
9a
1c,1a
16a,17c
32c,32a
Seuil
Istator
AC / DC
Filter
+Vcc
0V
T
-Vdd
GAIN
+
RAMP
-
12c
Ampli PI
Limitation
LED
NT1950090/a-11/92 f:1/2
43
AVR
Model R610 / R630
R04
R02
MA1/1
9
MA1/3
8
R05
3
1
CR3
4
R06
R10
R11
R07
R09
10
CR01
11
2
C01
9a R01
LIMIT Istator
Optional card
6
MA1/2
R03
7
MA1/4
P01
CR4
C02
14
12
R08
5
CR02
C03
13
R12
0V
0V
16a
17c
(Positif = desexcitation)
0V
1a,1c
+Vcc
+Vcc
32a,32c
-Vcc
R27
R23
L1
C04
-Vcc
R19
C06
Q01
R25
R14
11
2
MA2/1
3
P02
1
R16
R17
CR06
MA2/2
4
R15
CR05 C05
7
R22
10
R20
R21
R24
LIMIT
I STATOR
LIMIT
FRONT VIEW
Lim Istator card
P1
SEUIL
P2
Ramp
P3
GAIN
44
MA2/3
P03
0V
NT1950090/a-11/92 f:2/2
9
CR07
5
R18
R13
6
8
CR08
R26
12c
AVR
Model R630
CAUTION
Never energize the AVR when
the driver card is removed.
An overvoltage can appear and the power
transistor can be damaged.
1 - STARTING WITH MANUAL MODE CARD
- For initial start-up, the best is to use the manual mode
for testing the sensing wires between the generator and
the AVR.
- For this it is necessary to have a manual mode card
plugged in the AVR. If not, see directly §2.
- Short-circuit terminals 47and 48 (AVR terminal block).
- Set the potentiometer P2 on manual card maximum
CCW, start the prime mover up to the nominal speed.
- Turn slowly the potentiometer CW to obtain the nominal
voltage.
Start-up
R630
4 - ADJUSTMENTS
- Refer also to card descriptions.
- The AVR is normally preset in factory.
- The nominal voltage can be set by Vref (P5) on sensing
card. Fine adjustment can be made by an external voltage potentiometer (10KΩ), (terminals 21,22,23)
- If an adjustment must be moved, note carefully the original setting for resetting in case of problems.
- If the strap V/Hz of sensing card is on kV/Hz position,
the original setting is V/Hz and can be changed between
V/Hz and 2V/Hz by potentiometer P4.
-The stability is adjusted with the machine in factory. If
necessary, the response time can be changed by the
setting of potentiometer P4 of PID card.
- Other settings are difficult to adjust without specific
electronics equipments. It is better to not change them.
5 - FIELD FLASHING
- Check that the voltage between terminal 25 and 26 of
the AVR terminal block is about one volt.
- Generally, field flashing is not necessary, but in some
cases like long stop time or fault trip, it can be possible
that the voltage does not appear naturally.
In this case, connect a 12Vdc to 24Vdc voltage source to
the terminals 4 and 8 of AVR terminal block, + to 4 for a
short time and remove it when the voltage increases.
- If yes, remove the strap between terminals 47 and 48 of
AVR terminal block.
6 - PARALLEL OPERATION (1F)
- The voltage must reach the nominal value.
- The generator voltages must be as equal as possible.
- Go to §3
- Same for the droop. If it is not possible to measure it,
set the potentiometers P1 of the sensing cards all in the
same position (middle set for example).
If the droop setting is made from cosØ/KVAR card (when
used), see notice NT 1950080.
- Check the presence and the value of the three phases
at the AVR terminal block (terminals 1, 2, 3).
- Set the voltage to 5% above the nominal voltage.
2 - STARTING WITHOUT MANUAL MODE
CARD
- Start the prime mover up to the nominal speed..
- If the voltage does not appear, check wires between
AVR and the generator field (terminals 5 and 6 of AVR),
and the also the wires between AVR and power transformer (terminals 18 and 19 of AVR). Check also the fuse
inside the terminal 19 of AVR terminal block.
- If the voltage is too hight, check that the auxiliary voltage at the terminals 16 and 17 of AVR and the sensing
voltages at the terminals 1, 2, 3 of the AVR terminal
block are present.
- Adjust the nominal voltage with Vref (P5) of the sensing
card for the middle position of the external voltage potentiometer (if used).
- The reactive currents (KVAR) must be shared, immediatly after coupling, even the KW are not shared.
- If, immediatly after coupling, the current increases
abnormally, check if the parallel CT wires are not reversed
(9 et 10 of AVR terminal block).
- If the coupling is OK but if when the load increases, the
cosØ or the current have an abnormal value, check that
the sensing phases at the input of the AVR are right
connected. (U, V, W respectively to the terminals 1, 2, 3
if clockwise rotation or W, V, U, if counter clockwise
rotation).
3 - DE-ENERGIZING (optional)
- External contacts E01 and E02 must be used.
- E01 must be serie with terminal 19 of AVR (power
input) and is opened for de-energizing.
- E02 must short-circuit the booster output (if used)
(terminals 7 and 8 of AVR) and is closed for de-energizing.
NT1959000/a-11/92 f:1/2
45
AVR
Model R630
Start-up
R630
7 - PARALLEL WITH THE MAINS (2F)
9 - MANUAL OPERATION (if used)
- The generator and mains voltages must be as equal as
possible. (see §8 if MAIN I/O card is used). The contact
between terminals 33, 34 of AVR terminal block must
be closed at the same time as the coupling and will
remain closed as long as the generator is connected to
the mains.
It will be open when parallel between generators.
- If a manual mode card is used, it is possible to control
directly the field current of the generator.
- If, immediatly after coupling, the current increases abnormally, check if the parallel CT wires are not reversed
(9 et 10 of AVR terminal block).
- If the coupling is OK but if when the load increases, the
cosØ or the current have an abnormal value, check that
the sensing phases at the input of the AVR are right
connected. (U, V, W respectively to the terminals 1, 2, 3
if clockwise rotation or W, V, U, if counter clockwise
rotation).
- The PF value is normally factory set to 0.8. It can be
adjust by mean of potentiometer P2 on cosØ/KVAR card
or by mean of an external potentiometer (10KΩ-1W)
connected to AVR terminal block (27,28,29).
- If the KVAR regulation is required terminals 48 and 53
must be short-circuited and the KVAR can be set by
mean of potentiometer P1 on cosØ/KVAR card or by
mean of an external potentiometer (10KΩ-1W) connected
to AVR terminal block (30, 31, 32).
- For droop setting, see notice NT 1950080.
8 - VOLTAGE EQUALISATION (3F)
- The following procedure must be made one time to take
account of the mains transformer primary/secondary
ratio.
- At no load and mains voltage present at terminals 12,
13, 14 of the AVR terminal block.
- Short circuit terminals 35,36 of the AVR terminal block
- Adjust P1 of MAIN I/O card to have generator and
mains voltage as equal as possible.
- Remove the strap between terminals 35, 36 of the AVR
terminal block.
- The initial setting is made.
In normal operation the contact between terminals 35,
36 of the AVR terminal block must be closed with synchronizer operation and can be opened after coupling.
NT1959000/a-11/92 f:2/2
46
- In automatic mode, adjust the potentiometer P2 on
manual mode card to have the LEDs "HIGHT" and
"LOW" off and the LED OK ligthing. At this time the
manual setting is equal to the automatic channel control.
- Short-circuit the terminals 47,48 of the AVR terminal
block gives control to the manual channel and the field
current is adjusted by potentiometer P2 and/or by an
external optionnal potentiometer (10KΩ-1W) connected
to the terminals 30, 52, 23 of the AVR terminal block
cusor on 52 and hot point on 30.
- This mode can be used when initial start-up of the
generator, to make test after problems or when operating
with the mains. It cannot be used when solo operation
because it is not possible to follow the load variations.
- When coupling with the mains on load, if trip of the
generator occurs, an overvoltage may occurs due to the
fact that the field current setting is too hight regarding the
load of the generator. On this case, an internal circuit of
the card decreases the field current to limit the overvoltage approximatively to 110% of nominal. LED
"LIMIT" on front of the card will light. The setting of field
current must be reset manually to the no load value and
the LED "LIMIT" will switch off.
Related documents