Download Improved power quality and productivity in an iron ore mine by

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ohm's law wikipedia , lookup

Electric power system wikipedia , lookup

Electrification wikipedia , lookup

Distributed control system wikipedia , lookup

Power factor wikipedia , lookup

Electrical ballast wikipedia , lookup

Resilient control systems wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Opto-isolator wikipedia , lookup

Current source wikipedia , lookup

Control system wikipedia , lookup

Power inverter wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Rectifier wikipedia , lookup

Power engineering wikipedia , lookup

Power MOSFET wikipedia , lookup

History of electric power transmission wikipedia , lookup

Triode wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electrical substation wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Islanding wikipedia , lookup

Surge protector wikipedia , lookup

Voltage regulator wikipedia , lookup

Stray voltage wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Buck converter wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Mains electricity wikipedia , lookup

Voltage optimisation wikipedia , lookup

Transcript
Improved power quality and productivity in an iron ore mine
by means of SVC
In 2009, an SVC supplied by ABB was commissioned in the
LKAB iron ore mine at Kirunavaara in the north of Sweden.
The SVC, rated at 0-35 Mvar at 6.3 kV, has the purpose of
improving power quality at the 145 kV Point of Common
Coupling (PCC) as well as inside the mine by reducing voltage
fluctuations and harmonics. As a direct benefit, with the SVC
in operation, the ore hoisting capacity has risen, as well, making the extracting process more efficient than before.
In the demanding environment of an iron ore mine, special
focus was given to creeping distances of support insulators
of outdoor equipment due to iron dust. Likewise, as the mine
is situated north of the Arctic Circle, focus was given to snow
clearance in winter time, as well as surrounding temperatures
down to -50 C.
Mine loads
In the underground mine of LKAB, iron ore is brought to the
surface by a total of seven mine hoists, each driven by a 4.3 MW
thyristor equipped 6-pulse DC drive and representing a fast
varying load affecting the whole supply system. The load cycle
consists of 3 different phases: acceleration, full speed operation and retardation. A typical load cycle duration is about 90 sec.
Before the advent of the SVC, due to insufficient strength of
the feeding grid, simultaneous operation of the drives was seriously restricted, preventing the full capacity of the hoists to
be utilized. Only 3% of voltage variations are permitted at the
145 kV PCC. Thus, to limit the voltage variations at the PCC
to an acceptable level, only one mine hoist could be started
at a time, resulting in reduced productivity. With a planned
extension of production capacity from 25 Mtonnes annually to
35 Mtonnes, the situation was aggravated further.
Due to the rapid load variations, conventional mechanically
switched capacitors (MSC) were ruled out for voltage control
of the drives.
With the SVC in operation, the voltage feeding the drives is
supported at all times, with voltage sag never exceeding 3%
at the 6.3 kV bus. Under these conditions, the mine hoists
can be utilized more efficiently, cutting the total load cycle
from previously 96 seconds to 72 seconds, an improvement
of hoisting capacity by some 30%. One year of operational
experience has corroborated this result, with a noted increase
in hoisting capacity by 25-30%.
145 kV
48 MVA
6.3 kV
Load
Load
Load
Load
Load
Load
Mine hoists:
P max = 4.3 MW
Qmax = 6.6 Mvar
5th
10 Mvar
7th
5 Mvar
TCR
12th
35 Mvar 20 Mvar
Single-line dagram, SVC and mine hoists
Load
Control system
The control system is based on the ABB MACH 2 concept,
which is a system of both hardware and software specifically
developed for power applications. The MACH 2 concept is
built around an industrial PC with add-in boards and I/O racks
connected through standard type field busses like CAN and
TDM.
−− Closed loop control, based on power factor control, Mvar
control or voltage control on the 6.3 kV bus;
− − Open loop reactive power control.
Operating experiences
The main goal of the SVC installation is to reduce voltage
variations on the 6.3 kV and 145 kV bus bars. A comparison
between the voltage variations on the 6.3 kV busbar without
the SVC as well as with the SVC in operation at approximately
30 MW hoist load is shown in the graphs. It can be seen that
the voltage variations have been reduced from typically -/+ 10%
down to -/+ 2%. An increase of hoisting capacity by 25-30%
has been noted.
Measured
values
6.3 kV
145 kV
6.3 kV
145 kV
3%
3%
3%
1.3%
Power factor
0.98
-
0.998
-
Total harmonic
distortion, voltage
4.8%
1.5%
3.2%
0.8%
Total harmonic
distortion, current
5%
5%
2%
2%
ABB AB
FACTS
SE-721 64 Västerås, SWEDEN
Phone: +46 (0)21 32 50 00
Fax:
+46 (0)21 32 48 10
www.abb.com/FACTS
3800
3600
3400
T
3200
09-10-29
09:30:00
09-10-29
09:35:00
09-10-29
09:40:00
09-10-29
09:45:00
09-10-29
09:50:00
09-10-29
09:55:00
09-10-29
10:00:00
09-10-29
10:05:00
09-10-29
10:10:00
U1 Min
U1 Max
U [V ]
4000
3800
3600
3400
T
3200
08-11-28
08:20:00
08-11-28
08:25:00
08-11-28
08:30:00
08-11-28
08:35:00
08-11-28
08:40:00
Bus voltage variation without SVC
(Blue: maximum values; black: minimum values)
Max voltage variations
For more information please contact:
U1 Min
U1 Max
U [V ]
4000
Bus voltage variation with SVC
(Blue: maximum values; black: minimum values)
There are two SVC control modes available:
Required
values
Performance results
The contractual requirements on the performance of the SVC
are listed in the left column below, together with the actually
measured values with the SVC in operation. As can be seen,
the SVC fulfils its tasks, as well as actually surpasses them.
Main technical data, SVC
Controlled voltage
6.3 kV
Dynamic rating
0-35 Mvar (capacitive)
Harmonic filters
5 th harmonic / 10 Mvar
7 th harmonic / 5 Mvar
12 th harmonic / 20 Mvar
Control system
- Closed loop control, based on power factor control, Mvar control or voltage control on the 6.3 kV bus;
- Open loop reactive power control
Thyristor valve
Water cooled, PCT type thyristors,
indirect light firing
Application Note A02-0226 E, 2011-10
Main design features
The SVC consists of a Thyristor Controlled Reactor (TCR)
rated at 6.3 kV, 35 Mvar, in parallel with three harmonic filters
tuned to the 5th, 7th, and 12th harmonics. The total reactive
power yield of the filters is 35 Mvar at 50 Hz, giving the SVC
an overall control range of 0-35 Mvar capacitive, continuously
variable. For proper design of the harmonic filters, not only
the grid impedance was taken into consideration but also the
reactance of a 250 m cable connection between the feeding
switchgear and the SVC. The 12th harmonic filter has a highpass character, enabling it to damp the 11th, 13th and higher
harmonics, as well.